    <item>
      <title>NFPA 11 Supplementary Foam Hose Streams and Monitors</title>
      <link>https://selvi.org/en/blog/foam-flammable-liquids/nfpa-11-supplementary-hose-monitors</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/foam-flammable-liquids/nfpa-11-supplementary-hose-monitors</guid>
      <description>NFPA 11-2024 5.9 and 5.2.4: number and duration of supplementary foam hose streams, monitors and handlines as primary tank protection, the 1.5 factor.</description>
      <category>Foam &amp; Flammable Liquids</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>NFPA 11 Subsurface Foam Injection: Outlets and Velocity</title>
      <link>https://selvi.org/en/blog/foam-flammable-liquids/nfpa-11-subsurface-foam-injection</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/foam-flammable-liquids/nfpa-11-subsurface-foam-injection</guid>
      <description>NFPA 11-2024 subsurface and semi-subsurface foam injection: where it is allowed, outlet table, 3/6 m/s velocity limits, 4.1 mm/min and discharge times.</description>
      <category>Foam &amp; Flammable Liquids</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>NFPA 11 High-Expansion Foam: Submergence and Rate</title>
      <link>https://selvi.org/en/blog/foam-flammable-liquids/nfpa-11-high-expansion-foam</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/foam-flammable-liquids/nfpa-11-high-expansion-foam</guid>
      <description>NFPA 11-2024 7.12: high-expansion foam depth and submergence volume, Table 7.12.7.1 times, the leakage and sprinkler discharge formula, worked example.</description>
      <category>Foam &amp; Flammable Liquids</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>NFPA 11 Foam Concentrate Supply and Proportioning</title>
      <link>https://selvi.org/en/blog/foam-flammable-liquids/nfpa-11-concentrate-supply-proportioning</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/foam-flammable-liquids/nfpa-11-concentrate-supply-proportioning</guid>
      <description>NFPA 11-2024 Chapter 4: foam concentrate quantity, 24-hour reserve, storage tanks, compatibility, proportioner types and concentrate pump rules.</description>
      <category>Foam &amp; Flammable Liquids</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>NFPA 11 Floating Roof Seal Protection: Over and Under</title>
      <link>https://selvi.org/en/blog/foam-flammable-liquids/nfpa-11-floating-roof-seal-protection</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/foam-flammable-liquids/nfpa-11-floating-roof-seal-protection</guid>
      <description>NFPA 11-2024 floating roof seal protection: top-of-seal 12.2 mm/min for 20 min, below-seal 20.4 mm/min for 10 min, foam dam, spacing and internal roofs.</description>
      <category>Foam &amp; Flammable Liquids</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>NFPA 11 Fixed-Roof Tank Foam: Application Rate and Time</title>
      <link>https://selvi.org/en/blog/foam-flammable-liquids/nfpa-11-fixed-roof-tank-foam</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/foam-flammable-liquids/nfpa-11-fixed-roof-tank-foam</guid>
      <description>NFPA 11-2024 fixed foam outlets on cone-roof tanks: 4.1 mm/min rate, 30/55 min times, outlet count by diameter, the 70 % rule and a worked example.</description>
      <category>Foam &amp; Flammable Liquids</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>NFPA 11 Dikes, Spill Areas and Loading Racks</title>
      <link>https://selvi.org/en/blog/foam-flammable-liquids/nfpa-11-dike-spill-loading-rack</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/foam-flammable-liquids/nfpa-11-dike-spill-loading-rack</guid>
      <description>NFPA 11-2024 foam for diked areas, nondiked spills and loading racks: 4.1 and 6.5 mm/min, 15/20/30 min times, low-level outlet spacing and examples.</description>
      <category>Foam &amp; Flammable Liquids</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>NFPA 11 Acceptance Tests and ITM Under NFPA 25</title>
      <link>https://selvi.org/en/blog/foam-flammable-liquids/nfpa-11-acceptance-tests-itm</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/foam-flammable-liquids/nfpa-11-acceptance-tests-itm</guid>
