A data centre came out of a five-year insurance survey with a list of major recommendations: the dry pipe valve trip test had not been done for three years, fire pump run records were incomplete, and gauge status was unknown. The site had been working to an annual flow test regime, but FM Global DS 2-81 (Fire Protection System Inspection, Testing and Maintenance, April 2019, Interim Revision April 2026) sets out tasks in Tables 2.4.2.1–2.12.3.1 at frequencies from weekly to 15 years. Under 2.4.1 some activities may be modified for site conditions in discussion with an FM field engineer. This article summarises the frequencies period by period.

Weekly

Monthly

Quarterly and Semiannually

Annually

Multi-Year Tasks

Comparison With NFPA 25 (DS 2-81 Appendix C, Table C-1)

Appendix C of DS 2-81 compares FM frequencies with the 2026 edition of NFPA 25 (the table was updated in the April 2026 interim revision of DS 2-81). Some examples:

TaskFM DS 2-81NFPA 25-2026 (per Table C-1)
Visual inspection of indicating control valvesWeeklyMonthly / weekly
Physical test of non-indicating valvesMonthlyAnnually
Dry system valve air and water pressuresWeeklyMonthly / quarterly
Full-flow trip test3 years (10 years with nitrogen)3 years
Dry-type sprinkler sample test15 years10 years
Electric pump churn testMonthlyWeekly / monthly
Diesel pump churn testWeeklyWeekly
Diesel battery checkMonthlyAnnually

The current edition of NFPA 25 is not among the sources for this article; the comparison reproduces only the table in DS 2-81.

Quick Checklist

Frequently Asked Questions

What does the main drain test actually tell you?

Under DS 2-81 Table 2.5.1.1 item 4, the annual main drain flow test checks for significant obstructions in the water supply upstream of each riser, discharging to an outside location. Where several risers are manifolded on a common lead-in, one test covers them all. It is ideally done after the annual valve exercise, since it is often the final step in restoring impairments such as valve closures.

How often is a full dry pipe trip test required?

Under DS 2-81 Table 2.5.3.3 item 14, every 3 years, or every 10 years for systems with nitrogen; a videoscope or ultrasonic localized guided wave evaluation is an accepted alternative. The system must deliver water to the hydraulically remote area within the specified time, 60 seconds unless an occupancy data sheet states otherwise. A partial-flow trip test is also done annually (item 13).

Which sprinklers are sample tested?

Per DS 2-81 Table 2.5.1.1: dry-type (dry pendent) sprinklers every 15 years, recalled O-ring sprinklers every 5 years, and sprinklers with fusible elements of 180 °C or more under prolonged exposure to 150 °C every 3 years. Dry-type sprinklers made before 2003 are replaced when found, and after a fire all non-operated sprinklers within 6 m of operated ones are replaced.

How do FM expectations differ from NFPA 25 in practice?

DS 2-81 Appendix C Table C-1 compares FM with NFPA 25-2026. FM is more frequent for some tasks, such as the monthly physical test of non-indicating valves (NFPA annually), weekly dry system pressure checks and monthly diesel battery checks (NFPA annually), and less frequent for others, such as the 15-year dry sprinkler sample test (NFPA 10 years).

Can the weekly pump test be automated?

Under the October 2025 revision of DS 2-81, yes: an FM Approved automated fire pump test system can conduct the weekly (diesel) and monthly (electric) churn tests without personnel present (2.9.2.2, 2.9.3.2). Such systems monitor alignment, vibration, cooling water flow, room temperature and leakage and send an alert if limits are exceeded (3.1.11.3). DS 3-7 2.4.9.1 separately warns against relying on a controller's own weekly test timer without supervision.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

FM Global Property Loss Prevention Data Sheet DS 2-81, Fire Protection System Inspection, Testing and Maintenance, April 2019, Interim Revision April 2026 (2.2, 2.4.2, Tables 2.4.2.1, 2.5.1.1, 2.5.2.1, 2.5.3.3, 2.6.1.1, 2.7.3.1, 2.9.1.1, 2.10.1.1-2; 2.9; 3.1.11.3; Appendix C Table C-1); FM Global DS 3-7, Section 2.4.9.