Metro (subway) stations operate fire-protection equipment under harsh conditions (vibration, dust, humidity, 24/7). NFPA 130 applies to fixed guideway systems, and NFPA 25 governs ITM. Reliability depends on strict daily and weekly discipline.
Daily Checks
- Control panel: normal/trouble lamps
- Sprinkler valve: OS&Y valve locked in the open position
- Portable extinguisher: in place, sealed
- Emergency light: lit, tested
- Pump room: leaks, oil level
Weekly Tests
- Diesel pump: 30-min no-flow test
- Jockey pump: running pressure check
- Fire alarm: random smoke test on 1 detector
- Smoke damper: manual operation in 1/8 of zones
- PA system: announcement test
Monthly Tests
- Standpipe: pressure-flow check
- Electric pump: no-flow test, minimum 10 min run; weekly for pumps serving buildings beyond fire department pumping capacity, limited service controllers, vertical turbine pumps or suction from ground-level tanks, otherwise (and with a redundant pump) monthly (NFPA 25-2026 8.3.1.2, 8.3.2.3)
- Hydrant: flow measurement on internal and external hydrants
- Stair lighting: luxmeter measurement
- Sprinkler vibration points: simulation of train-induced vibration effects
Annual Tests
- Sprinkler: visual inspection, deflector and orifice cleaning
- Tunnel jet fan: full operational test
- Alarm: all zones actual test
- Hydrostatic test: every 5 years on manual standpipe systems and semiautomatic dry standpipe systems (including FDC piping), at least 200 psi (13.8 bar) for 2 hours, or maximum pressure + 50 psi where maximum exceeds 150 psi; manual wet standpipes in combined sprinkler/standpipe systems exempt; FDC piping to the check valve 150 psi (10 bar) for 2 hours every 5 years (NFPA 25-2026 6.3.2.1, 13.8.5)
- Annual pump flow test: at no-flow (churn), rated flow and 150 percent of rated flow; electric pumps run at least 10 min, diesel pumps at least 30 min before shutdown (NFPA 25-2026 8.3.3.1, 8.3.3.10)
Field Experience
- Tube tunnel: weekly 3-TPH drill
- Major transfer station: monthly zone-valve test
- Airport link: 24/7 fire brigade
- Record-keeping: NFPA 25 form signed
- Most chronic issue: train vibration loosens sprinkler connections

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, FM-200 clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 130, NFPA 25, NFPA 72, APTA-PR-E-RP-003, UIC IRS 70105. NFPA 130 Transit code.