Plastik (polietilen, polipropilen, PVC) hammadde (pellet/granul) cok yuksek HRR (1000 MJ/kg) ile yanar. Dunya'da LyondellBasell, BASF, SABIC, Petkim depolarinda ESFR K=25.2 (K360) sprinkler kullanilir. 12 m yigim yukseklik, 75 psi nozzle basinc ve 12 tetiklemeli oda kritik kriterlerdir.
Plastik Grup Siniflandirma
- Group A plastik: PE, PP, PS, PVC, ABS
- Group B plastik: Butadien, acrylonitrile
- Group C plastik: PVC sertlesmis
- Elastomer: Group A esdeger
- Expanded (EPS): En kotu - hizli yanma
ESFR K=25.2 Sistem
- K-factor: 25.2 (SI) / K360 (US)
- Nozzle basinci: 75 psi (5.2 bar)
- Debi per nozzle: 725 L/min
- Design area: 12 sprinkler acik
- Toplam debi: 12 × 725 = 8700 L/min
- Hose allowance: 500 gpm (1900 L/min)
Yigim Tasarimi
- Max yigim: 12.2 m (40 ft) NFPA 13 limit
- Aisle genislik: 2.4 m (8 ft) min
- Yigim duzen: Solid pile veya rack
- Flue space: 150 mm transverse, 75 mm longitudinal
- Tavan yukseklik: 13.7 m (45 ft)
Alternatif Koruma
- In-rack sprinkler: K=14 level spraye
- CMSA K=16.8: Daha dusuk basinc, eski
- High-expansion foam: Ozel tasarim gerekli
- Kartonlu depo: Class IV commodity
- Open shelving: ESFR yeterli olabilir
Gerekli Tesisatlar
- Pompa: 12,000 L/min @ 9 bar
- Tank: 8 saatlik: 12,000 × 60 × 8 = 5,760,000 L = 5760 m3? Hayir - 60 dk × 12,000 = 720 m3
- Riser boru: DN200-250
- Zon valv: 4 zona ayrim
- Detection: Sprinkler + smoke vent

Plastik Depo SprinkCalc ile
SprinkCalc ESFR K=25.2 tasarim, 75 psi nozzle, 12 sprinkler room, pompa debisi ve NFPA 13 Group A plastik zonlama hesabi yapar.
SprinkCalc'i App Store'dan indir
Kaynaklar & İleri Okuma
NFPA 13, FM DS 8-9, FM DS 8-1, Viking ESFR-25, Tyco ESFR. NFPA 13 Sprinkler kodu.