Pressure-flow table for a K57 sprinkler. Every value is calculated from Q = K√P, with Q in litres per minute and P in bar.

Metric K57 corresponds to roughly K4.0 in US units (gpm/psi½), with a conversion factor of 14.4. Typical application: The nominal K-factor for the LH (light hazard) class in EN 12845 Table 37a. K57 is not one of the NFPA 13 nominal values; the nearest in NFPA Table 7.2.2.1 is K4.2 (K60), with a range of 57–63.

Pressure-flow table (K57)

Pressure (bar)Flow (L/min)Flow (L/s)
0.5040.30.67
0.7047.70.79
1.0057.00.95
1.4067.41.12
1.7575.41.26
2.0080.61.34
2.5090.11.50
3.0098.71.65
3.50106.61.78
4.00114.01.90
5.00127.52.12
6.00139.62.33
7.00150.82.51
8.00161.22.69
10.00180.23.00
12.00197.53.29

Required pressure at common design combinations

The table below shows the pressure a K57 sprinkler requires for a given density and coverage area. The calculation: required flow = density × coverage area; required pressure = (flow / K)².

Density (mm/min)Coverage area (m²)Required flow (L/min)Required pressure (bar)
2.2512.027.00.22
5.0012.060.01.11
7.5012.090.02.49
10.009.090.02.49
12.509.0112.53.90
12.507.492.52.63

How to use it

  1. Take the design density (mm/min) from the hazard class.
  2. Find the coverage area (m²) from the sprinkler layout.
  3. Calculate the required flow by multiplying them.
  4. Read the required pressure from the table above, or calculate P = (Q/K)².
  5. Compare the result with the minimum sprinkler pressure: under EN 12845 13.4.4, 0.70 bar in LH, 0.35 bar in OH and 0.50 bar in HHP/HHS; under NFPA 13 28.2.4.11, 7 psi (0.5 bar) or the higher value in the listing. If the calculated pressure is lower, use the minimum and recalculate the flow.

The table gives the pressure at the sprinkler inlet. In the hydraulic calculation, pipe friction loss, fitting equivalent lengths and elevation are added on top; the pressure at the system entry point is their sum.

Points to watch

Frequently Asked Questions

How much does a K57 sprinkler flow at 4 bar?

114 L/min from Q = K√P. That value corresponds to the pressure at the sprinkler inlet.

What is the US-unit equivalent of metric K57?

Roughly K4.0. The conversion factor is 14.4, and the unit in which a catalogue gives the K value must always be confirmed.

Can the sprinkler operate below a table value?

No. You cannot go below the standard's minimum sprinkler pressure (EN 12845 13.4.4, NFPA 13 28.2.4.11) or the minimum operating pressure in the product's listing or approval; for ESFR sprinklers that limit is especially binding.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

NFPA 13 (2025) · EN 12845:2015+A2:2026 · EN 12259-1. Table values are calculated from Q = K√P; the manufacturer's approval document governs the product-specific minimum and maximum operating pressure.