When power fails, the building goes dark. Fire smoke reduces visibility to zero. At that moment, emergency lighting and exit signs are the only system guiding people to safety. NFPA 101 (Life Safety Code) and NFPA 110 (Emergency Power) define design, testing, and maintenance. A practical summary for engineers below.
Why It Matters
- Fire → panel trips → normal lighting off
- Smoke → visibility zero
- Panic → people run the wrong way
- Emergency lighting + exit signs: under NFPA 101 they light and mark the egress path for 90 minutes
NFPA 101 Illumination Requirements
Minimum emergency illumination:
- At floor level: average 10.8 lux (1 fc), min 1.1 lux
- Even distribution along egress path width
- On loss of normal lighting, emergency lighting must come on within 10 seconds (NFPA 101-2024, 7.9.1.3)
- Duration at least 90 minutes; by the end, levels may decline to an average of 6.5 lux and 0.65 lux at any point (NFPA 101-2024, 7.9.2.1 and 7.9.2.1.2)
Where emergency lighting is required, exit signs must also be illuminated for the emergency lighting duration (90 minutes); illumination may decline to 60 percent by the end (NFPA 101-2024, 7.10.4).
Power Systems
- Self-contained (battery luminaire): Individual battery per fixture. Simple but battery tracking hard.
- Central battery system: One battery bank feeds all luminaires. Easier monitoring and testing.
- Generator (NFPA 110): New systems feeding emergency lighting must be at least Type 10, Class 1.5, Level 1, i.e. on line within 10 s (NFPA 101-2024, 7.9.2.2 and 7.9.1.3). Hospitals, data centers.
- UPS: Instantaneous transfer, no break. Combined with generator for critical facilities.
Test Protocol
NFPA 101 mandatory test intervals:
- Monthly 30-second test: Cut power, system activates, luminaires light.
- Annual 90-minute test: Full discharge. Still above minimum lux after 90 min?
- Every test must be recorded.
- Failed luminaire replaced immediately.
Exit Sign Placement
NFPA 101 Chapter 7:
- Above or beside exit door
- Every point in corridor sees at least one sign
- Directional arrow: required when multiple paths
- Intermediate signs on corridors >30 m
- If smoke layers form at ceiling: floor-level signs
Situation in Turkey
BYKHY mandates emergency lighting: under Article 72(3) it must last at least 60 minutes after normal lighting fails, or at least 120 minutes where the occupant load exceeds 200, and Article 84 requires periodic inspection, testing and maintenance as specified in the relevant standards. But full-duration tests such as the NFPA 101 annual 90-minute test are rarely performed in practice. In most buildings inspected, aged batteries make the system go dark after 10-15 minutes. Without regular drills, this failure is only discovered in a real fire, when it is too late.
Common Mistakes
- Battery never replaced: batteries older than 5 years often retain less than half their nominal capacity.
- No test records: Required by insurance and inspection.
- LED status light on, battery empty: LED shows charged; battery doesn't.
- Wrong arrow direction: arrows point to the nearest door rather than the actual egress route.
- Monthly test skipped: Failure undetected for months.
Conclusion
Emergency lighting and exit signs are the cheapest and most critical part of the egress system. NFPA 101/110-compliant design + monthly/annual testing discipline + battery tracking saves lives in real fires. Unmaintained systems pass inspection and fail in fire.

Emergency lighting calc in MEP Calc
Egress lux calculation, battery capacity selection, monthly/annual test schedule.
View on App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreCore references: NFPA 101 Chapter 7, NFPA 110, NFPA 111. Original NFPA post: NFPA Today - Emergency Lighting.