In aircraft hangars we protect airframes carrying more than 300,000 L (79,000 gal) of jet fuel. Once a fuel spill ignites, the fire spreads within 60 seconds, and an aluminum fuselage can fail structurally in as little as 5 minutes. NFPA 409 classifies hangars by size as Group I (wide-body), Group II (narrow-body) and Group III (general aviation), and requires an AFFF or high-expansion foam system in each.
Hangar Classification
- Group I: Area over 2,800 m² (30,000 ft²); wide-body aircraft such as the B747 and A380
- Group II: 1,115–2,800 m² (12,000–30,000 ft²); narrow-body aircraft such as the A320 and B737
- Group III: Under 1,115 m² (12,000 ft²); business jets and general aviation
- Group IV: Membrane-covered hangar structures
- Group V: Special-purpose military hangars
Group I: AFFF Deluge System
- Overhead system: 6.5 L/min/m² (0.16 gpm/ft²)
- Low-level system: 10.2 L/min/m² (0.25 gpm/ft²) under the aircraft
- Duration: 10 min overhead + 10 min low-level
- 3% AFFF: The transition to fluorine-free (F3) foam is under way
- Activation: The entire system must operate within 60 seconds
High-Expansion Foam
- Expansion ratio: 500:1 to 1000:1 (NFPA 11 defines high expansion as roughly 200:1 to 1000:1)
- Fill rate: 1 m (3.3 ft) rise per minute
- Coverage: Fills the hangar to a depth of 2–3 m (6.6–9.8 ft)
- Foam generator: Blower type; the fan is driven by an electric motor or a water motor (NFPA 11 A.3.3.13.2)
- Advantage: Water savings and three-dimensional filling of the volume
Detection and Alarm
- Optical smoke detection: Beam type, 100 m (328 ft) range
- UV/IR flame detectors: 30 m (98 ft) coverage diameter
- Heat detectors: Rate-of-rise type
- Manual pull stations: Spaced at 30 m (98 ft)
- Voice alarm: For evacuation announcements
Turkish Hangar Examples
- Istanbul Airport maintenance base: 8 Group I hangars
- Sabiha Gökçen: Airline MRO facility
- Esenboğa: Military Group V hangar
- Kayseri: F-16 production line
- İzmir Çiğli: Turkish Air Force base

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, FM-200 clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 409, FAA AC 150/5210, ICAO Annex 14, MIL-STD 3020, FM DS 7-93. NFPA 409 Aircraft Hangars.