      <description>NFPA 11-2024 Chapters 12 and 13: flushing, hydrostatic and discharge tests, the −0/+30 % proportioning tolerance, signs, and ITM handed to NFPA 25.</description>
      <category>Foam &amp; Flammable Liquids</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>Foam Extinguishing in BYKHY: Articles 98 and 122</title>
      <link>https://selvi.org/en/blog/foam-flammable-liquids/turkey-foam-extinguishing-articles-98-122</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/foam-flammable-liquids/turkey-foam-extinguishing-articles-98-122</guid>
      <description>The Turkish Fire Protection Regulation gives no foam numbers: what Articles 98 and 122 require, the Guide's notes, new 98(7) and choosing NFPA 11 or EN 13565-2.</description>
      <category>Foam &amp; Flammable Liquids</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>Detection in Existing Buildings: BYKHY 143 and 161</title>
      <link>https://selvi.org/en/blog/fire-detection/turkey-existing-buildings-detection</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/fire-detection/turkey-existing-buildings-detection</guid>
      <description>Fire detection in existing buildings in Turkey: Articles 161 and 143, overlap with the Annex 7 annulment, single panel rule, cables, lifts and deadlines.</description>
      <category>Fire Detection</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>BYKHY Underground Tanks and Filling Points (Article 120)</title>
      <link>https://selvi.org/en/blog/foam-flammable-liquids/turkey-underground-tanks-article-120</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/foam-flammable-liquids/turkey-underground-tanks-article-120</guid>
      <description>BYKHY Article 120: underground tank cover (60 cm soil, 10 cm concrete), traffic slab, Annex 12/Ç distances, 4 m vent, tank fittings and filling points.</description>
      <category>Foam &amp; Flammable Liquids</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>BYKHY Liquid Storage in Buildings: Annex 12/A and 12/B</title>
      <link>https://selvi.org/en/blog/foam-flammable-liquids/turkey-liquid-storage-in-buildings</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/foam-flammable-liquids/turkey-liquid-storage-in-buildings</guid>
      <description>BYKHY Article 118: 120-minute liquid warehouses, basement ban, 5 stacks 3 m apart, 12,500 litres IA equivalent, Annex 12/A and Annex 12/B for factory stores.</description>
      <category>Foam &amp; Flammable Liquids</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>BYKHY Hazard Zones for Liquids: Articles 116 and 117</title>
      <link>https://selvi.org/en/blog/foam-flammable-liquids/turkey-hazard-zones-articles-116-117</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/foam-flammable-liquids/turkey-hazard-zones-articles-116-117</guid>
      <description>BYKHY Articles 116 and 117: Zone 0, 1 and 2 definitions, equipment limits and zone sizes at stores, tanks, filling points and fuel stations in Turkey.</description>
      <category>Foam &amp; Flammable Liquids</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>BYKHY Fuel Station Requirements (Article 121)</title>
      <link>https://selvi.org/en/blog/foam-flammable-liquids/turkey-fuel-station-article-121</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/foam-flammable-liquids/turkey-fuel-station-article-121</guid>
      <description>BYKHY Article 121: underground tanks only, 45,000 litres per tank and 250,000 per station, dispenser rules, extinguishers and Annex 13 distances in the Guide.</description>
      <category>Foam &amp; Flammable Liquids</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>BYKHY Flammable Liquid Classes: Article 113</title>
      <link>https://selvi.org/en/blog/foam-flammable-liquids/turkey-flammable-liquid-classes</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/foam-flammable-liquids/turkey-flammable-liquid-classes</guid>
      <description>Classes IA to IIIB under Article 113 of the Turkish Fire Protection Regulation: flash and boiling point limits, the heated-liquid rule and exemptions.</description>
