You cannot put out a petrol, solvent or jet-fuel fire with plain water. The water sinks below the hydrocarbon and the flame carries on at the fuel surface. That is why refineries, hangars and ignitable liquid stores use foam-water sprinkler systems: foam concentrate is proportioned into the water and discharged through sprinklers or spray nozzles, and once the foam period ends the system keeps discharging water. Since 2021 the rules for these systems sit in Chapter 6 of NFPA 11; this post walks through NFPA 11-2024 Chapter 6 clause by clause, in field terms.
Where Did NFPA 16 Go?
For many years foam-water sprinkler and spray systems had their own standard, NFPA 16. In the 2021 edition of NFPA 11 the NFPA 16 requirements were consolidated into a new Chapter 6 (NFPA 11-2024, "Origin and Development"). If a specification still says "NFPA 16", the current equivalent is NFPA 11-2024 Chapter 6.
Chapter 6 is a design and installation standard; it does not say where these systems are required (6.1.1). That comes from occupancy standards such as NFPA 30 (ignitable liquids) or NFPA 409 (aircraft hangars), or from building and fire codes. Where the occupancy standard asks for a more stringent density, area or spacing, it takes precedence (6.5.1.2).
Why Foam?
Three physical facts define a hydrocarbon fire:
- Fuel is lighter than water — water sinks straight below it.
- Burning happens at the fuel surface — the top of the flame zone must be covered.
- Vapor can re-ignite even after extinguishment — re-ignition must be prevented.
Foam solves all three in one move: it blankets the surface, traps the vapor and cuts off oxygen.
Foam Types
- AFFF (Aqueous Film-Forming Foam): the most common type, proportioned at 3% or 6%; the standard choice for hydrocarbons such as gasoline, diesel and kerosene.
- AR-AFFF (Alcohol Resistant AFFF): for polar solvents such as alcohol and acetone; alcohol-resistant concentrates are generally used at 3 to 10 percent solutions (NFPA 11 A.3.3.11.1).
- Protein foam: the classic protein-hydrolysate concentrate (NFPA 11 3.3.11.7).
- Fluorine-free foam (F3): a synthetic concentrate formulated without PFAS (SFFF; NFPA 11 3.3.11.8); application rates follow Annex H and the manufacturer's recommendation (6.5.2.2.1.1); selection follows the product listing.
On water-soluble and polar solvents NFPA 11-2024 allows only alcohol-resistant foam (6.1.3.4); the concentrate's proportioning ratio and the fuels it may be used on come from the product's listing.
Where It Works and Where It Does Not
Because the system delivers two agents (foam and water) through the same pipework, it suits combined Class A (ordinary combustible) and Class B (ignitable liquid) hazards (6.1.3.1). Foam-water deluge systems suit two-dimensional, spreading liquid fires and can serve three purposes (6.1.3.2):
- Extinguishment: the primary purpose; density, discharge devices and water pressure are chosen for it.
- Prevention: in garages, aircraft hangars, petrochemical or varnish plants, foam is discharged manually onto a spill to prevent ignition, and the blanket holds until clean-up is done.
- Control and exposure protection: controlled burning where extinguishment is not possible, and reducing heat transfer from an exposure fire.
The standard also lists fires where foam is not effective (6.1.3.3): liquefied or compressed gases (such as butane and propane), materials that react violently with water (such as metallic sodium), and electrical equipment where a non-conductive agent is the priority. On water-soluble and polar solvents (alcohols, acetone) only alcohol-resistant foam may be used (6.1.3.4). Possible contamination of water supplies and treatment systems by foam and foam-solution run-off must also be considered (6.1.3.5).
System Types and Discharge Devices
A foam-water system can be wet pipe, dry pipe, deluge or preaction (6.2.2). The type decides the discharge device and the detection:
| System type | Discharge device | Detection and actuation |
|---|---|---|
| Wet, dry, preaction | Automatic (closed) and non-air-aspirating sprinklers (6.4.2.3) | For preaction, detection to NFPA 13 (6.4.9.2) |
| Deluge and spray | Air-aspirating foam-water sprinklers and spray nozzles, or non-air-aspirating standard sprinklers (6.4.2.2) | Detection to NFPA 15 (6.4.9.1); automatic plus auxiliary manual tripping (6.2.1.1) |
- Detection and actuation circuits are supervised through a listed panel to NFPA 72 (6.4.9.3).
