Pressure-flow table for a K115 sprinkler. Every value is calculated from Q = K√P, with Q in litres per minute and P in bar.

Metric K115 corresponds to roughly K8.0 in imperial units (conversion factor 14.4). Typical application: Common in ordinary and high hazard process areas.

Pressure-flow table (K115)

Pressure (bar)Flow (L/min)Flow (L/s)
0.5081.31.36
0.7096.21.60
1.00115.01.92
1.40136.12.27
1.75152.12.54
2.00162.62.71
2.50181.83.03
3.00199.23.32
3.50215.13.59
4.00230.03.83
5.00257.14.29
6.00281.74.69
7.00304.35.07
8.00325.35.42
10.00363.76.06
12.00398.46.64

Required pressure at common design combinations

The table below shows the pressure a K115 sprinkler requires for a given density and coverage area. The calculation: required flow = density × coverage area; required pressure = (flow / K)².

Density (mm/min)Coverage area (m²)Required flow (L/min)Required pressure (bar)
2.2512.027.00.06
5.0012.060.00.27
7.5012.090.00.61
10.009.090.00.61
12.509.0112.50.96
12.507.492.50.65

How to use it

  1. Take the design density (mm/min) from the hazard class.
  2. Find the coverage area (m²) from the sprinkler layout.
  3. Calculate the required flow by multiplying them.
  4. Read the required pressure from the table above, or calculate P = (Q/K)².
  5. Compare the result with the minimum sprinkler pressure the standard requires; if it is lower, use the minimum and recalculate the flow.

The table gives the pressure at the sprinkler inlet. In the hydraulic calculation, pipe friction loss, fitting equivalent lengths and elevation are added on top; the pressure at the system entry point is their sum.

Points to watch

Frequently Asked Questions

How much does a K115 sprinkler flow at 4 bar?

230.0 L/min from Q = K√P. That value corresponds to the pressure at the sprinkler inlet.

What is the imperial equivalent of metric K115?

Roughly K8.0. The conversion factor is 14.4, and which unit a catalogue uses must always be confirmed.

Can the sprinkler operate below a table value?

No. You cannot go below the minimum operating pressure defined in the product's approval document; for ESFR heads that limit is especially binding.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 86+ Engineering Calculators

MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

NFPA 13 (2025) · BS EN 12845:2015+A1:2019 · EN 12259-1. Table values are calculated from Q = K√P; the manufacturer's approval document governs the product-specific minimum and maximum operating pressure.

FS

Fatih Selvi

Mechanical engineer and software developer. 16+ years of MEP and fire protection field experience.