Antalya Belek 5-star hotels host 2,000+ beds + 8 restaurants + 5,000+ covers/day. The kitchen hood collects grease fumes and duct temps can hit 500 C. NFPA 96 mandates 450 mm extension, UL 300 wet-chemical system and clean-out ports every 5 m.
Hood Design
- Type I: Grease, high heat
- Type II: Steam, heat
- Extension: 450 mm min beyond
- Capture velocity: 0.25-0.5 m/s
- Filter: Baffle, UL Class I
Grease Duct
- Velocity: 7.6 m/s min
- Slope: 2 percent to pit
- Material: Stainless 16 ga
- Clean-out: Every 5 m
- Clearance: 450 mm combustible
UL 300 Wet Chemical
- Agent: Potassium acetate K2CO2H3O2
- Flow: 4.5-7.5 L/min nozzle
- Coverage: 1 nozzle/wok
- Fuel shut-off: Gas valve auto
- Duct nozzle: Every 3.7 m
Inspection
- Grease cleaning: Monthly 24/7
- Semi-annual: Catering weekly
- Link fuse: 6-month check
- Tank pressure: 3 months
- UL 300: Annual certified
Fire Cases
- Antalya Belek: Two hotel hoods 2020, minor
- Marmaris 2021: Oil hood fire
- Istanbul Grand Hyatt: UL 300 system
- Old CO2: Now wet-chem mandatory
- Las Vegas MGM 1980: Kitchen incident

MEP Calc — 86+ Engineering Calculators
MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, FM-200 clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 96, UL 300, IMC Ch. 5, ASHRAE 154, NSF 2. NFPA 96 Ventilation Control and Fire Protection of Commercial Cooking.