Elektrikli araç batarya paketi 400-800V, 50-100 kWh icerir. Kullanim sonrasi recycling tesisleri bu pilleri parcalar, metal geri kazanimi yapar. Shredder sirasinda hasarli hucre thermal runaway tetikler, HF gazi salar. NFPA 855 enerji depolama ve pil sistemleri kurallarini verir.
Li-ion Kimyasi
- NMC: Ni-Mn-Co cathode, 250 Wh/kg
- LFP: Demir fosfat, 160 Wh/kg, guvenli
- Electrolit: LiPF6 + EC/DMC/EMC
- Thermal runaway: 80 C SEI, 130 C separator
- Off-gas: HF, CO, CO2, H2, hidrokarbon
Shredder Guvenlik
- N2 inerting: O2 %4 altinda tutulur
- Slurry shredder: Su altinda parcalama
- Pre-discharge: NaCl tank 48 saat
- Scrubber: HF yikama NaOH
- Hiz: 25 rpm yavas + 60 kW motor
NFPA 855 Gereksinim
- Pil birim: 600 kWh max odada
- Spacing: 910 mm aralik rack
- Sprinkler: K=160 (11.2) 12.2 L/min/m2
- 2-saat firewall: Ayirma duvar
- Gas detection: H2 %25 LEL alarm
Thermal Runaway Yanitli
- Propagation test: UL 9540A hucre level
- Mist system: Su sisi + dispersant
- F-500 ajan: Encapsulation
- Su saati: 4-8 saat soğutma
- Reignition: 24-48 saat izleme
Turk Tesis Ornekleri
- Exitcom Bursa: 5000 ton/yil Li-ion
- Togg Gemlik: Uretim + recycling entegre
- Mevzuat: Atik pil yonetmeligi
- EU: Battery Regulation 2023/1542
- Black mass: Li/Co/Ni hydrometallurgy

Recycling SprinkCalc ile
SprinkCalc Li-ion recycling tesisi sprinkler K=160 debi, N2 inerting kapasitesi, HF scrubber ve NFPA 855 layout kontrolu yapar.
SprinkCalc'i App Store'dan indir
Kaynaklar & İleri Okuma
NFPA 855, UL 9540A, NFPA 400, EU Battery Regulation, FM DS 5-33. NFPA 855 Energy Storage Systems.