Fire pumps are the most critical equipment in a fire. Lose power, the pump stops, sprinkler pressure drops, the system collapses. NFPA 20 therefore requires at least one alternate power source where the normal source is not reliable or the building is a high-rise (9.3.1), unless a backup engine-driven or steam turbine-driven pump, or a backup electric pump with an independent power source, is installed (9.3.2). The building blocks: primary + alternate feed, ATS (Automatic Transfer Switch), diesel pump or NFPA 110 generator. A practical design guide below.
Power Supply Options
- Single feed: Grid only; NFPA 20 accepts this only where the normal source is reliable and the building is not a high-rise; otherwise an alternate source or a 9.3.2 backup pump is required (9.3.1, 9.3.2).
- Primary + alternate grid: Two separate substations; simultaneous loss unlikely.
- Primary + generator: Grid loss → generator starts (via ATS).
- Electric + diesel pump combination: Each pump 100% capacity.
NFPA 20 Feeder Design
Electric pump requires:
- Separate tap: not shared with other loads
- Overcurrent protection: the device must be rated to carry indefinitely the locked rotor current of the largest pump motor plus the full-load current of all other pump motors and accessory equipment (NFPA 20 9.2.3.4)
- Short-circuit protection required, but thermal overload protection is prohibited: the pump must keep running to the end, even at the cost of the motor
- Cable: fire-resistant (minimum 2 hours), in a separate raceway, routed away from spaces with high fire load
ATS (Automatic Transfer Switch)
ATS switches between normal and emergency power. NFPA 110 Level 1 mandatory.
- Transfer time: max 10 seconds
- Delay: generator warm-up (30 s) + stabilization (10 s)
- Open transition (break-before-make) or closed transition (make-before-break, 100 ms)
- Bypass switch: service without outage
- Weekly automatic test: generator under real load
NFPA 110 Generator Requirements
- Level 1: fire pump included. Max 10 s transfer.
- Type 10, Class X: NFPA 20 9.6.2.1 requires NFPA 110 Level 1, Type 10, Class X; fuel must cover 8 hours of pump operation at 100% of rated capacity in addition to other demands (9.6.2.3)
- Diesel preferred (NFPA 37 rules)
- Environment: climate-controlled, -20 to +40°C
- Monthly 30 min test, annual 4-hour load test
Diesel Pump Option
Diesel pump instead of or alongside electric pump; power-independent:
- NFPA 20 Chapter 11 compliant
- Fuel: a tank dedicated to the fire pump, sized per NFPA 20 11.4.1.3.1 for at least 12 hours of engine run time plus 5% for expansion and 5% for sump (FM Global DS 3-7 2.4.21.6 requires at least 8 hours plus 5% + 5%)
- Two battery sets with auto charger
- Auto start: within 10 s of pressure drop
- Pro: power-independent; con: maintenance-heavy, exhaust management
Turkey Application Examples
Large malls, hospitals, data centers use electric + diesel. Mid-size: electric + generator. Small buildings often electric only — acceptable under NFPA 20 only where the normal source is reliable and the building is not a high-rise (9.3.1), and not unconditionally allowed by BYKHY either: Article 93(2) requires a standby pump of the same capacity where a single pump is used, and Article 93(4) requires that, where no standby diesel pump is used, the fire pump power supply comes from a reliable source independent of the building's general electrical system. A single electric pump on the general mains with no standby meets neither provision. Result: in fire-related outages, pump doesn't run.
Common Mistakes
- No ATS: Manual transfer; no one does it during fire.
- Generator not tested weekly: Doesn't start in fire.
- Stale diesel fuel: Diesel stored over 6 months degrades and clogs injectors and fuel lines.
- No FR cable: Cable burns, pump loses power.
- Thermal overload trips the pump: stopping the motor to protect it leaves the system dead in a fire. Use short-circuit (overcurrent) protection only, not thermal overload.
Conclusion
A fire pump isn't just mechanical equipment; it's inseparable from electrical reliability. Without primary + alternate + ATS + generator or diesel backup, the first outage collapses the system. Power supply is NFPA 20's most overlooked chapter — yet the most critical.

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, FM-200 clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreCore references: NFPA 20, NFPA 110, NFPA 37. Original NFPA post: NFPA Today - Fire Pump Power.