      <category>Foam &amp; Flammable Liquids</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>BYKHY Articles 82–83: Emergency Control and Cables</title>
      <link>https://selvi.org/en/blog/fire-detection/turkey-emergency-control-cables</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/fire-detection/turkey-emergency-control-cables</guid>
      <description>Turkish regulation Articles 82–83: fire-mode door, lift and pressurisation controls, panel priority, 60-minute fire-resistant and halogen-free cables.</description>
      <category>Fire Detection</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>BYKHY Articles 78–80: Sprinkler, Gas and Smoke Control</title>
      <link>https://selvi.org/en/blog/fire-detection/turkey-fire-alarm-interfaces</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/fire-detection/turkey-fire-alarm-interfaces</guid>
      <description>Turkish regulation Articles 78–80: wiring sprinkler, gaseous suppression, smoke control and pressurisation signals to the fire panel; cause and effect.</description>
      <category>Fire Detection</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>BYKHY Articles 76–77: Alarm Signalling and Panels</title>
      <link>https://selvi.org/en/blog/fire-detection/turkey-alarm-signalling-control-panel</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/fire-detection/turkey-alarm-signalling-control-panel</guid>
      <description>Turkish regulation Articles 76 and 77: the three alarm channels to panel staff, occupants and fire brigade, and where control and repeater panels go.</description>
      <category>Fire Detection</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>BYKHY Article 84: Fire Alarm Testing and Maintenance</title>
      <link>https://selvi.org/en/blog/fire-detection/turkey-fire-alarm-testing-article-84</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/fire-detection/turkey-fire-alarm-testing-article-84</guid>
      <description>Turkish regulation Article 84: who is responsible for periodic checks, tests and maintenance of fire detection, acceptance, out-of-service rules and records.</description>
      <category>Fire Detection</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>BYKHY Article 81: Audible and Visual Alarm Devices</title>
      <link>https://selvi.org/en/blog/fire-detection/turkey-audible-visual-alarms-article-81</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/fire-detection/turkey-audible-visual-alarms-article-81</guid>
      <description>Turkish regulation Article 81: sounder levels (ambient +15 dBA, 75 dBA), visual alarms, pre-alarm limits, phased evacuation and voice alarm thresholds.</description>
      <category>Fire Detection</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>BYKHY Article 75: Automatic Detection and Annex 7</title>
      <link>https://selvi.org/en/blog/fire-detection/turkey-article-75-automatic-detection</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/fire-detection/turkey-article-75-automatic-detection</guid>
      <description>Turkish regulation Article 75 and Annex 7: when automatic fire detection is mandatory, the annulled rows, call point rules and TS EN 54-14 layout.</description>
      <category>Fire Detection</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>BYKHY Annex 11 and Article 115: Liquid Quantity Limits</title>
      <link>https://selvi.org/en/blog/foam-flammable-liquids/turkey-annex-11-maximum-liquid-quantities</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/foam-flammable-liquids/turkey-annex-11-maximum-liquid-quantities</guid>
      <description>Turkish Fire Protection Regulation: Annex 11 notification and permit thresholds, Article 114 filling rule, Article 115 maximum quantities in rooms and shops.</description>
      <category>Foam &amp; Flammable Liquids</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>BYKHY Aboveground Tanks: Annex 12/C Distances and Bunds</title>
      <link>https://selvi.org/en/blog/foam-flammable-liquids/turkey-aboveground-tank-distances-bunds</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/foam-flammable-liquids/turkey-aboveground-tank-distances-bunds</guid>