- In a deluge system, concentrate injection starts automatically with, or at the same time as, the main water control valve (6.5.8.2.1).
- Manual controls must operate with a pull of no more than 178 N (40 lbf) and a movement of no more than 356 mm (14 in.) (6.5.8.6.2).
- Wet pipe systems are preprimed with foam-water solution, unless the concentrate manufacturer recommends otherwise and the AHJ approves (6.2.5).
- All components, concentrate included, are listed for the intended use, and discharge devices and concentrate are listed for use together (6.4.1.1, 6.4.2.1).
Design Criteria
The numerical core of Chapter 6 fits in a short table. Where the occupancy standard gives a more stringent value, that value governs.
| Item | NFPA 11-2024 value | Clause |
|---|---|---|
| Design density | From the occupancy standard, but never below 6.5 mm/min (0.16 gpm/ft²) | 6.5.2.2.1 |
| Total design area (wet, dry, preaction) | 465 m² (5000 ft²), or the occupancy standard's area | 6.5.2.2.2.1 |
| Foam solution discharge time | 10 minutes: over the entire system area for deluge and spray, over the design area for wet, dry and preaction | 6.5.2.3.1 |
| Reduced duration | Where actual discharge exceeds the minimum density, proportionate reduction is permitted, but not below 7 minutes | 6.5.2.3.2 |
| After the foam | The system keeps discharging water until manually shut off | 6.2.3.2 |
| Area per sprinkler | Not more than 9.3 m² (100 ft²) | 6.5.6.1 |
| Sprinkler spacing | Not more than 3.7 m (12 ft) on and between branch lines; line-to-line 3.8 m (12 ft 6 in.) except in buildings whose primary structural members are 7.6 m (25 ft) apart, where the system density is 0.25 or more (the clause gives no unit) | 6.5.6.1 |
| Temperature rating | At roof or ceiling 121–149 °C (250–300 °F); at intermediate levels 57–77 °C (135–170 °F) unless ambient conditions require higher | 6.5.7 |
| Reserve concentrate | How a reserve supply is provided is agreed with the AHJ; the reserve must be listed for use with the system components | 6.2.4 |
With synthetic fluorine-free foam (SFFF), application rates come from Annex H and the manufacturer's recommendations (6.5.2.2.1.1). Examples of occupancy standards are NFPA 409 for aircraft hangars and NFPA 30 for ignitable liquid storage and handling; they may require a higher density or a different design area.
6.5 mm/min is a floor, not a "typical rate". The earlier version of this page, like some tables in circulation on site, quoted lower foam-water densities such as 4.1 mm/min (0.10 gpm/ft²). NFPA 11-2024 6.5.2.2.1 does not allow anything below the floor for a foam-water system.
Worked Example: Wet Pipe Foam-Water System
A wet pipe system at the floor values, where the occupancy standard asks for nothing more stringent:
- Solution flow: 6.5 mm/min × 465 m² = 3,022.5 L/min (about 800 gpm).
- Foam solution volume: 3,022.5 L/min × 10 min ≈ 30,225 L.
- Concentrate: the proportioning ratio comes from the concentrate's listing. At 3%, 30,225 × 0.03 ≈ 907 L; at 6%, about 1,814 L. Add the reserve supply agreed with the AHJ (6.2.4).
- Actual discharge: if the hydraulic calculation shows the system discharging more than the minimum, the concentrate runs out sooner. That is why 6.5.10.2.3 requires the hydraulic balance to show the concentrate supply can sustain the actual discharge for the time in 6.5.2.3.
Spill control and drainage: the facility must safely remove or retain the largest anticipated liquid spill plus the free water from the fixed system and the hose-stream discharge (6.5.2.6.1). The Annex A example (A.6.5.2.6.1) builds that volume as 6.5 mm/min × 465 m² + 946 L/min hose = 3,969 L/min; 3,969 L/min × 60 min = 238,140 L, plus the volume of liquid. Where the occupancy standard specifies different containment or drainage, it takes precedence (6.5.2.6.2).
