In CMSA design, matching the commodity and storage arrangement to the product listing matters more than anything else. K-factor selection, 15–30 operating sprinklers, in-rack hydraulic balance, pressure management — step by step. Where ESFR cannot be used, CMSA is what saves the project.
At a tyre distribution warehouse, CMSA K200 was selected because a 12 % roof slope ruled ESFR out. The design described the commodity as "tyres stacked on tread, 6 m". The manufacturer's listing, however, read "tyres, palletized, ≤ 6 m" — that is, on pallets. On site the tyres were stacked directly, without pallets. The insurer recorded a specific-application mismatch, and the heads had to be replaced with a product listed for "tyres, columnar, ≤ 6 m", with a two-week delay. A product listing has to describe the storage geometry exactly as built.
Ten-step CMSA design flow
- Establish storage height and commodity classification
- Confirm why ESFR is unsuitable (roof > 5 %, large skylights, obstructions)
- Match commodity and storage arrangement to the manufacturer's listing
- Select the K-factor (K115–K240 depending on commodity)
- Determine the number of design sprinklers (15–30)
- Set the pressure, 2–4 bar, from the product listing
- Coordinate in-rack protection where storage exceeds 6 m
- Calculate water demand for 60–90 min
- Produce the hydraulic report
- Obtain insurer approval
Commodity, K-factor and design sprinkler table
| Commodity | Storage height | K-factor | Pressure | Design heads |
|---|---|---|---|---|
| Tyres, columnar | ≤ 6 m | K160 | 3.5 bar | 20 |
| Tyres, palletized | ≤ 6 m | K160 | 3.0 bar | 15 |
| Paper rolls on end | ≤ 8 m | K200 | 3.0 bar | 15 |
| Paper rolls on side | ≤ 6 m | K160 | 2.4 bar | 15 |
| Class III cartons | ≤ 7.6 m | K160 | 2.4 bar | 15 |
| Group A plastics, palletized | ≤ 6 m | K200 | 3.5 bar | 20 |
| Mixed plastics | ≤ 6 m | K240 | 3.5 bar | 30 |
| Idle timber pallets | ≤ 6 m | K160 | 3.0 bar | 15 |
Worked water demand example
Tyres stored columnar, K160, 3.5 bar, 20 design heads:
- Per sprinkler: Q = K × √P = 160 × √3.5 ≈ 299 L/min
- 20 sprinklers: 20 × 299 = 5980 L/min
- In-rack, 6 heads at K80 and 2 bar: 6 × 80 × 1.41 ≈ 677 L/min
- Total: 5980 + 677 = 6657 L/min
- Duration: 90 min
- Water volume: 6657 × 90 ≈ 599 000 L, i.e. about 600 m³
- Tank: 600 m³ plus margin, so around 660 m³
- Pump pressure: 3.5 + 2 (friction) + 1.2 (static) + 0.5 (margin) = 7.2 bar
In-rack coordination
| Storage height | In-rack levels | Horizontal spacing |
|---|---|---|
| ≤ 6 m | None (ceiling only) | — |
| 6–9 m | 1 (at about 3 m) | 3 m |
| 9–12 m | 2 (at about 3 m and 6 m) | 3 m |
| 12–15 m | 3 (at about 3 m, 6 m and 9 m) | 2.4 m |
Hydraulic balance: ceiling plus in-rack
- Ceiling pressure is the highest in the system
- In-rack pressure must sit below the ceiling pressure
- Calculate as parallel branches — the ceiling branch and the in-rack branch
- Total flow: 20 ceiling heads plus the six worst-case in-rack heads
- Use hydraulic software to balance the two parametrically
- The insurer's report must identify the critical point
Field error — in-rack hydraulics left out of the calculation
A paper warehouse was designed with CMSA at ceiling plus in-rack heads, but the hydraulic analysis covered only the ceiling branch. During commissioning water reached the in-rack heads at 0.8 bar against a requirement of 2 bar. The main had to be increased from DN150 to DN200 and a separate feed branch added. Ceiling plus in-rack always demands a parallel-branch calculation.
Checking the listing
- The commodity is named explicitly (tyres, paper rolls and so on)
- The storage geometry is stated (palletized, columnar, on side)
- The storage height limit is given
- K-factor and pressure are specified
- The number of design sprinklers is stated
- Roof slope limit is given
- Skylight limit is given
- Obstruction tolerance is stated
Turkish regulation and local practice
BYKHY contains no CMSA-specific provision; the EN 12845-2 or NFPA 13 reference is sufficient. Turkish tyre and paper manufacturers commonly use CMSA, frequently with foam-water. When procuring listed heads, products carrying both FM Approval and EN certification are preferred; domestic insurers generally accept EN certification alone.
Quick check list
- The ten-step design flow was followed.
- The reason ESFR is unsuitable is stated in writing.
- Commodity and storage geometry match the listing.
- K-factor and design head count match the table.
- In-rack hydraulics calculated as a parallel branch.
- Ceiling pressure exceeds in-rack pressure.
- Hydraulic report ready for the insurer.
- Foam-water system listed, where used.
Frequently Asked Questions
What decides the CMSA K-factor?
The commodity and its storage geometry, taken from the manufacturer's listing — not the storage height alone. Typical values run K115 to K240, with 2–4 bar operating pressure.
How many sprinklers are assumed to operate in a CMSA design?
Between 15 and 30, depending on the commodity. Class III cartons and paper rolls are typically 15; Group A plastics and columnar tyres are typically 20; mixed plastics can reach 30.
Does storage geometry really have to match the listing?
Yes, exactly. A listing for tyres "palletized" does not cover tyres stacked columnar. This mismatch is one of the most common reasons an insurer rejects a CMSA installation.
Must in-rack heads be calculated separately?
Yes — as a parallel hydraulic branch. Calculating only the ceiling branch is a recurring error that surfaces at commissioning, when in-rack pressure falls well short.

SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.
Download SprinkCalc on the App Store
MEP Calc — 86+ Engineering Calculators
MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App StoreBS EN 12845:2015+A1:2019 Fixed firefighting systems — Automatic sprinkler systems. EN 12845-2:2024 (CMSA & ESFR sprinkler systems). NFPA 13 Standard for the Installation of Sprinkler Systems. Turkish Regulation on Fire Protection of Buildings (BYKHY). FM Global Property Loss Prevention Data Sheet 2-0.