The fire pump is the heart of the protection system. The annual flow test proves the pump still operates on the NFPA 20 performance curve. NFPA 25 Chapter 8 mandates it yearly. In many facilities this gets reduced to 'dumping some water' — but it is a technical measurement procedure. Here is how to do it correctly.
Purpose
Prove the pump still operates on its original performance curve. NFPA 20 defines three points:
- Churn (shutoff): 0% flow, ~140% rated pressure
- Rated: 100% flow, 100% rated pressure
- 150%: 150% flow, ≥65% rated pressure
Annual measurement of these three points proves the curve has not dropped. A drop indicates wear, cavitation or impeller damage.
Equipment Setup
- Test header / hose manifold: Branched off pump discharge; 4-6× 2.5" hose connections
- Pitot gauge: Measures jet from each hose end via 2.5" playpipe nozzle
- Flowmeter (optional, recommended): Direct flow measurement alternative to pitot
- Suction and discharge gauges: Must be calibrated (annually)
- Flow table: NFPA 20 Table 7.4.2 pitot-to-flow conversion
Test Procedure
- Pre-check: Pump room clean, bleeders open, gauges zeroed
- Churn: All discharge valves closed, start pump, run 5 min, record pressure
- 100% flow: Open 2-3 hoses, adjust flow to rated value (pitot), record pressure
- 150% flow: Open more hoses, bring flow to 150% rated, record pressure — must be ≥65% rated pressure
- Shutoff: Close valves gradually, run pump 2 min for cooling, then stop
- Report: Plot the three points and compare to original curve
Interpretation
If measured points fall >5% below original curve, internal inspection required. Disassemble pump; check impeller, wear ring, shaft seal. 10%+ drop = immediate action. Increases usually indicate gauge error or RPM drift in diesel pumps.
Field Cautions
- Discharge during test must not exceed drainage capacity — test drain sizing is critical
- Diesel pumps: monitor exhaust and fuel system during warm-up
- A test with out-of-calibration gauges invalidates the report
- Failed test: notify AHJ + insurer, initiate out-of-service procedure

Pump selection with SprinkCalc
Pump curve selection, 3-point test calculation and performance reporting.
Learn MoreReferences: NFPA 20 - Stationary Pumps, NFPA 25 - ITM Chapter 8. Official standard: NFPA 25.