Clinker, cement, bypass dust and fuel silos at cement plants need special protection against dust explosion. Clinker itself does not burn but coal/petcoke, bypass dust and fly ash can. NFPA 68 deflagration venting and NFPA 69 explosion prevention (inerting) offer silo protection options.
Silo Types and Risk
- Coal dust silo: St1 (Kst 50-150)
- Petcoke silo: upper end of St1 (Kst 150-200)
- Clinker bypass dust: alkali salts, dust - self-heating with moisture
- Fly ash silo: St1 (from thermal plant)
- Cement silo: non-combustible (CaCO3-CaO-CaSO4)
NFPA 68 Vent Calculation
The required vent area is calculated with the equations of the current edition of NFPA 68, using the measured Kst and Pmax of the dust, the silo volume (V) and the target reduced explosion pressure (Pred); the dust's laboratory data is the basis of the calculation.
500 m3 coal silo, Kst 150, Pmax 8 bar, Pred 0.5 bar, using the EN 14491 equation (same as VDI 3673):
- A = B × [1 + C × log(L/D)]
- B = [3.264·10−5 × Pmax × KSt × Pred−0.569 + 0.27 × (Pstat − 0.1) × Pred−0.5] × V0.753
- C = −4.305 × log Pred + 0.758 (pressures in bar, KSt in bar·m/s, V in m3, A in m2)
- Assumed: vent static burst pressure Pstat = 0.1 bar, silo L/D = 1
- B = [3.264·10−5 × 8 × 150 × 0.5−0.569 + 0.27 × 0] × 5000.753 = 0.0581 × 107.7 = 6.26 m2
- C = −4.305 × log 0.5 + 0.758 = 2.05; for L/D = 1, log(L/D) = 0 → A ≈ 6.3 m2
- A slender silo needs more area: A ≈ 10.1 m2 for L/D = 2 and A ≈ 12.4 m2 for L/D = 3; if the vent efficiency is below 1, divide the area by it (A/η)
- Validity range of the equation: 0.1 ≤ Pred ≤ 1.5 bar; 0.1 ≤ Pstat ≤ 1 bar; 5 ≤ Pmax ≤ 10 bar (KSt ≤ 300 bar·m/s); 0.1 ≤ V ≤ 10,000 m3
- NFPA 68 uses its own equation: Equation 8.2.2 (Av0) for L/D ≤ 2 and 8.2.3 (Av1) for 2 < L/D ≤ 6, with limits Pstat ≤ 0.75 bar, 10 ≤ KSt ≤ 800 bar·m/s, 0.1 ≤ V ≤ 10,000 m3 and 5 ≤ Pmax ≤ 12 bar. The two methods can give different results; design to the current edition of the standard that applies.
- Placement: upper half of silo, straight vent duct
St Class and Kst
- St0: Kst = 0 (non-combustible)
- St1: Kst 1-200 (most common - coal, petcoke, flour, sugar)
- St2: Kst 200-300 (some reactive organic dusts)
- St3: Kst >300 (metal dust - Al, Mg)
- Kst measurement: 1 m3 KSEP test (VDI 2263)
Panel Design
- Bursting pressure: Pstat = 0.1-0.2 bar
- Panel efficiency: Ef = 0.5 (with vent duct)
- Flame vent direction: no personnel, minimal debris
- Isolation valve: NFPA 69 isolation - prevents a secondary explosion propagating to connected equipment
- Recoil: silo opposite side loaded - support required
NFPA 69 Inerting Alternative
- N2 inerting: O2 <8 percent for coal
- CO2 inerting: alternative, lower cost
- LOC: coal 14 percent, petcoke 12 percent
- HRD suppression: 25 kg monoammonium phosphate at 50 bar

Silo venting with MEP Calc
MEP Calc sizes cement/coal silo NFPA 68 Av panel area, St class, Kst and NFPA 69 inerting calculations.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 68, NFPA 69, NFPA 652, NFPA 664, VDI 2263, FM DS 7-76. NFPA 68 Explosion Venting standard.