AI and HPC GPU clusters now routinely reach 50-100 kW per rack. Air cooling cannot keep up at that level, so immersion cooling — submerging the hardware in dielectric fluid — has become necessary. Novec 7100 boils at 61°C (3M product data), while hydrocarbon mineral oil has a flash point around 280°C. On the fire-protection side, the reference is NFPA 75, the standard for fire protection of information technology equipment; its 2017 edition has no provision specific to immersion cooling.
Immersion Types
- Single-phase: mineral oil bath, flash point 280°C; the fluid stays liquid and is cooled externally by pumping
- Two-phase: fluids such as Novec 649 boil at 49°C and condense back on a condenser above the tank
- Synthetic hydrocarbon: the SpectraSyn family; cleaner and more stable than mineral oil
- Fluorinated fluids: Novec production is being phased out after 2025; supply will tighten
- Global warming potential (GWP): mineral oil 0, Novec family 1-300
NFPA 75 Protection
- Flash point: where oil or an equivalent liquid is used for cooling, the unit liquid must have a closed-cup flash point of at least 149°C (300°F), in a sealed container with automatic pressure relief (NFPA 75 8.2)
- Sprinkler: information technology equipment areas in a sprinklered building have an automatic sprinkler system installed to NFPA 13 (NFPA 75 9.1.1, 9.1.2); sprinkler type and density come from NFPA 13
- aspirating smoke detection: sampling sampling pipes run between racks
- Clean agent: NFPA 2001 systems are not required for immersion tanks, but are still used in critical shared areas
- Drainage: the floor must allow removal of liquid coolant leaks by floor drains, liquid containment with removal pumps, or another method approved by the authority having jurisdiction (NFPA 75 6.3.3, 6.3.3.1); the standard gives no containment volume
GPU Cluster Power
- H100-class GPU: typically 700 W per GPU
- Rack: rack load of 50-100 kW; at 700 W per GPU that is roughly 70-140 GPUs per rack
- Immersion tank: a typical tank circulates about 2,000 L of dielectric fluid
- Pump: the target is 20-30 m³/h coolant circulation
- Coolant Distribution Unit (CDU): the heat exchanger between the tank and the external cooling tower
Risk Management
- Electrical fault: the dielectric fluid quenches arcing; fire growth risk is markedly lower than in an air-cooled rack
- Leak: a bunded floor with leak detection can be evaluated as an alternative to drainage through the risk analysis (NFPA 75 6.3.4)
- Odor: mineral-oil systems have a characteristic smell; plan ventilation accordingly
- Biological growth: not expected in water-free dielectric fluids, but periodic samples are still taken
- Retrofit: converting an existing air-cooled hall to immersion takes about 6 months on site
AI Data Center Trends
- Largest AI training clusters: single clusters of 100,000 GPUs run on immersion cooling
- Hyperscale AI campuses: announced plans foresee around 500 MW per campus
- Turkey: hyperscale investment is accelerating at major telecom operators' data center campuses
- PUE: about 1.4 in a typical air-cooled hall, around 1.05 with immersion
- Liquid metal cooling: on the post-2030 roadmap, currently in R&D

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 75, NFPA 76, ASHRAE TC 9.9, Open Compute Project, EN 50600. NFPA 75 Fire Protection of IT Equipment.