Short answer: BS EN 12845+A2:2026 Clause E.1, EN p.139: the requirements of this annex shall apply to the sprinkler protection of multi-storey buildings where the difference in height between the highest and the lowest sprinkler exceeds 45 m. The requirements may be applied to buildings designed for occupancies where the hazard is not greater than OH3; high-rise systems with a hazard greater than OH3 require specific fire engineering solutions and expert advice should be sought. Clause 5.5, EN p.30 repeats the same 45 m threshold.

Annex E (normative, EN p.139-142) of BS EN 12845+A2:2026 (EN 12845:2015+A2:2026) specifies the particular requirements for sprinkler protection in high-rise buildings. The annex is a short and precise text: three main clauses (E.1, E.2, E.3) and two typical layout figures. The content of the annex and the body clauses linked to it are set out below in order.

1. The threshold: 45 m

Clause E.1 General (EN p.139): The requirements of this annex shall apply to the sprinkler protection of multi-storey buildings where the difference in height between the highest and the lowest sprinkler exceeds 45 m.

The same threshold also appears in the body. Clause 5.5 (EN p.30): where the difference in height between the highest and the lowest sprinklers in a system or building exceeds 45 m, the requirements of Annex E shall apply. In addition, the difference in height between the highest and the lowest sprinkler in an installation connected to a single control valve set shall not exceed 45 m.

The criterion is not the number of storeys or the height of the building but the vertical difference between the sprinklers.

2. The hazard class limit

Clause E.1 (EN p.139) continued: The requirements may be applied to buildings designed for occupancies where the hazard is not greater than OH3. High-rise systems with a hazard greater than OH3 require specific fire engineering solutions and expert advice should be sought.

Clause E.2.1 Hazard group (EN p.139): High-rise sprinkler systems shall comply with the requirements for Ordinary Hazard Group III (OH3) protection.

The design equivalent of OH3 is fixed by Table 3 (Clause 7.1, EN p.36): a density of 5.0 mm/min and an area of operation of 216 m² (wet or pre-action system). The water supply duration is 60 min for OH under Clause 8.1.1 (EN p.42).

3. Design criteria (Clause E.2)

E.2.2 Division of high-rise sprinkler systems

High-rise sprinkler systems must be split into separate sprinkler installations so that, within any one installation, the highest and lowest sprinklers are no more than 45 m apart in height (see Figures E.1 and E.2).

E.2.3 Standing water pressures at non-return and alarm valves

  • At the inlet of every non-return or alarm valve, the standing pressure must be at least 1.25 times the static head difference between that valve and the highest sprinkler of the installation.
  • Non-return valves that control flow into an installation must work correctly with a service-to-installation pressure ratio no higher than 1.16:1, measured by valve lift and pressure equalisation upstream of the non-return valve.

E.2.4 Calculation of distribution pipes for pre-calculated systems

The main distribution pipes (including risers and drops) between the highest design point in the installation and the zone subsidiary stop valve at the same floor level shall be sized by hydraulic calculation. The maximum friction loss shall not exceed 0.5 bar at a flow rate of 1 000 l/min (see 13.3.4.2).

When one installation protects several floor levels, the allowable pressure loss between a lower-level design point and its zone subsidiary stop valve may be raised by the static head gained from the highest sprinkler of the installation down to the sprinklers on that level.

E.2.5 Water pressures

All pipes, fittings, valves and other equipment must be able to withstand the highest pressure they are likely to see. Where pressures would exceed 12 bar, the hydraulic alarm gongs may be fed through a pressure reducing valve, or from a secondary supply (a town main, for example) controlled by a diaphragm valve that is connected to the alarm port of the main installation control valve set.

4. The 12 bar rule and its high-rise exception

Clause 8.2.1 (EN p.42): Other than during testing, the water pressure shall not exceed 12 bar at the following equipment connections or locations (8.2.1.1, for all types of sprinkler system): a) sprinklers; b) multiple jet controls; c) water flow detectors; d) dry pipe and pre-action alarm valves; e) accelerators and exhausters; f) water motor alarms; g) zone control valves. The pressure in pumped systems shall take into account the increase in drive speed and pressure due to the closed valve condition.

