Kombine cevrim santrali, gaz turbini ve buhar turbini yataklari icin hidrolik-yaglama yag sistemi 10,000-25,000 litre mineral yag icerir. Tutusma sicakligi ~320 C olan ISO VG 32/46 yagi, yuksek basincli (15-20 bar) borunun sizintisinda jet fire olusturur. NFPA 850 (Electric Generating Plants) lube oil reservoir, yag pompasi ve bearing pedestal icin water spray ve CO2 koruma tasarimini tanimlar.
Yag Sistemi Risk Noktalari
- Ana rezervuar: 15,000-25,000 L paslanmaz celik tank
- AC/DC yag pompasi: Salmastra arizasi jet fire riski
- Bearing pedestal: Yag sizintisi sicak turbin govdesinde tutusur
- Oil cooler: Plate heat exchanger sizintisi boiler room
- Hidrolik sistem: 200-300 bar phosphate ester (Skydrol) daha yuksek flash point
Water Spray Tasarim (NFPA 15)
- Yogunluk: 10.2 L/min/m2 (0.25 gpm/ft2)
- Uygulama alani: Rezervuar + pompa + 6 m radius
- Nozzle: Medium velocity spray, 90 derece konik
- Aktivasyon: Linear heat detector (thermistor kablosu) 57 C
- Su rezervi: 30 dakika minimum, AHJ 2 saat isteyebilir
CO2 Total Flooding
- NFPA 12: Bearing enclosure icin CO2 surface total flooding
- Tasarim konsantrasyon: percent 34 (mineral yag)
- Boşaltma suresi: 2 dakika
- Kilitleme: Predischarge alarm 30 sn, kapi kilit, HVAC kapat
- Dezavantaj: Insan olmayan yerlerde - CO2 asphyxiant, tahliye zorunlu
Acil Kapatma
- Yag pompa ESD: Yangin algilamada 5 saniye
- Dump valve: Ana rezervuar alt dogusu underground emergency tank'e
- Turbin trip: Burner management system (BMS) fuel cut
- Havalandirma kapat: Duman yayilimini onle

Yag Yangin Water Spray SprinkCalc ile
SprinkCalc turbojenerator yag yangini water spray icin 10.2 L/min/m2 yogunluk, medium velocity nozzle sayisi ve 2 saat su rezervini NFPA 850 uyarinca hesaplar.
SprinkCalc'i App Store'dan indir
Kaynaklar & İleri Okuma
NFPA 850, NFPA 15, NFPA 12, FM Global DS 7-101, IEEE 979. NFPA 850 Electric Generating Plants.