Cement, mortar, clinker dust and fuel silos need special protection against dust explosion. Clinker itself does not burn but coal/petcoke, bypass dust and fly ash can. NFPA 68 deflagration venting and NFPA 69 explosion prevention (inerting) offer silo protection options.

Silo Types and Risk

NFPA 68 Vent Calculation

500 m3 coal silo, Kst 150, Pmax 8 bar, Pred 0.5 bar:

St Class and Kst

Panel Design

NFPA 69 Inerting Alternative

Silo venting with MEP Calc

MEP Calc sizes cement/coal silo NFPA 68 Av panel area, St class, Kst and NFPA 69 inerting calculations.

Download MEP Calc on the App Store
Sources & Further Reading

NFPA 68, NFPA 69, NFPA 652, NFPA 664, VDI 2263, FM DS 7-76. NFPA 68 Explosion Venting standard.