      <description>BYKHY Article 119: aboveground tank safety distances (Annex 12/C), bund volume and wall rules, protection zone and Annex 12/D for portable containers in Turkey.</description>
      <category>Foam &amp; Flammable Liquids</category>
      <pubDate>Sun, 01 Nov 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>Tree, Loop and Grid Sprinkler Pipework: NFPA 13 vs EN 12845</title>
      <link>https://selvi.org/en/blog/guides/tree-loop-grid-sprinkler-pipework-hydraulic-calculation</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/guides/tree-loop-grid-sprinkler-pipework-hydraulic-calculation</guid>
      <description>Sprinkler pipe layouts: tree, loop and grid. Dry system bans, most unfavourable and favourable areas, 1.2√A, pipe tables; NFPA 13 and EN 12845 side by side.</description>
      <category>Comprehensive Guides</category>
      <pubDate>Mon, 26 Oct 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>ESFR Sprinklers: NFPA 13 and EN 12845 Tables and Limits</title>
      <link>https://selvi.org/en/blog/guides/esfr-sprinklers-nfpa-13-en-12845-tables-and-prohibitions</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/guides/esfr-sprinklers-nfpa-13-en-12845-tables-and-prohibitions</guid>
      <description>ESFR sprinklers to NFPA 13-2025 and EN 12845-2: every design table, layout rules, wet pipe only, water supply and 63 prohibitions, with clause numbers.</description>
      <category>Comprehensive Guides</category>
      <pubDate>Mon, 26 Oct 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>Self-Storage Fire Protection: NFPA 13 and Turkish BYKHY</title>
      <link>https://selvi.org/en/blog/nfpa/self-storage-fire-protection</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/nfpa/self-storage-fire-protection</guid>
      <description>Self-storage fire protection: NFPA 13 OH2/EH1 hazard class, water demand, Turkish BYKHY compliance, smoke control, sprinkler type, pump sizing, checklist.</description>
      <category>NFPA Guides</category>
      <pubDate>Mon, 12 Oct 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>IG-541 vs HFC-227ea (FM-200) vs FK-5-1-12 (Novec 1230)</title>
      <link>https://selvi.org/en/blog/comparison/ig-541-vs-hfc-227ea-vs-fk-5-1-12</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/comparison/ig-541-vs-hfc-227ea-vs-fk-5-1-12</guid>
      <description>IG-541 vs HFC-227ea (FM-200) vs FK-5-1-12 per NFPA 2001-2025: design concentration, NOAEL and O₂ limits, discharge time, storage, quantity per m³ at 21 °C.</description>
      <category>Comparison</category>
      <pubDate>Mon, 12 Oct 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>FM DS 8-33 Carousel Storage and Retrieval Protection</title>
      <link>https://selvi.org/en/blog/fmglobal/ds-8-33-carousel-storage</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/fmglobal/ds-8-33-carousel-storage</guid>
      <description>FM DS 8-33 carousels: 6-12 mm/min ceiling densities over 186 m2, 84 L/min per in-rack sprinkler, 1.1 m separation and the horizontal carousel exception.</description>
      <category>FM Global Guides</category>
      <pubDate>Mon, 12 Oct 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>FM DS 8-30 Carpet Storage and In-Rack Sprinklers</title>
      <link>https://selvi.org/en/blog/fmglobal/ds-8-30-carpet-storage</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/fmglobal/ds-8-30-carpet-storage</guid>
      <description>FM DS 8-30 carpet storage: in-rack sprinklers above 12 ft in standard racks, the 22 gpm rule, 36 in. clearance, a 500 gpm hose allowance and a 2-hour supply.</description>
      <category>FM Global Guides</category>
      <pubDate>Mon, 12 Oct 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>FM DS 8-24 Idle Pallet Storage: Distances and Protection</title>
      <link>https://selvi.org/en/blog/fmglobal/ds-8-24-idle-pallet-storage</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/fmglobal/ds-8-24-idle-pallet-storage</guid>
      <description>FM DS 8-24 idle pallet storage: outdoor separation from 15 to 150 ft, the 5 ft limit in production areas, plastic pallets as UUP and Table 3 protection.</description>
      <category>FM Global Guides</category>
