Short answer: BS EN 12845+A2:2026 Clause F.1 General, EN p.143: where required by national regulations, the following clauses apply. In other words, Annex F is not mandatory of itself; the clauses F.2 to F.8 become binding when national regulations call it up.

Annex F (normative, EN p.143-144) of BS EN 12845+A2:2026 (EN 12845:2015+A2:2026) is entitled "additional measures to improve the reliability and availability of the system". The annex is short: eight clauses, none of them longer than a few sentences. The clauses are set out below in the order in which they appear in the standard, with their content.

1. When Annex F comes into play

Clause F.1 General (EN p.143): "Where required by national regulations, the following clauses apply."

This single sentence establishes the status of the annex: Annex F is normative, but it is not self-triggering; what brings it into application is national regulations or the contract. The same relationship is also visible in the NOTE to Annex D (Clause D.1, EN p.136): zoning is optional unless required elsewhere in this standard; Annex E and Annex F are that "elsewhere".

2. F.2 Division into zones

In order to minimise the unprotected area in the event of a failure, installations shall be divided into zones in accordance with Annex D, with a protected floor area of not more than 2 400 m² per zone.

This requirement applies only to LH and OH.

For comparison, the limit in Annex D itself (Clause D.3.1, EN p.136) is 6 000 m² per zone. When Annex F comes into play, that limit drops to 2 400 m².

3. F.3 Wet pipe installations

Every sprinkler installation must be a wet pipe installation; a subsidiary dry pipe or alternate extension, if there is one, has to meet 11.5.

Clause 11.5.2 (EN p.69) gives the limit for these extensions: one subsidiary extension may contain at most 100 sprinklers, and where a single control valve set controls more than two subsidiary extensions, their combined sprinkler count must not exceed 250.

4. F.4 Sprinkler type and sensitivity

Quick response sprinklers shall be used; however, standard 'A' and special response sprinklers may be used in rooms with an area of not less than 500 m² or a height of not less than 5 m.

This clause is read together with the general sensitivity rule in the body. Table 38 (Clause 14.5.1, EN p.106):

Sensitivity rating In racks Ceiling above in-rack sprinklers Dry systems and Type A pre-action All others
Standard 'A' No Yes Yes Yes
Special No Yes Yes Yes
Quick Yes Yes No Yes

In other words, the quick response requirement of F.4 and the wet pipe requirement of F.3 complement each other: quick response sprinklers cannot be used in dry systems.

5. F.5 Control valve set

During the servicing and maintenance of the installation alarm valves, the sprinkler installation shall remain fully operational in all respects.

NOTE: in some countries duplicate installation control valve sets are required.

6. F.6 Water supplies

At least one superior single water supply is required for the system.

NOTE: in some countries duplicate supplies are required.

The same wording also appears in Annex E (Clause E.3.1, EN p.140).

7. F.7 Additional measures for theatres

In theatres with a separated stage (that is, those with a safety curtain between the stage and the auditorium):

  • The safety curtain must have a drencher line, controlled by a quick opening valve (for example a plug valve) placed where it can easily be reached.
  • The drenchers must draw their water from a point upstream of every control valve set.
  • The stage itself must be covered by a water spray installation that can be activated both automatically and manually.
  • As an alternative, a stage whose overall height is 12 m or less may be sprinkler protected instead.
  • Sprinkler protection is required for all workshops, dressing rooms, scenery and store rooms, and for the spaces below the stage.

The hazard class of theatres and cinemas is OH4 under Table A.2 (EN p.125) (the "Cinemas and theatres", "Concert halls" column).

8. F.8 Additional precautions for maintenance

  • Only one zone of a multi-zone installation shall be shut off at any one time. An installation or zone shall be kept shut off for the minimum time necessary for maintenance.
  • The partial or complete shutting off of a sprinkler installation shall be avoided wherever possible. Only the smallest part necessary shall be isolated.
  • When a zone (or zones) is filled or refilled with water after being drained, the flushing valves (see D.3.3) shall be used to check that water is present in the zone.
  • Where necessary, the individual alarm valves in a duplicate control valve set shall be taken into service separately, provided that the water supply to the installation is maintained.
  • Before a duplicate control valve set is serviced, this sequence must be followed: first open the stop valves of the standby alarm valve; then close the stop valves of the alarm valve to be serviced and run an alarm test (see 20.2.2.3) on the other alarm valve straight away. If no water is available, the stop valve must be reopened at once and the fault corrected before work continues.

The Clause 20.2.2.3 (EN p.119) referred to is the water motor alarm test in the weekly routine: each water motor alarm shall be sounded for at least 30 s.