8.2.1.2: in systems where the difference in height between the highest and the lowest sprinkler heads does not exceed 45 m, the same 12 bar limit also applies at: a) pump outlets; b) wet alarm valves; c) stop valves; d) mechanical pipe couplings.

Clause 8.2.2 (EN p.43): in high-rise sprinkler systems where the difference in height between the highest and the lowest sprinkler exceeds 45 m, and provided that all equipment subjected to a pressure higher than 12 bar is suitable for that purpose, the water pressures may exceed 12 bar at the following locations: a) pump outlets; b) risers and distribution pipes.

There is a related prohibition as well: when Clause 8.3 (EN p.43) lists the conditions for taking water from a sprinkler system for other services, item c) states that "the sprinkler system shall not be a high-rise system" and item d) that "the sprinkler system shall not protect a multi-storey building".

5. Water supplies (Clause E.3, EN p.140)

E.3.1 Types of water supply

At least one superior single water supply is required for the system.

E.3.2 Pressure and flow requirements for pre-calculated installations

The water supply must be designed so that the minimum pressure and flow of Table 6 are available at the outlet of the zone subsidiary stop valve; here ps is the pressure difference corresponding to the height of the highest sprinkler above the installation zone subsidiary stop valve.

The values in Table 6 (Clause 7.3.1, EN p.39) for an OH3 wet system: 1 100 l/min @ 1.7 + ps bar and a maximum demand of 1 350 l/min @ 1.4 + ps bar.

E.3.3 Water supply characteristics for pre-calculated installations

The water supply characteristics must be found by hydraulically calculating the pipework upstream of the zone subsidiary stop valve outlet at both the high and low flow rates of Table 6, and the calculation must also cover the water supply datum point.

E.3.4 Pump set performance for pre-calculated installations

The characteristics of automatic pump sets must conform to Table 16. NOTE: the pressures refer to the pump outlet (for multi-stage pumps, the relevant stage), measured on the discharge side of any orifice plate.

Table 16 (Clause 10.7, EN p.62) gives three height bands for OH3 wet or pre-action systems:

OH3 wet or pre-action Nominal data Characteristic 1 Characteristic 2
h ≤ 15 m 1.4 bar / 2 250 l/min 2.9 bar / 1 350 l/min 3.2 bar / 1 100 l/min
15 < h ≤ 30 m 2.0 bar / 2 700 l/min 4.4 bar / 1 350 l/min 4.7 bar / 1 100 l/min
30 < h ≤ 45 m 2.5 bar / 3 100 l/min 5.9 bar / 1 350 l/min 6.2 bar / 1 100 l/min

NOTE 2 (same table): in buildings exceeding the heights shown, it shall be proved that the pump characteristics are adequate to provide the flow rates and pressures specified in 7.3.1.

6. Figures E.1 and E.2: two typical layouts

Annex E shows two typical layouts (EN p.141-142): Figure E.1 a high-rise system fed by a pump set, Figure E.2 with gravity tanks and feed pumps. The key to both figures is the same and lists the mandatory components of the system: 1 storage tank, 2 multi-stage pump, 3 flow meter, 4 water supply datum point, 5 alarm valve station (with bypass arrangement), 6 flow test and zone drain, 7 zone subsidiary stop valve, 8 water flow alarm switch, 9 sprinkler head, 10 water flow alarm switch test valve and zone drain valve.

7. Other clauses linked to Annex E

  • Pump room (Clause 10.3.1, EN p.57): pump sets shall be housed in a compartment with a fire resistance of at least 60 min, used for no purpose other than fire protection. In order of preference: a separate building; a building adjoining a sprinkler protected building with direct access from outside; a compartment within a sprinkler protected building with direct access from outside.
  • Pump room temperature (Clause 10.3.3, EN p.58): at least 4 °C for electric pump sets, at least 10 °C for diesel pump sets.
  • Multiple pump arrangement (Clause 10.2, EN p.57): where two pumps are installed, each shall be capable of providing the specified flow rates and pressures independently; where three pumps are installed, each pump shall be capable of providing at least 50% of the specified flow rate at the specified pressure. Where more than one pump is installed on a superior or duplicate water supply, not more than one of them shall be driven by an electric motor.
  • Zoning (Annex D, EN p.136-137): the zone subsidiary stop valve, water flow alarm switch and zone test/drain facilities referred to by Annex E are defined in Annex D. The NOTE to D.1 states that zoning is required in Annex E and Annex F.
  • Fire resisting separation (Clause 5.3, EN p.30): the separation between a sprinkler protected area and an unprotected area shall have a fire resistance determined by the authority, but in no case less than 60 min.

