Rafineride cok buyuk hampetrol/gasoline tanklari (50,000-150,000 m3) floating roof (yuzer tavan) ile havaya maruziyeti azaltir. Yildirim veya statik elektrik rim seal (tavan kenar sızdirmazligi) yanginlari baslatir. NFPA 11 rim seal foam, semi-subsurface foam ve full-surface foam yöntemlerini tanimlar. Buncefield 2005 (UK) ve Jaipur 2009 (India) buyuk kazalardir.
Tank Tipleri
- Floating roof (FRT): Yuzer tavan, sivi ustunde
- Internal FRT (IFRT): Dis sabit tavan + ic yuzer
- Fixed roof: Sabit - kucuk tanklarda
- Rim seal: Primary (shoe) + secondary (fin)
- Vapor tutum: Flotating az, fixed cok
Rim Seal Yangini
- Sebep: Yildirim (50-70 percent), statik, kaynak
- Alan: Rim genislik dar - 400 mm
- Cevre uzunlugu: 80 m capli tank = 251 m
- Foam debi: 12.2 L/min/m2 (0.3 gpm/sqft)
- Duration: 20 dk
NFPA 11 Foam Tipleri
- AFFF (aqueous film): Hızli kapanir, flashback zayif
- AR-AFFF (alcohol-resistant): Polar çözücü (metanol)
- FP (fluoroprotein): Uzun kaplanma, subsurface ideal
- F3 (fluorine-free): 2026 gecis - PFAS yasak
- High-expansion: LNG/amonyak icin
Full-Surface Yangin
80 m capli tank, full surface:
- Alan: A = π × 40² = 5027 m2
- Debi: 6.5 L/min/m2 → 32,670 L/min
- Sure: 65 dk (0.35 mobilizasyon dahil)
- Foam konsantre: 3 percent → 980 L/min x 65 = 63.7 m3
- Su: 32,670 × 65 = 2,124 m3
Buncefield 2005 Dersi
- Olay: Benzin tankı overfill, vapor cloud explosion
- Hasar: 2 Mt infilak buyukluk, 43 yarali
- Sebep: Tank seviye alet arizali
- Ders: Yuksek-seviye alarm bagimsiz, high-integrity
- Process Safety: API 2350 overfill prevention

FRT SprinkCalc ile
SprinkCalc rafineri floating roof tank rim seal foam, full-surface debi, subsurface injection ve NFPA 11 uyumluluk hesaplamalarini yapar.
SprinkCalc'i App Store'dan indir
Kaynaklar & İleri Okuma
NFPA 11, NFPA 30, API 2350, API 650, EEMUA 159, HSE Buncefield Report. NFPA 11 Low-/Medium-/High-Expansion Foam.