      <pubDate>Mon, 12 Oct 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>FM DS 8-23: Rolled Nonwoven Fabric Storage Protection</title>
      <link>https://selvi.org/en/blog/fmglobal/ds-8-23-rolled-nonwoven-fabric-storage</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/fmglobal/ds-8-23-rolled-nonwoven-fabric-storage</guid>
      <description>FM DS 8-23 rolled nonwoven fabric: 30 ft ceiling limit on the floor, 12 K14.0 sprinklers at 75 psi in racks, no dry-pipe systems and the loft factor 25 rule.</description>
      <category>FM Global Guides</category>
      <pubDate>Mon, 12 Oct 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>FM DS 8-22 Baled Storage: Fiber, Waste Paper, Plastics</title>
      <link>https://selvi.org/en/blog/fmglobal/ds-8-22-baled-fiber-storage</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/fmglobal/ds-8-22-baled-fiber-storage</guid>
      <description>FM DS 8-22 baled storage: 1,000 m2 outdoor piles and 6.1 m height, 150 m2 indoor piles, the 30% plastics threshold and the 2-hour water supply requirement.</description>
      <category>FM Global Guides</category>
      <pubDate>Mon, 12 Oct 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>FM DS 3-7 Fire Pump Acceptance and Annual Test Criteria</title>
      <link>https://selvi.org/en/blog/fmglobal/ds-3-7-pump-acceptance-annual-test</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/fmglobal/ds-3-7-pump-acceptance-annual-test</guid>
      <description>FM DS 3-7 fire pump acceptance test: six flow points to 150%, 6 manual and 6 automatic starts, a 1-hour run, 65% pressure at 150% flow and speed correction.</description>
      <category>FM Global Guides</category>
      <pubDate>Mon, 12 Oct 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>FM DS 3-29: Reliable Fire Protection Water Supply</title>
      <link>https://selvi.org/en/blog/fmglobal/ds-3-29-reliable-water-supply</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/fmglobal/ds-3-29-reliable-water-supply</guid>
      <description>FM DS 3-29 reliable water supply: preference order of 6 supply types, 8 conditions that undermine reliability and the loss data behind 80% of failures.</description>
      <category>FM Global Guides</category>
      <pubDate>Mon, 12 Oct 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>FM DS 3-26 Water Demand: Four Worked Examples</title>
      <link>https://selvi.org/en/blog/fmglobal/ds-3-26-water-demand-worked-example</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/fmglobal/ds-3-26-water-demand-worked-example</guid>
      <description>FM DS 3-26 water demand step by step: HC-1/2/3 density and area, 950 and 1,900 L/min hose allowances, 60 minutes and four worked examples from 91 to 450 m3.</description>
      <category>FM Global Guides</category>
      <pubDate>Mon, 12 Oct 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>FM DS 2-81 ITM Frequency Table and Common Findings</title>
      <link>https://selvi.org/en/blog/fmglobal/ds-2-81-test-frequency-table</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/fmglobal/ds-2-81-test-frequency-table</guid>
      <description>FM DS 2-81 ITM frequencies: weekly valve checks, monthly physical tests, 3-yearly full-flow trip tests, the 120 ml obstruction rule and 30-minute diesel churn.</description>
      <category>FM Global Guides</category>
      <pubDate>Mon, 12 Oct 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>FM DS 2-0 Pipe Sizing: C-Values, Delivery Time, Tests</title>
      <link>https://selvi.org/en/blog/fmglobal/ds-2-0-pipe-sizing-hydraulic-criteria</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/fmglobal/ds-2-0-pipe-sizing-hydraulic-criteria</guid>
      <description>FM DS 2-0 pipe sizing: default C=120 and C=100, 1 in. (25 mm) minimum size, grid and loop limits, 60 s water delivery and the 13.8 bar hydrostatic test.</description>
      <category>FM Global Guides</category>
      <pubDate>Mon, 12 Oct 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>BYKHY for Existing Buildings: Which Provisions Apply</title>
      <link>https://selvi.org/en/blog/bykhy/bykhy-existing-buildings</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/bykhy/bykhy-existing-buildings</guid>
