Soguk depolar (-25 C freezer, +2 C chiller) amonyak (NH3) soğutucu ile calisir. Amonyak yanici (LFL percent 15) ve zehirlidir (IDLH 300 ppm). Donma nedeniyle wet-pipe sprinkler calismaz; NFPA 13 dry-pipe veya pre-action sistem kullanilir. IIAR-2 machinery room ve havalandirma kurallarini tanimlar.
Dry-Pipe Sprinkler Tasarimi
- Air pressure: 25-50 psi borunda
- Water delivery time: max 60 sn (sistem zorunlulugu)
- Sistem hacmi limit: 750 gal (2840 L)
- Sprinkler: Upright veya dry pendant
- Low-point drum drips: Su birikimi dren
IIAR-2 Machinery Room
- Ayrim: 2 saat firewall
- Havalandirma: Normal 0.5 ACH, emergency 30 ACH
- NH3 detektor: 25 ppm alarm, 150 ppm high alarm
- Tahliye cikisi: 2 bagimsiz kapi
- ESD: Emergency shutdown butonu disaridan
Amonyak Yangin/Patlama Riski
- LFL: percent 15 (15,000 ppm)
- UFL: percent 28
- MIE: 680 mJ (cok yuksek)
- Patlama basinci: Pmax 6 bar
- Ateslenme zorlugu: Genelde yangin olmaz, siki alan gerekir
Havalandirma Hesabi
500 m2 machinery room, 30 ACH emergency:
- Volume: 500 × 4 = 2000 m3
- Debi: 2000 × 30 = 60,000 m3/h
- Fan: 2 × 30,000 m3/h (redundancy)
- Exhaust: Cati seviyesine - sicak gaz yukari
- Inlet: Dis duvar alt seviyede, oto damper

Soguk Depo MEP Calc ile
MEP Calc soguk depo amonyak machinery room havalandirma debisi, NH3 detektor setpointleri ve dry-pipe sistem hacim hesabini IIAR-2/NFPA 13 uyarinca yapar.