Hidrojen yakit hucreli arac istasyonlari 700 bar basincli gaseous H2 sunar. H2 LFL percent 4, MIE 0.02 mJ (statik elektrik yeter) ve flame neredeyse gorunmez. NFPA 2 Hydrogen Technologies Code setback, ventilation, detection ve cadir yapi kurallarini verir.
H2 Fiziksel Ozellikleri
- LFL: percent 4 (40,000 ppm)
- UFL: percent 75 (cok genis)
- MIE: 0.02 mJ (statik elektrik)
- Auto-ignition: 500 C
- Flame visibility: Gunduzde gorulmez (UV/IR detektor gerekli)
- Buoyancy: 14x hava-daha hafif - hizla yukari cikar
NFPA 2 Setback Distances
- Bina acik: 3-10 m (kapasiteye gore)
- Ignition kaynagi: 8 m
- Public way: 5-15 m
- Gaz tankt (LPG, doga gazi): 10 m
- Dispenser-tank: 3 m min
- Overhead clearance: 6 m acik gokyuzu
700 bar Storage
- Tip IV tank: Polimer liner + karbon fiber kompozit
- Calisma basinci: 875 bar (nominal 700)
- TPRD (Thermal Pressure Relief): 110 C ergiyen plug
- Burst pressure: 1600 bar min
- Impact testi: Mermi, bonfire, drop
Leak Detection
- H2 sensor: Catalytic bead veya electrochemical
- Setpoint: 25 percent LFL alarm, 50 percent ESD
- UV/IR flame detector: H2 flame UV'de gorulur
- Ses detektoru: Ultrasonic gas leak (40 kHz)
- Dispenser ESD: Hose breakaway, auto-shutoff
Deflagration ve Jet Fire
- Jet fire: 1-2 m flame, 300 kW/m2 radiation
- Deflagration: Canopi altinda riskli - venting gerekli
- DDT (Def-Det Transition): Uzun borularda mumkun
- Acil durum plan: Izole alan, tahliye 30 m
- Firewater: H2 sonduremezsin, sadece radyasyon kontrol

H2 Istasyon SprinkCalc ile
SprinkCalc hidrojen dolum istasyonu setback mesafesi, leak detection debiler, radyasyon koruma ve NFPA 2 layout kontrolu yapar.
SprinkCalc'i App Store'dan indir
Kaynaklar & İleri Okuma
NFPA 2, NFPA 55, ISO 19880-1, HyARC, CSA HGV. NFPA 2 Hydrogen kodu.