      <description>BYKHY for existing buildings: the 19.12.2007 permit cut-off, change of use and major alterations, Part Ten escape rules and Article 165(1) sprinkler thresholds.</description>
      <category>BYKHY</category>
      <pubDate>Mon, 12 Oct 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>Sprinkler Commissioning Protocol: NFPA 13 Acceptance Tests</title>
      <link>https://selvi.org/en/blog/nfpa/sprinkler-commissioning-protocol</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/nfpa/sprinkler-commissioning-protocol</guid>
      <description>Sprinkler commissioning under NFPA 13-2025 Chapter 29: hydrostatic test (200 psi, 2 hours), flushing, dry pipe valve trip test, main drain test, checklist.</description>
      <category>NFPA Guides</category>
      <pubDate>Thu, 08 Oct 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>NFPA Standards List: First and Current Edition Years (2026)</title>
      <link>https://selvi.org/en/blog/nfpa/nfpa-standards-edition-years</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/nfpa/nfpa-standards-edition-years</guid>
      <description>First, current and next edition years of all 246 active NFPA codes and standards, and where the 90 consolidated and 80 withdrawn documents went.</description>
      <category>NFPA Guides</category>
      <pubDate>Mon, 05 Oct 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>Hose Reel and Hydrant Water Demand: BYKHY Annex 8/C</title>
      <link>https://selvi.org/en/blog/bykhy/hose-reel-and-hydrant-extra-water-demand</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/bykhy/hose-reel-and-hydrant-extra-water-demand</guid>
      <description>Water added to the tank for hose cabinets and hydrants: BYKHY Annex 8/C, the four routes of Article 92 and TS EN 12845 9.2, 9.6.4, 9.3.2, with a worked example.</description>
      <category>BYKHY</category>
      <pubDate>Fri, 02 Oct 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>What Is a Fire Compartment? BYKHY Definition and Tables</title>
      <link>https://selvi.org/en/blog/bykhy/what-is-a-fire-compartment</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/bykhy/what-is-a-fire-compartment</guid>
      <description>Fire compartment under BYKHY: Article 4(tt) definition, Article 24 rules, Annex 1 hazard classes, Annex 4 maximum areas and Annex 3/B, 3/C fire resistance.</description>
      <category>BYKHY</category>
      <pubDate>Thu, 01 Oct 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>Why Fire Insurance Claims Are Denied: 3 Engineering Reasons</title>
      <link>https://selvi.org/en/blog/saha/insurance-claim-denial-reasons</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/saha/insurance-claim-denial-reasons</guid>
      <description>Unreported impairments, missing ITM records and occupancy drift from the design basis: three reasons fire claims are declined, and how to prevent them.</description>
      <category>Field Notes</category>
      <pubDate>Tue, 29 Sep 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>Sprinkler Installation Mistakes on Site: Illustrated Gallery</title>
      <link>https://selvi.org/en/blog/saha/sprinkler-installation-mistakes-gallery</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/saha/sprinkler-installation-mistakes-gallery</guid>
      <description>Deflector distance, duct and beam obstructions, painted heads, caps, escutcheons, orientation, hangers and storage clearance: 10 mistakes, sketched.</description>
      <category>Field Notes</category>
      <pubDate>Tue, 29 Sep 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>Sports Hall and Stadium Fire Protection: Smoke, Evacuation</title>
      <link>https://selvi.org/en/blog/cozumler/sports-hall-and-stadium-fire-protection</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/cozumler/sports-hall-and-stadium-fire-protection</guid>
      <description>Sports hall and stadium fire protection: classification, high ceilings, under-stand spaces, smoke control, water supply, PA integration, BYKHY and a checklist.</description>
      <category>Solution Guides</category>
      <pubDate>Tue, 29 Sep 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>Residential and Apartment Building Fire Protection</title>
