AI and HPC GPU clusters now routinely reach 50-100 kW per rack. Air cooling cannot keep up at that level, so immersion cooling — submerging the hardware in dielectric fluid — has become necessary. Novec 7100 boils at 61°C (3M product data), while hydrocarbon mineral oil has a flash point around 280°C. On the fire-protection side, the reference is NFPA 75, the standard for fire protection of information technology equipment; its 2017 edition has no provision specific to immersion cooling.

Immersion Types

  • Single-phase: mineral oil bath, flash point 280°C; the fluid stays liquid and is cooled externally by pumping
  • Two-phase: fluids such as Novec 649 boil at 49°C and condense back on a condenser above the tank
  • Synthetic hydrocarbon: the SpectraSyn family; cleaner and more stable than mineral oil
  • Fluorinated fluids: Novec production is being phased out after 2025; supply will tighten
  • Global warming potential (GWP): mineral oil 0, Novec family 1-300

NFPA 75 Protection

  • Flash point: where oil or an equivalent liquid is used for cooling, the unit liquid must have a closed-cup flash point of at least 149°C (300°F), in a sealed container with automatic pressure relief (NFPA 75 8.2)
  • Sprinkler: information technology equipment areas in a sprinklered building have an automatic sprinkler system installed to NFPA 13 (NFPA 75 9.1.1, 9.1.2); sprinkler type and density come from NFPA 13
  • aspirating smoke detection: sampling sampling pipes run between racks
  • Clean agent: NFPA 2001 systems are not required for immersion tanks, but are still used in critical shared areas
  • Drainage: the floor must allow removal of liquid coolant leaks by floor drains, liquid containment with removal pumps, or another method approved by the authority having jurisdiction (NFPA 75 6.3.3, 6.3.3.1); the standard gives no containment volume

GPU Cluster Power

  • H100-class GPU: typically 700 W per GPU
  • Rack: rack load of 50-100 kW; at 700 W per GPU that is roughly 70-140 GPUs per rack
  • Immersion tank: a typical tank circulates about 2,000 L of dielectric fluid
  • Pump: the target is 20-30 m³/h coolant circulation
  • Coolant Distribution Unit (CDU): the heat exchanger between the tank and the external cooling tower

Risk Management

  • Electrical fault: the dielectric fluid quenches arcing; fire growth risk is markedly lower than in an air-cooled rack
  • Leak: a bunded floor with leak detection can be evaluated as an alternative to drainage through the risk analysis (NFPA 75 6.3.4)
  • Odor: mineral-oil systems have a characteristic smell; plan ventilation accordingly
  • Biological growth: not expected in water-free dielectric fluids, but periodic samples are still taken
  • Retrofit: converting an existing air-cooled hall to immersion takes about 6 months on site

AI Data Center Trends

  • Largest AI training clusters: single clusters of 100,000 GPUs run on immersion cooling
  • Hyperscale AI campuses: announced plans foresee around 500 MW per campus
  • Turkey: hyperscale investment is accelerating at major telecom operators' data center campuses
  • PUE: about 1.4 in a typical air-cooled hall, around 1.05 with immersion
  • Liquid metal cooling: on the post-2030 roadmap, currently in R&D

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

NFPA 75, NFPA 76, ASHRAE TC 9.9, Open Compute Project, EN 50600. NFPA 75 Fire Protection of IT Equipment.