Field note: The whole of Annex E rests on two ideas: limiting the static head seen by a single installation and guaranteeing that the valves also operate correctly under that head.

Frequently Asked Questions

To which buildings does Annex E apply?

BS EN 12845+A2:2026 Clause E.1, EN p.139: the requirements of this annex shall apply to the sprinkler protection of multi-storey buildings where the difference in height between the highest and the lowest sprinkler exceeds 45 m. The requirements may be applied to buildings designed for occupancies where the hazard is not greater than OH3; high-rise systems with a hazard greater than OH3 require specific fire engineering solutions and expert advice should be sought. Clause 5.5, EN p.30 repeats the same 45 m threshold.

To which hazard class is a high-rise system designed?

Clause E.2.1, EN p.139: high-rise sprinkler systems shall comply with the requirements for Ordinary Hazard Group III (OH3) protection.

How is a high-rise system divided?

Clause E.2.2, EN p.139: high-rise sprinkler systems must be split into separate sprinkler installations so that, within any one installation, the highest and lowest sprinklers are no more than 45 m apart in height (see Figures E.1 and E.2). Clause 5.5, EN p.30: the same 45 m maximum applies to the height difference between the highest and lowest sprinkler of an installation connected to a single control valve set.

What is the minimum standing pressure at the inlet of a non-return or alarm valve?

Clause E.2.3, EN p.139: at the inlet of every non-return or alarm valve, the standing pressure must be at least 1.25 times the static head difference between that valve and the highest sprinkler of the installation. Non-return valves that control flow into an installation must work correctly with a service-to-installation pressure ratio no higher than 1.16:1.

Where may the 12 bar limit be exceeded in a high-rise building?

Clause 8.2.1, EN p.42: other than during testing, the water pressure shall not exceed 12 bar at sprinklers, multiple jet controls, water flow detectors, dry pipe and pre-action alarm valves, accelerators and exhausters, water motor alarms and zone control valves. Clause 8.2.2, EN p.43: in high-rise systems where the difference in height between the highest and the lowest sprinkler exceeds 45 m, the pressure may exceed 12 bar at the pump outlets and in the risers and distribution pipes, provided that all equipment subjected to a pressure higher than 12 bar is suitable for that purpose.

References

  • BS EN 12845+A2:2026 (EN 12845:2015+A2:2026), Clauses 5.3 and 5.5 (EN p.30)
  • BS EN 12845+A2:2026, Clause 7.1 and Table 3 (EN p.35-36)
  • BS EN 12845+A2:2026, Clause 7.3.1 and Table 6 (EN p.39)
  • BS EN 12845+A2:2026, Clauses 8.1.1 and 8.2.1, 8.2.1.1 (EN p.42)
  • BS EN 12845+A2:2026, Clauses 8.2.1.2, 8.2.2 and 8.3 (EN p.43)
  • BS EN 12845+A2:2026, Clauses 10.2 and 10.3.1 (EN p.57), Clause 10.3.3 (EN p.58)
  • BS EN 12845+A2:2026, Clause 10.7 and Table 16 (EN p.62)
  • BS EN 12845+A2:2026, Annex D, Clause D.1 (EN p.136)
  • BS EN 12845+A2:2026, Annex E, Clauses E.1, E.2.1, E.2.2, E.2.3, E.2.4, E.2.5 (EN p.139)
  • BS EN 12845+A2:2026, Clauses E.3.1, E.3.2, E.3.3, E.3.4 (EN p.140)
  • BS EN 12845+A2:2026, Figure E.1 (EN p.141) and Figure E.2 (EN p.142)

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

BS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; BS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.