      <link>https://selvi.org/en/blog/cozumler/residential-apartment-fire-protection</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/cozumler/residential-apartment-fire-protection</guid>
      <description>Residential fire protection: NFPA 13/13R and EN 16925, residential sprinklers, car parks and lockers, pressure, alarm and smoke control, BYKHY and a checklist.</description>
      <category>Solution Guides</category>
      <pubDate>Tue, 29 Sep 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>Quick-Response vs Standard-Response Sprinkler Selection</title>
      <link>https://selvi.org/en/blog/saha/quick-response-vs-standard-response-sprinklers</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/saha/quick-response-vs-standard-response-sprinklers</guid>
      <description>Quick vs standard response sprinklers: RTI, mandatory and prohibited uses, mixing rules, dry systems, ESFR and identifying them on site by SIN.</description>
      <category>Field Notes</category>
      <pubDate>Tue, 29 Sep 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>Plastics Injection Moulding Plant Fire Protection</title>
      <link>https://selvi.org/en/blog/cozumler/plastics-injection-moulding-plant-fire-protection</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/cozumler/plastics-injection-moulding-plant-fire-protection</guid>
      <description>Plastics moulding plant fire protection: classification, hydraulic units, dust, plastics storage and ESFR, water supply, smoke venting, BYKHY and a checklist.</description>
      <category>Solution Guides</category>
      <pubDate>Tue, 29 Sep 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>Pharmaceutical Plant and Cleanroom Fire Protection: ATEX</title>
      <link>https://selvi.org/en/blog/cozumler/pharmaceutical-plant-cleanroom-fire-protection</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/cozumler/pharmaceutical-plant-cleanroom-fire-protection</guid>
      <description>Pharma fire protection: cleanroom sprinklers, pressure cascade and smoke scenario, solvents and ATEX, clean agents, firewater retention, BYKHY and a checklist.</description>
      <category>Solution Guides</category>
      <pubDate>Tue, 29 Sep 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>Office Building Fire Protection — NFPA 13 and EN 12845</title>
      <link>https://selvi.org/en/blog/cozumler/office-building-fire-protection</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/cozumler/office-building-fire-protection</guid>
      <description>Office fire protection: hazard class, concealed voids, archives and car parks, water supply, alarm and smoke control interface, Turkish rules and a checklist.</description>
      <category>Solution Guides</category>
      <pubDate>Tue, 29 Sep 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>NFPA 13: System Components — Pipe, Fittings and Valves</title>
      <link>https://selvi.org/en/blog/nfpa13/nfpa-13-system-components-pipe-fittings-valves</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/nfpa13/nfpa-13-system-components-pipe-fittings-valves</guid>
      <description>NFPA 13 system components: pipe wall thickness by joining method, CPVC limits, fitting rules, indicating valves and control valve supervision.</description>
      <category>NFPA 13 Clause Guide</category>
      <pubDate>Tue, 29 Sep 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>NFPA 13: Scope, Purpose and How the Standard Is Organised</title>
      <link>https://selvi.org/en/blog/nfpa13/nfpa-13-scope-purpose-structure</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/nfpa13/nfpa-13-scope-purpose-structure</guid>
      <description>What NFPA 13 covers, what it leaves to NFPA 20, 22, 24 and 25, how it is organised and why edition differences matter, explained by an engineer.</description>
      <category>NFPA 13 Clause Guide</category>
      <pubDate>Tue, 29 Sep 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>NFPA 13: Residential Sprinklers</title>
      <link>https://selvi.org/en/blog/nfpa13/nfpa-13-residential-sprinklers</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/nfpa13/nfpa-13-residential-sprinklers</guid>