For tank, dike and spill scenarios you can size concentrate and water with the foam concentrate calculator.
Proportioners
Equipment that mixes foam concentrate into water at the correct ratio:
- Bladder tank: works on system water pressure and delivers foam to the line within minutes; the most common solution on site.
- Balanced pressure pump: a separate pump injects the concentrate; suited to large systems.
- Around-the-pump: concentrate injected into a side stream of the main pump; preferred for mid-size systems.
- Inline eductor: useful for small installations; high pressure loss.
The Concentrate Side: Pipe, Strainers and Connections
The proportioning system follows NFPA 11 Section 4.5, concentrate pumps Section 4.6, and the power supply and controllers for pump drivers NFPA 20 and NFPA 70 (6.5.2.4). The details most often got wrong on site:
- Concentrate pipe: brass, bronze, stainless steel, or another material with the manufacturer's compatibility certification and AHJ approval (6.4.7.2.1). Carbon steel is not used (6.4.7.2.2), and pipe carrying concentrate is not galvanised (6.4.7.2.3).
- Long concentrate lines: lines run underground, or above ground for more than 15 m (50 ft), are kept full with a means of checking tightness (6.5.2.5.1). Lines and components stay within the concentrate's storage temperature limits (6.5.2.5.2).
- Concentrate strainers: where a listed strainer of the right size is not available, use one with an open-basket area of at least 10 times the inlet pipe area; perforations no larger than the smallest orifice in the system and not less than 3 mm (6.4.8). Strainers are accessible for flushing while the system keeps discharging (6.5.5).
- Test connection: sized for both the low flow and the maximum anticipated flow through the proportioner (6.4.10). A test line sized only for the maximum flow makes it impossible to prove the proportioner at its lower limit.
- Fire department connection: where required, it goes on the supply side of the proportioner (6.5.9.1). Over-pressurisation, proportioner imbalance and dilution are evaluated before installation (6.5.9.2), and a sign states that the connection feeds a foam-water system and must not be pumped above the design pressure (6.5.9.3).
- Equipment location: concentrate tanks, proportioners, pumps and control valves are as close as possible to the hazard but not exposed to the fire in a way that impairs performance (6.5.3).
Hydraulic Calculations
Pipe carrying water or foam solution is calculated to NFPA 13, as if it carried water (6.5.10.1.3, 6.5.10.2.5). The rules specific to Chapter 6:
- Deluge: pipe sizes are adjusted for uniform foam and water distribution, with a maximum variation of 20% above the specified discharge per sprinkler or nozzle (6.5.10.1.1.1).
- Wet, dry and preaction: two calculations: the most hydraulically demanding area and the least demanding design area, both balanced to the water supply (6.5.10.2.2). The least demanding area flows more water and therefore more concentrate, so the concentrate supply is checked against it (6.5.10.2.3).
- Concentrate pipe: friction loss by Darcy-Weisbach, using the concentrate's actual density for the Reynolds number and its actual viscosity at the lowest anticipated storage temperature (6.5.10.1.4). For alcohol-resistant concentrate, friction characteristics come from the manufacturer (6.5.10.1.4.4, 6.5.10.3.2).
- Hazen-Williams C values come from Table 6.5.10.1.5 of the standard (6.5.10.1.5, 6.5.10.2.6).
Spare Sprinkler Cabinet
The NFPA 13 spare sprinkler rule applies to foam-water systems too (6.4.11): at least 6 spares for fewer than 300 sprinklers, at least 12 for 300 to 1,000, and at least 24 for more than 1,000; one wrench per sprinkler type and a posted sprinkler list in the cabinet. The cabinet location must not exceed the maximum ceiling temperature allowed for the sprinklers inside.
Test and Maintenance
In NFPA 11-2024, acceptance tests for foam-water systems follow Section 12.9, and inspection, testing and maintenance follow Chapter 13 (6.6, 6.7). The items below are general site practice; confirm frequencies against the edition in force.
