A Fluid Catalytic Cracking (FCC) unit turns heavy hydrocarbon residue into gasoline. The riser runs at 520 C, the regenerator at 720 C and 4-5 bar. The Texas City 2005 blast killed 15. NFPA 30, API 2510 and API RP 752 cover FCC fire protection.
FCC Process
- Feed: VGO 350 C
- Catalyst: Zeolite 5-100 micron
- Riser: 520 C, 2-3 s contact
- Regenerator: 720 C cat combustion
- Capacity: 40,000-100,000 bpd
Riser and Catalyst Risk
- Erosion: Catalyst wears metal
- Feed pipe hot spot: 750 C
- Expander: Flue gas 720 C turbine
- Slurry pump: Seal fire
- Hot rotating: Steam curtain
Water Spray NFPA 15
- Vessel exposure: 10.2 L/min/m2
- Riser: 20.4 L/min/m2 special
- Structural steel: 4.1 L/min/m2 column
- Monitor nozzle: 20 L/s 45 m range
- Duration: 4 hours
Texas City 2005 Lessons
- Incident: Isomerization unit overfill
- Dead: 15, injured 180
- Cause: Trailer siting
- CSB report: Safety culture
- MOC: Management of Change mandatory
Turkish Refinery FCC
- Tupras Izmir Aliaga: FCC 40,000 bpd
- Tupras Kirikkale: Unit 2
- STAR Aliaga: SOCAR 2018
- BYKHY Annex-12: Petrochemical
- SEVESO III: Upper-tier

MEP Calc — 86+ Engineering Calculators
MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, FM-200 clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 30, NFPA 15, API 2510, API RP 752, CSB Texas City. NFPA 30 Flammable and Combustible Liquids.