9. Clauses not to be confused with Annex F

There are two neighbouring annexes that fall outside the scope of Annex F but relate to reliability:

  • Annex H (normative, EN p.153-154), Monitoring of sprinkler systems: all devices used for monitoring shall have a protection of at least IP 54 in accordance with EN 60529; not more than 15 non-addressable supervisory alarm devices shall be connected to a common indicator. The functions to be monitored: the position of all stop valves controlling the flow of water to the sprinklers (H.2.2); the position of other stop valves which could prevent the correct operation of an alarm or indicating device (H.2.3); critical fluid levels, with an indication before the water tank level falls more than 10% of the nominal fill level and before the fuel level falls more than 25% (H.2.4); pressures, where the static pressure on a town main falls below the calculated operating pressure and, in all other cases, where the static pressure falls more than 20% below the level tested (H.2.5); electrical power (H.2.6); the minimum temperature of the sprinkler valve room and the pump room (H.2.7).
  • Annex I (normative, EN p.155-156), Transmission of alarms: alarms shall be connected to an alarm panel in the sprinkler control room or the pump room and transmitted onwards according to the importance of the alarm. Alarms shall be transmitted to a continuously manned location, and type B alarms (technical alarms) may also be transmitted to a responsible person so that corrective action can be taken immediately. Table I.1 classifies each alarm as type A or type B; for example the water flow alarm is A, low town main pressure is B, electric pump set running is A and failure to start is B. Clause I.2: signals from water flow alarms and/or alarm valves shall be indicated as a fire alarm (level A); technical faults such as a power failure that could prevent the correct operation of the system shall be indicated as a fault alarm (level B).
  • Annex J (informative, EN p.157-158) gives the precautions to be taken and the procedures to be followed when the system is not fully operational; Annex K (informative, EN p.159) deals with the twenty-five year inspection and Annex M (informative, EN p.161) with the independent certification body.

Field note: Annex F is not a system of "reliability levels"; it is eight independent additional requirements that are applied together when national regulations call them up. If the contract states that "Annex F shall apply", its most visible effects are that the zone area drops from 6 000 m² to 2 400 m² and that the installation has to be of the wet pipe type.

Frequently Asked Questions

When does Annex F apply?

BS EN 12845+A2:2026 Clause F.1 General, EN p.143: where required by national regulations, the following clauses apply. In other words, Annex F is not mandatory of itself; the clauses F.2 to F.8 become binding when national regulations call it up.

What area limit per zone does Annex F impose?

Clause F.2, EN p.143: in order to minimise the unprotected area in the event of a failure, installations shall be divided into zones in accordance with Annex D and the protected floor area per zone shall not exceed 2 400 m². This requirement applies only to LH and OH.

Which sprinkler type does Annex F require?

Clause F.4 Sprinkler type and sensitivity, EN p.143: quick response sprinklers shall be used; however, standard 'A' and special response sprinklers may be used in rooms with an area of not less than 500 m² or a height of not less than 5 m.

What does Annex F require of the water supply?

Clause F.6 Water supplies, EN p.143: at least one superior single water supply is required for the system. NOTE: in some countries duplicate supplies are required. Likewise Clause F.5 Control valve set: the sprinkler installation shall remain fully operational in all respects during the servicing and maintenance of the installation alarm valves; NOTE: in some countries duplicate installation control valve sets are required.

Which additional measures does Annex F impose for theatres?

Clause F.7, EN p.143: in theatres with a separated stage (those with a safety curtain between the stage and the auditorium), the safety curtain must have a drencher line controlled by a quick opening valve placed where it can easily be reached, and the drenchers must draw their water from a point upstream of every control valve set. The stage itself must be covered by a water spray installation that can be activated both automatically and manually; as an alternative, a stage whose overall height is 12 m or less may be sprinkler protected instead. Sprinkler protection is required for all workshops, dressing rooms, scenery and store rooms, and for the spaces below the stage.

References

  • BS EN 12845+A2:2026 (EN 12845:2015+A2:2026), Clause 11.5.2 (EN p.69)
  • BS EN 12845+A2:2026, Clause 14.5.1 and Table 38 (EN p.106)
  • BS EN 12845+A2:2026, Clause 20.2.2.3 (EN p.119)
  • BS EN 12845+A2:2026, Table A.2 (EN p.125)
  • BS EN 12845+A2:2026, Annex D, Clauses D.1 and D.3.1, D.3.3 (EN p.136)
  • BS EN 12845+A2:2026, Clause E.3.1 (EN p.140)
  • BS EN 12845+A2:2026, Annex F, Clauses F.1, F.2, F.3, F.4, F.5, F.6, F.7 (EN p.143)
  • BS EN 12845+A2:2026, Clause F.8 (EN p.144)
  • BS EN 12845+A2:2026, Annex H, Clauses H.1, H.2.2, H.2.3, H.2.4, H.2.5 (EN p.153), H.2.6 and H.2.7 (EN p.154)
  • BS EN 12845+A2:2026, Annex I, Clause I.1 and Table I.1 (EN p.155-156), Clause I.2 (EN p.156)
  • BS EN 12845+A2:2026, Contents - Annexes J, K, M (EN p.9)

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

BS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; BS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.