- Annual foam concentrate test: samples go to the manufacturer or an approved laboratory (NFPA 25-2026 11.3.1.1, 11.3.1.2)
- Proportioner flow test annually (NFPA 25-2026 11.3.2 and Table 11.1.1.2)
- Complete system operational test annually (NFPA 25-2026 11.3.10.2 and Table 11.1.1.2); the full-flow discharge of foam-water deluge systems may be run on water instead of foam (11.3.10.2.3)
- After the PFAS ban, legacy concentrate stocks are special waste and cannot be disposed of by normal routes
The PFAS Transition
In 2024 AFFF was banned in Europe because of its PFAS content. Turkey has no active ban yet, but the transition has quietly started. Three jobs stand out for legacy systems:
- Conversion to F3 (fluorine-free) concentrate
- Safe disposal of legacy concentrate — no burning on site; a specialized high-temperature facility is required
- Equipment cleaning: even PFAS residue on valve and pipe interiors is a problem
Common Mistakes
- Density below 6.5 mm/min. Values such as 4.1 mm/min taken from old tables do not meet 6.5.2.2.1.
- A single hydraulic calculation. Without the least demanding area calculation for wet, dry and preaction systems, nobody knows whether the concentrate lasts 10 minutes.
- Carbon steel or galvanised concentrate line. 6.4.7.2.2 and 6.4.7.2.3 prohibit both.
- Test line sized only for maximum flow. The proportioner's accuracy at low flow cannot be proven.
- Non-alcohol-resistant foam in a polar solvent area. 6.1.3.4 allows only alcohol-resistant foam.
- Forgetting drainage and containment. The spill, the sprinkler water and the hose streams have to be handled together (6.5.2.6.1).
- A specification written "to NFPA 16". The current equivalent is NFPA 11-2024 Chapter 6; the edition year should be stated explicitly.
Conclusion
Foam-water sprinklers are the main tool of hydrocarbon fire engineering. Sprinklers, proportioner, concentrate and pump only work when they are calculated together: a 6.5 mm/min floor density, a 465 m² area, 10 minutes of foam and a second hydraulic calculation for the least demanding area. The PFAS transition is reshaping the industry — F3 conversion takes serious investment but has become an environmental necessity. Major hangar and refinery owners in Turkey have long since put it on the planning table.
Frequently Asked Questions
Is NFPA 16 still in force?
No. The requirements for foam-water sprinkler and spray systems were consolidated into NFPA 11 as a new Chapter 6 in the 2021 edition. The current equivalent is NFPA 11-2024 Chapter 6.
What is the minimum density for a foam-water sprinkler system?
Under NFPA 11-2024 6.5.2.2.1 the density comes from the occupancy standard but is never below 6.5 mm/min (0.16 gpm/ft²). For wet, dry and preaction systems the total design area is 465 m² (5000 ft²).
How long is foam discharged?
Foam solution is discharged for 10 minutes: over the entire system area for deluge and spray systems, and over the design area for wet, dry and preaction systems (6.5.2.3.1). Where actual discharge exceeds the minimum density the time may be reduced proportionately, but never below 7 minutes. After the foam, the system keeps discharging water until shut off manually.
What is the difference between AFFF and AR-AFFF?
AFFF is used on hydrocarbons such as petrol, diesel and kerosene. AR-AFFF is alcohol-resistant and is used on polar solvents such as alcohols and acetone. Under NFPA 11-2024 6.1.3.4, only alcohol-resistant foam may be used on water-soluble and polar solvent fires; the proportioning ratio comes from the product's listing.

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreCore reference: NFPA 11-2024, Chapter 6 (Low-Expansion Foam Sprinkler and Spray Systems) and Annex A (A.6.5.2.6.1). Chapter 6 holds the requirements of NFPA 16, a separate standard until the 2021 edition. Occupancy standards: NFPA 30 (ignitable liquids) and NFPA 409 (aircraft hangars); NFPA 13 for pipe hydraulics and alarms, NFPA 15 and NFPA 72 for detection. Related posts: deluge system design, foam system design guide, AFFF to F3 foam transition, floating roof tank protection.