Cimento, cimentolu harc, klinker toz ve yakit silolari toz patlamasi icin ozel koruma gerektirir. Klinker kendisi yanmaz ama komur/petcoke, bypass toz ve flyash yanici olabilir. NFPA 68 deflagration venting, NFPA 69 explosion prevention (inerting) silo koruma secenegi sunar.
Silo Tipleri ve Risk
- Komur tozu silo: St1 (Kst 50-150)
- Petcoke silo: St1-St2 (Kst 150-200)
- Klinker dust bypass: Alkali tuzu, dust - nem ile self-heating
- Fly ash silo: St1 (termal santralden gelir)
- Cimento silosu: Yanmaz (CaCO3-CaO-CaSO4)
NFPA 68 Venting Hesabi
500 m3 komur silosu, Kst 150, Pmax 8 bar, Pred 0.5 bar:
- Av = (Kst × V^0.75) / (Pred × 1000)
- Av = (150 × 500^0.75) / (0.5 × 1000)
- Av = (150 × 105.6) / 500
- Av = 31.7 m2 (panel alani)
- Panel yerlesim: Silo ust yarisi, duz vent duct
St Class ve Kst
- St0: Kst = 0 (yanmaz)
- St1: Kst 1-200 (en yaygin - komur, un, seker)
- St2: Kst 200-300 (petcoke, alumina)
- St3: Kst >300 (metal tozu - Al, Mg)
- Kst olcumu: 1 m3 KSEP test (VDI 2263)
Panel Dizayni
- Bursting pressure: Pstat = 0.1-0.2 bar
- Panel efficiency: Ef = 0.5 (vent duct ile)
- Flame vent yeri: Personel yok, kiyi hurdas az
- Isolation valve: NFPA 69 isolation - ardil patlama engelle
- Recoil: Panel karsı tarafa yuklenme (silo desteklensin)
NFPA 69 Inerting Alternatif
- N2 inerting: O2 <8 percent komur icin
- CO2 inerting: Alternatif, maliyeti dusuk
- LOC (Limiting Oxygen Concentration): Komur percent 14, petcoke percent 12
- Suppression (HRD): 25 kg monoammonium phosphate, 50 bar

Silo Venting MEP Calc ile
MEP Calc cimento/komur silosu icin NFPA 68 Av panel alani, St class, Kst hesabi ve NFPA 69 inerting hesaplamalari yapar.
MEP Calc'i App Store'dan indir
Kaynaklar & İleri Okuma
NFPA 68, NFPA 69, NFPA 652, NFPA 664, VDI 2263, FM DS 7-76. NFPA 68 Explosion Venting kodu.