Rafineri ve petrokimya tesislerinde mekanik salmastra yangini en sik basvurulan risk senaryolarindan biridir. Yuksek basincli hidrokarbon jet yangini olusturur — 5-10 m yuksekligine bir ates sutunu. API 2218 (Fireproofing Practices in Petroleum and Petrochemical Processing Plants) yapisal koruma, pompa secondary containment ve deluge spray water tasarimini tanimlar.
Salmastra Ariza Modlari
- Primer salmastra asinmasi: Kuru calisma, abrazif sivi
- Secondary seal arizasi: Yanici sivi atmosfere kacar
- Pompa kavitasyon: Asiri vibrasyon, eksen sapmasi
- Tutusma: Sicak yuzey (>350 C otoignition), kivilcim
Typical API 610 pompa salmastra omru 3-5 yil.
Firesafe Secondary Seal
- Dual mechanical seal: Iki primer + bariyer sivi
- API Plan 52/53: External flush + bariyer sivi sirkulasyonu
- API Plan 66: Secondary containment + drain
- Magnetic drive pump: Salmastra yok — sizinti yok
Deluge Spray Water
API 2218 pompa etrafina deluge:
- Tasarim yogunlugu: 10.2 L/min/m2 (0.25 gpm/ft2)
- Uygulama alani: pompa + motor + diskanek valf
- Nozzle: Medium velocity spray, 60 derece konik
- Aktivasyon: Flame detector (UV/IR), gaz detektoru veya manuel
- Su rezervi: 30 dakika (AHJ) veya 2 saat (FM Global)
Yapisal Firepfproofing
- Yapisal celik: PFP (passive fire protection) - intumesan boya, 2 saat rating
- Kablo tepsisi: Ablative kaplama veya mineral wool
- Boru destegi: Firepfroof beton kaplama yuksekligi 9 m
- ESD valfi: Isi veya duman ile kapanir, 30 saniye

Pompa Deluge SprinkCalc ile
SprinkCalc rafineri pompa deluge icin 10.2 L/min/m2 yogunluk, spray nozzle secimi, ESD entegrasyonu ve 2 saat su rezervini API 2218 uyarinca hesaplar.
SprinkCalc'i App Store'dan indir
Kaynaklar & İleri Okuma
API 2218, API 610, API 682, NFPA 15, NFPA 30, FM Global DS 7-88. API 2218 Petroleum Plants Fireproofing.