      <description>NFPA 13 residential sprinklers: where allowed, the four-adjacent-sprinkler and 0.1 gpm/ft² rule, deflector distances and differences from 13R and 13D.</description>
      <category>NFPA 13 Clause Guide</category>
      <pubDate>Tue, 29 Sep 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>NFPA 13: Obstruction Rules — Clause Guide</title>
      <link>https://selvi.org/en/blog/nfpa13/nfpa-13-obstruction-rules</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/nfpa13/nfpa-13-obstruction-rules</guid>
      <description>NFPA 13 obstruction rules: the beam rule, the three-times rule and 600 mm (24 in) cap, sprinklers under obstructions over 4 ft wide, EC, residential and ESFR.</description>
      <category>NFPA 13 Clause Guide</category>
      <pubDate>Tue, 29 Sep 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>NFPA 13: Extended Coverage (EC) Sprinklers</title>
      <link>https://selvi.org/en/blog/nfpa13/nfpa-13-extended-coverage-sprinklers</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/nfpa13/nfpa-13-extended-coverage-sprinklers</guid>
      <description>NFPA 13 EC sprinklers: listed square coverage up to 37.2 m² (400 ft²), 2.4 m minimum spacing, hydraulics on listed area and stricter obstruction rules.</description>
      <category>NFPA 13 Clause Guide</category>
      <pubDate>Tue, 29 Sep 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>NFPA 13: Definitions and Core Concepts</title>
      <link>https://selvi.org/en/blog/nfpa13/nfpa-13-definitions-core-concepts</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/nfpa13/nfpa-13-definitions-core-concepts</guid>
      <description>Listed vs approved, quick response and RTI, obstructed construction, concealed spaces and area of operation in NFPA 13, and how each shapes design.</description>
      <category>NFPA 13 Clause Guide</category>
      <pubDate>Tue, 29 Sep 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>NFPA 13 Working Plans and Hydraulic Calculations</title>
      <link>https://selvi.org/en/blog/nfpa13/nfpa-13-plans-and-hydraulic-calculations</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/nfpa13/nfpa-13-plans-and-hydraulic-calculations</guid>
      <description>NFPA 13-2025 Chapter 28 working plans and hydraulics: Hazen-Williams, C-factors, equivalent lengths, junction balancing, supply curve and data sign.</description>
      <category>NFPA 13 Clause Guide</category>
      <pubDate>Tue, 29 Sep 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>NFPA 13 Water Supplies: Flow Tests, Hose Allowance, Duration</title>
      <link>https://selvi.org/en/blog/nfpa13/nfpa-13-water-supplies</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/nfpa13/nfpa-13-water-supplies</guid>
      <description>NFPA 13 water supplies: acceptable sources, flow tests, safety margin, hose allowance and duration by hazard class, and how to size the tank.</description>
      <category>NFPA 13 Clause Guide</category>
      <pubDate>Tue, 29 Sep 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>NFPA 13 Underground Pipe: Thrust Restraint, Flushing, Tests</title>
      <link>https://selvi.org/en/blog/nfpa13/nfpa-13-underground-piping</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/nfpa13/nfpa-13-underground-piping</guid>
      <description>Underground fire mains to NFPA 13-2025 Chapter 6 (from NFPA 24): pipe materials, cover depth, thrust blocks, restrained joints, flushing, 200 psi test.</description>
      <category>NFPA 13 Clause Guide</category>
      <pubDate>Tue, 29 Sep 2026 00:00:00 +0000</pubDate>
    </item>
    <item>
      <title>NFPA 13 Systems: Wet, Dry, Pre-action, Deluge, Antifreeze</title>
      <link>https://selvi.org/en/blog/nfpa13/nfpa-13-system-types</link>
      <guid isPermaLink="true">https://selvi.org/en/blog/nfpa13/nfpa-13-system-types</guid>
      <description>NFPA 13 system types: wet, dry, pre-action, deluge and antifreeze; the 30% area increase, dry system water delivery time and the listed antifreeze rule.</description>
      <category>NFPA 13 Clause Guide</category>
      <pubDate>Tue, 29 Sep 2026 00:00:00 +0000</pubDate>
    </item>
  </channel>