In combined-cycle plants the lube and hydraulic oil system feeding the gas and steam turbine bearings holds 10,000-25,000 litres of mineral oil. ISO VG 32/46 oil, with an autoignition temperature of about 320 °C, sprays out as a jet fire if a line operating at 15-20 bar leaks. On site this risk is described as "the plant's quietest big hazard"; nobody notices the oil until it finds the hot turbine casing. NFPA 850 (Electric Generating Plants) is the main standard defining the water spray and CO₂ protection logic for lube oil reservoirs, oil pumps and bearing pedestals.
Oil System Risk Points
- Main reservoir: 15,000-25,000 L stainless steel tank, typically located at basement level of the turbine building.
- AC/DC oil pump: a seal failure creates a direct jet fire risk; even with two pumps in parallel, a single leak is enough.
- Bearing pedestal: leaking oil ignites the moment it reaches the hot turbine casing; the most critical area met on projects.
- Oil cooler: a leaking gasket in the plate heat exchanger spreads oil into the mechanical room.
- Hydraulic system: phosphate ester fluid (Skydrol) at 200-300 bar has a higher ignition temperature than mineral oil, but the high pressure makes any leak spray more violently.
Water Spray Design (NFPA 15)
- Density: 10.2 L/min/m² (0.25 gpm/ft²) — the standard reference value for hydrocarbon surface fires.
- Area: reservoir + oil pump + a 6 m radius protection circle.
- Nozzles: medium-velocity spray, 90-degree cone.
- Activation: linear heat detection cable (thermistor), operating at 57 °C.
- Water reserve: at least 30 minutes; the authority having jurisdiction often asks for 2 hours, and systems are sized for 2 hours from the start on site.
CO₂ Total Flooding
- NFPA 12: total flooding CO₂ designed for surface fires is applied to the bearing enclosure.
- Design concentration: 34% (for mineral oil).
- Discharge time: 2 minutes.
- Interlocks: 30 s pre-discharge alarm, electromechanical door lock, HVAC dampers close.
- Drawback: CO₂ is an asphyxiant; where people may be present, an evacuation scenario and escape lighting must be planned.
Emergency Shutdown
- Oil pump ESD: the shutdown signal reaches the pump within 5 seconds of detection.
- Dump valve: oil is drained from the bottom of the main reservoir to an underground emergency tank.
- Turbine trip: the burner management system (BMS) cuts the fuel.
- Ventilation shutdown: dampers close, preventing smoke and oil vapour from spreading through the building.

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, FM-200 clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 850, NFPA 15, NFPA 12, FM Global DS 7-101, IEEE 979. NFPA 850 Electric Generating Plants.