All three are sprinklers, but each carries a different fire philosophy. CMDA controls the fire by wetting it, CMSA controls it by overcoming the fire plume with large droplets, and ESFR aims to suppress it outright. Choosing the wrong mode changes the pump pressure, the tank volume and the rack design together.

The distinction in one line each

Side by side

Values are from the NFPA 13-2025 tables; where EN 12845-2:2024 differs, it is stated.

ParameterCMDACMSAESFR
ObjectiveControlControlSuppression
Design inputDensity × areaSprinkler count × minimum pressure12 sprinklers (4 × 3) × minimum pressure (NFPA 23.2.2)
K-factorTypically K5.6–K11.2 (K80–K160)K11.2–K25.2 (K160–K360) (Tables 22.2–22.5); EN 12845-2 also has K33.6 (K480) on dry systemsK14–K25.2 (K200–K360) (Table 23.3.1); EN 12845-2 Table 7 also has K28 (K400) and K33.6 (K480)
Minimum operating pressureCalculated from density and K-factor0.7–5.2 bar (Table 22.4)1.0–5.2 bar (Table 23.3.1)
Sprinklers in the designDerived from the design areaMostly 15 on wet (20 in some options); 25–36 on dry (Table 22.4)12 (4 × 3)
ResponseTypically standard responseQuick or standard response (NFPA 22.1.1–22.1.2)Fast response
Max ceiling slopeMore flexible4 in 12 (≈18.4°; NFPA 13.2.1.2); EN 12845-2: 10° (5.2.1)4 in 12 (≈18.4°; NFPA 14.2.3); EN 12845-2: 10° (5.2.1)
In-rack sprinklersRequired for racks over 7.6 m (NFPA 21.4.2.1 → Chapter 25)Required in some table optionsUsually unnecessary (except solid shelving)
On a dry systemPermittedPermitted (where the table has a dry option)Wet only (NFPA: except specific listings; EN 12845-2: no dry installation option, an installation with dry pendent ESFR is treated as wet, propylene glycol designs with K320 or larger and tree pipework may be used, 6.5)
Water supply duration (NFPA Table 20.15.2.6)60–150 min by design area60–150 min by sprinkler count (13–15 sprinklers: 90 min)60 min up to 12 sprinklers

A numerical comparison on 9 m storage

Under NFPA 13-2025: rack storage, Class III commodity, 9 m storage height, 12 m ceiling, wet system. Flows are calculated from the minimum pressure at each sprinkler (Q = K·√P); hydraulic imbalance is not included, so the real demand is higher.

Mode and basisSprinkler demandHose allowanceTotal flowDurationWater volumeIn-rack
CMDA plus in-rack (Figure 25.4.3.1.1.2(a)–(g): 12.2 mm/min over 185 m², ordinary temperature; in-rack 10 × 114 L/min)2,257 + 1,140 = 3,397 L/min1,900 L/min≈ 5,300 L/min120 min≈ 636 m³Required (at most 3.0 m of storage above the top in-rack level)
CMSA, ceiling only (Table 22.4: K25.2 (K360) pendent, 15 sprinklers, 1.6 bar)15 × 455 = 6,830 L/min1,900 L/min≈ 8,730 L/min90 min≈ 786 m³None
ESFR, ceiling only (Table 23.3.1: K25.2 (K360) pendent, 12 sprinklers, 1.7 bar)12 × 469 = 5,630 L/min950 L/min≈ 6,580 L/min60 min≈ 395 m³None

Three lessons from that table: thanks to its 60-minute duration and smaller hose allowance, ESFR needs the smallest water volume; CMSA produces the highest flow and the largest tank; CMDA has a low ceiling flow but leaves you carrying the in-rack maintenance burden for the life of the building. The pump pressure depends on the pipe network and elevation and comes from the hydraulic calculation.

Decision tree

  1. Storage up to 4 m, light or ordinary hazard → CMDA. No argument needed.
  2. Storage of 4 to 7 m, or a specific commodity such as rubber tyres or paper rolls → CMSA.
  3. Storage of 6 m or more, suitable ceiling slope, limited skylights, wet system → ESFR.
  4. Ceiling slope above 4 in 12 (NFPA) or 10° (EN 12845-2) → neither ESFR nor CMSA can be applied directly; consider a flat false ceiling or the in-rack solution (EN 12845-2 5.2.1), or CMDA plus in-rack.
  5. Cold store or freezing risk → ESFR is out (unless an ESFR specifically listed for dry or preaction use exists under NFPA; EN 12845-2 has no dry installation option, but unheated areas may use dry pendent ESFR (treated as a wet installation) or a propylene glycol design with K320 or larger and tree pipework, 6.5).
  6. Open-top containers → ESFR is not permitted (NFPA 23.1.3.2). Solid shelf racking → ESFR only together with in-rack sprinklers to Chapter 25 (23.1.3.1).

The design height trap: an ESFR design is valid only up to a defined maximum storage and ceiling height (NFPA Table 23.3.1). If the racking rises five years later the design is no longer valid, and the insurer will raise that at a claim. A five-year growth projection belongs in the design.

Maintenance and life cost

ESFR's strongest feature is that the sprinklers are only at ceiling level: no entering the racking, no emptying product, no hunting for a damaged sprinkler. CMSA and CMDA with in-rack branches create an access problem every year. Over ten years of total ownership cost, ESFR comes out ahead in most warehouses; on first cost it falls behind, because of the pump and the pipe sizes.

Frequently Asked Questions

What is the basic difference between ESFR and CMSA?

ESFR aims at suppression; in NFPA 13 the design is generally based on the most demanding 12 sprinklers (23.2.2) at minimum pressures of 1.0 to 5.2 bar from Table 23.3.1. CMSA controls the fire, mostly with 15 sprinklers on wet systems and 25 to 36 on dry systems, at 0.7 to 5.2 bar from Table 22.4. In both modes the criteria are taken from the standard's tables by commodity class, storage height and ceiling height.

When is ESFR ruled out?

Where the ceiling slope exceeds 4 in 12 (about 18.4°; NFPA 13 14.2.3) or 10° under EN 12845-2 (5.2.1); with open-top containers (NFPA 23.1.3.2); in spaces at risk of freezing (unless an ESFR specifically listed for dry or preaction use is available); on solid shelf racking unless in-rack sprinklers are added (23.1.3.1); and where the clearance between sprinklers and the top of storage falls below 900 mm in NFPA (14.2.11) or 1 m in EN 12845-2 (5.1.3.7).

Which mode is cheapest?

Usually CMDA on first cost, because the pump and pipe sizes are smaller. But over ten years ESFR comes out ahead in most warehouses, because there is no in-rack sprinkler maintenance.

Can ESFR be used on a dry system?

Under NFPA 13 14.2.2 ESFR is used on wet systems; ESFR sprinklers specifically listed for dry or preaction use are the exception. Under EN 12845-2 ESFR is used on wet systems only. Specifically listed dry-type ESFR products are limited and the water demand increases.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

NFPA 13 (2025) Chapter 14 and the storage chapters (20–25). EN 12845:2015+A2:2026 and EN 12845-2:2024. EN 12259-13 (ESFR sprinklers). FM Global DS 8-9. Values are for information only.