A large power transformer is one of the most expensive and slowest-to-replace items on any site. In an oil-insulated unit, an internal arc can rupture the tank within seconds, release thousands of litres of oil and create a large pool fire. The production loss while waiting for a replacement is often as large as the direct damage. FM Global DS 5-4 Transformers addresses this risk both by preventing the electrical failure and by limiting the spread of fire and damage.
Scope
The data sheet covers liquid-insulated (mineral oil, natural or synthetic ester, silicone) and dry-type transformers, indoors and outdoors. It is not only about fire protection: electrical protection, condition monitoring and maintenance aimed at preventing transformer failure are a major part of it. A typical loss chain runs as follows:
- An internal fault starts through insulation ageing, overload, lightning or poor maintenance.
- The internal arc vaporises oil rapidly and pressure rises suddenly inside the tank.
- The tank or a bushing ruptures and oil is released and ignites.
- The burning pool exposes the nearby building, other transformers and cable routes.
The logic of DS 5-4 is to put a measure at every link in that chain.
Key Loss-Prevention Principles
1. Prevent the failure: electrical protection and condition monitoring
Differential protection, sudden pressure relays, gas relays (Buchholz) and overcurrent protection aim to clear an internal fault before it grows. Dissolved gas analysis (DGA), oil quality tests, thermography and bushing inspections can warn of a failure weeks or months ahead. For FM these programmes are the first line of defence, ahead of fire protection.
2. Outdoors: separation
For outdoor transformers the primary measure is adequate distance to buildings and to each other. The distance depends on the liquid volume and the liquid type: larger for mineral oil, smaller for approved less-flammable liquids. Whether the building wall is combustible and has openings also affects the result. The current revision of the data sheet should be used for the separation tables.
3. Where distance cannot be achieved: fire barriers
If the layout does not allow the distance, a fire-resistant barrier is placed between transformers or between transformer and building. Its height and width are sized to extend beyond the equipment so that it cuts off flame and radiation from the main tank, conservator and bushings. The barrier should also withstand fragments thrown out in a rupture.
4. Oil containment and drainage
A pit or bund below the transformer collects released oil and limits the fire area. A fill of coarse gravel or crushed stone reduces burning at the surface. Collected oil and firewater should be routed through an oil separator to a safe point, and the pit must not fill up and overflow with rainwater.
5. Indoor transformers
Oil-filled units inside buildings should be in a separate fire-resistant room (vault), with sills and drainage that keep oil inside. Indoors, approved less-flammable liquids or dry-type units reduce the risk significantly. The room is protected by sprinklers or water spray where needed.
6. Active protection
Where separation and barriers fall short, or the transformer is close to a critical building, water spray is added, designed together with DS 4-1N. The purpose of water spray is often less to extinguish the fire than to protect adjacent structures and equipment from radiation and keep the fire under control.
7. Spares and continuity
Large transformers can have long lead times. A spare unit, a mobile transformer or an alternative supply plan is what really determines the business interruption loss. At FM surveys this question matters at least as much as fire protection. The spare itself should not be stored where the same fire could reach it.
How It Differs from NFPA and IEC Practice
| Topic | Typical reference | FM DS 5-4 emphasis |
|---|---|---|
| Power plant transformers | NFPA 850 | Similar separation logic; redundancy from the insurer's viewpoint |
| Indoor transformer rooms | NFPA 70 (NEC) and local wiring rules | Preference for approved less-flammable liquid or dry type |
| Outdoor substations | IEC 61936-1 | Distance by liquid type and volume; barriers; containment |
| Water spray | NFPA 15 | An added layer where passive measures fall short |
NFPA 15 gives the commonly cited density of 10.2 L/min·m² (0.25 gpm/ft²) for transformer surfaces. The FM difference is that, before reaching that table, it asks about failure prevention, separation, barriers and containment. FM also makes liquid selection a fire protection tool by allowing relaxed separation for approved less-flammable liquids and transformers filled with them.
Practical tip: on a new factory project, transformer positions are often chosen by the electrical designer to minimise cable cost. Checking separation and barriers before the layout is frozen is far cheaper than adding a fire wall or water spray later.
Practical Checklist
- Transformer inventory: rating, liquid type, liquid volume, location (indoor/outdoor).
- Differential, sudden pressure and gas relays are in service and tested.
- DGA, oil testing and thermography are carried out regularly.
- Outdoor separation to buildings and adjacent units is checked against the current data sheet.
- Where distance is insufficient, a suitably sized fire barrier is in place.
- Containment pit, stone fill and drainage work together with an oil separator.
- Indoor units are in fire-resistant rooms; less-flammable liquid or dry type has been considered.
- Water spray is designed to DS 4-1N where needed.
- A spare transformer or alternative supply plan is documented.
Frequently Asked Questions
What most often causes transformer fires?
Internal electrical faults, insulation ageing and bushing failures lead the list. That is why FM puts electrical protection and condition monitoring ahead of fire protection.
What does a less-flammable liquid gain?
Approved high fire point liquids such as esters or silicone are harder to ignite. The data sheet may allow smaller separations and lighter protection for them.
Does every transformer need water spray?
No. With adequate separation, barriers and containment it is often unnecessary. Water spray is added where passive measures fall short.
Why is the containment pit filled with gravel?
The stone fill breaks up the surface of burning oil flowing into the pit and limits its contact with air, helping to smother or reduce the flames. The fill needs maintenance so it does not clog with dust and sediment.
Are dry-type transformers free of fire risk?
The risk is lower but not zero. Overheating and insulation failure remain possible, so maintenance and temperature monitoring are still needed.

SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.
Download SprinkCalc on the App Store
MEP Calc — 86+ Engineering Calculators
MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App StoreFM Global Property Loss Prevention Data Sheet 5-4, Transformers; NFPA 850; NFPA 15; NFPA 70; IEC 61936-1. This page is a summary in our own words, not the data sheet text. Download and design to the current revision from fmglobal.com.