Tahil silosu 20.000-100.000 ton bugday depolar, bucket elevator ile 30-50 m yukarli-asagi tasima yapar. Tahil tozu (nisasta agirlikli) ince parcaciklar LEL 40 g/m3, Kst 100-200 bar.m/s. ABD'de yilda 5-10 silo patlamasi meydana gelir. NFPA 61 tarim ve gida tesisleri kurallarini verir.
Tahil Toz Ozellikleri
- Bugday tozu: Kst 115 bar.m/s (ST1)
- Misir tozu: Kst 150
- LEL: 40-60 g/m3
- MIE: 20-50 mJ
- Auto-ignition: 450 C yigilmis
Bucket Elevator Risk
- Kayis kaymasi: 60-100 C surtunme
- Yatak arizasi: Spark kaynak
- Tramp metal: Yabanci cisim manyetik separator
- Belt alignment: Weekly kontrol
- Hiz monitor: Slip %10 trip
NFPA 61 Deflagration Vent
- Silo: Top vent Av/V = 0.1 m2/m3
- Elevator: Leg her 6 m vent
- Conveyor: Kapak hafif, 0.5 kPa acilis
- Isolation: Rotary valve + chemical barrier
- Ball check valve: Inlet suppression
Dust Collection ve Housekeeping
- Aspirasyon: Her transfer noktasi enclosed
- Baghouse: 1 m3/s tipik silo
- Housekeeping: 0.5 mm toz 20 percent alan
- Temizlik: Vacuum, basinçli hava YASAK
- Degisim: Vardiya sonu
Turk ve Dunya Kazalari
- Polatli TMO 2018: Bucket elevator - 1 oldu
- Imperial Sugar GA 2008: 14 oldu
- DeBruce Grain KS 1998: 7 oldu
- Konya Cumra: TMO buyuk silo komplekss
- Trakya: Bugday hasatli depo fabrika

Silo SprinkCalc ile
SprinkCalc tahil silosu deflagration vent alani, bucket elevator spark detection ve NFPA 61 ilkeleri ile sprinkler koruma hesabi yapar.
SprinkCalc'i App Store'dan indir
Kaynaklar & İleri Okuma
NFPA 61, NFPA 68, NFPA 654, OSHA 1910.272, FM DS 7-75. NFPA 61 Agricultural and Food Products.