EN 12845 design parameters for class OH3 — Ordinary Hazard Group 3: design density 5.00 mm/min, area of operation 216 m², water supply duration 60 minutes.

Which areas fall into this class?

OH3 examples from Table A.2: department stores and shopping centres, glass factories, electronics and radio equipment factories, car workshops, paper and cardboard factories, book binding, woodworking and furniture factories (without foam plastics), weaving and clothing factories, railway stations, plant rooms and farm buildings. See the Annex A article for the full list and edge cases.

Design parameters

ParameterValue
Design density5.0 mm/min
Area of operation (wet / pre-action)216 m²
Area of operation (dry / alternate)270 m²
Water supply duration (8.1.1)60 minutes
Theoretical minimum sprinkler flow1080 L/min
Theoretical minimum water volume64.8 m³

The theoretical minimum values come only from density × area. The real design flow is higher because of hydraulic imbalance and the minimum sprinkler pressure, and hose reel and hydrant flows are added on top.

Required pressure by K-factor

The maximum area per sprinkler for OH3 is 12.0 m² (Table 19). A sprinkler covering that area needs 60.0 L/min. Table 37a permits nominal K80 / K115 sprinklers in this class, and under 13.4.4 the pressure at the most unfavourable sprinkler may not be less than 0.35 bar.

K-factorRequired flow (L/min)Pressure for density (bar)Table 37aPressure to use (bar)
K5760.01.11Not used in this class—
K8060.00.56Permitted0.56
K11560.00.27Permitted0.35
K16060.00.14Not used in this class—

Where the pressure calculated for the density is below the 0.35 bar floor of 13.4.4, 0.35 bar is used and the flow recalculated from Q = K√P.

Dry, alternate and pre-action installations

Under EN 12845 Table 3, the OH3 area of operation rises from 216 m² to 270 m² for dry or alternate (wet/dry) installations; the density does not change. Pre-action installations use the same area as wet installations (216 m²). Dry pipe installations are only installed where there is a risk of frost or the temperature exceeds 70 °C (11.2.1). NFPA 13 instead increases the design area by 30% for dry pipe and double interlock pre-action systems (19.2.3.2.6); the rules of the two standards are not interchangeable.

Classification is a decision; the table is a consequence. Whether an area falls into class OH3 — Ordinary Hazard Group 3 is determined by assessing its actual activity, stored materials and fire load, and defended with a written justification in the design report. If the classification is wrong, every number here is invalid.

Checklist

  1. Has the area's activity and stored material been defined in writing?
  2. Have sections of the same building in different classes been calculated separately?
  3. Where there is storage, have the storage rules been applied as well?
  4. Have hose reel and hydrant flows been added to the total demand?
  5. Have the water supply duration and volume been verified?
  6. Is there any planned operational change that could alter the class?

Frequently Asked Questions

What is the design density for class OH3?

Under EN 12845 Table 3, 5.0 mm/min over an area of operation of 216 m², with a 60 minute water supply duration (8.1.1).

What minimum water volume does OH3 need?

A theoretical minimum of 64.8 m³ (density × area × duration). The real volume is higher because of hydraulic imbalance, minimum sprinkler pressure and hose reel and hydrant flows.

Do these values change on a dry system?

Under EN 12845 Table 3 the area of operation rises to 270 m² for dry or alternate installations; pre-action installations use the wet area. The 30% increase of NFPA 13 does not apply to an EN 12845 design.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

TS EN 12845+A2:2026 (EN 12845:2015+A2:2026) · NFPA 13 (2025). Table values are for information; the binding text is the current edition of the standard, and separate rules apply to storage.