The invisible detail holding up the sprinkler network: what spacing, what anchor, what clamp.

On an acceptance walk at a logistics warehouse, looking up, a DN100 distribution main was found hung between two steel trusses over a 4.5 m span from a single M10 threaded rod. Water-filled, the pipe masses about 17.5 to 24 kg per metre depending on wall thickness (NFPA 13-2025 Table A.18.5.9: 17.53 kg/m for Schedule 10, 24.10 kg/m for Schedule 40); the sag was visible to the naked eye. EN 12845 Clause 17.2.2 sets a maximum of 4 m for steel pipe; this project had 4.5 m and the exception condition — two independent supports, or a support capable of bearing a load 50 % greater than Table 40 — had not been met. Pipe support is the one detail skipped because nobody looks at it, and the one that can bring the whole installation down the night it is charged with water.

The basic rule

The pipe support section has three parts: general principles, spacing and position, and design parameters. First the principles:

  • Supports are fixed directly to the building, and where necessary to machinery, storage racking or another structure. No other service — ventilation, cable tray, lighting — may be hung from a sprinkler hanger.
  • Hangers must be of the adjustable type, so load is distributed evenly rather than concentrated at one overloaded point.
  • The clamp must fully encircle the pipe and must not be welded to the pipe or a fitting.
  • Pipe above 50 mm may not be hung from profiled metal decking or aerated concrete.
  • No support component may be of combustible material, and nails may not be used.
  • On copper pipe, an electrically insulating liner goes inside the clamp to prevent galvanic corrosion.

Hanger spacing — a one-line rule, not a table

EN 12845 does not give a row-by-row table by diameter the way NFPA 13 does. It sets a single rule:

  • Steel pipe: maximum 4 m spacing.
  • Copper pipe: maximum 2 m spacing.
  • Pipe above 50 mm: spacing may be increased by 50 % — 6 m for steel, 3 m for copper — provided one of two conditions is met:
    • Two independent supports fixed directly to the structure, or
    • A single support capable of carrying 50 % more than the tabulated load capacity.

In practice this summary works:

PipeDNStandard spacingWith the 50 % exception
Steel≤ 50 mm (DN25–DN50)4.0 m—
SteelDN65–DN1004.0 m6.0 m
SteelDN125–DN2004.0 m6.0 m
Copper≤ 50 mm2.0 m—
Copper> 50 mm2.0 m3.0 m

The standard does not state why copper needs closer supports. Engineering comment: copper's modulus of elasticity is markedly lower than steel's, so it deflects more over the same span and load.

Extra rules for mechanically jointed pipe

Mechanical joints such as grooved couplings are common on steel pipe, and the standard adds two conditions for mechanical joints:

  • At least one support within 1 m of every mechanical joint.
  • At least one support on every pipe length — a length with no support between two couplings is not acceptable.

Grooved pipe is less rigid between lengths than welded pipe; with no hanger, a turning moment develops at the coupling and the gasket leaks. So the 6 m exception is rarely applied on a grooved system — staying at 4 m is the safe practice.

Terminal sprinklers and the last support

An overlooked part of the clause is the sprinkler-to-support distance:

  • On DN25 pipe: no more than 0.9 m from the end sprinkler to the last support.
  • Above DN25: no more than 1.2 m.
  • On upright sprinklers: at least 0.15 m between support and sprinkler.

Additional support for vertical pipe

Vertical pipes must be supported as well as horizontal runs. Two limits apply:

  • Additional support for vertical pipes longer than 2 m.
  • Additional support for vertical pipes more than 1 m long feeding single sprinklers.

Pipes at a low level or otherwise vulnerable to mechanical impact (for example at risk of forklift impact) are separately supported; two exceptions apply — horizontal pipes less than 0.45 m long and drop or rise pipes less than 0.6 m long, each feeding an individual sprinkler, are exempt.

Design: hanger capacity and anchor size

The load capacity, cross-sectional area and anchor embedment of hanger components come from a table:

Nominal pipe diameterMin. load capacity (20 °C)Min. threaded sectionMin. anchor embedment (concrete)
d ≤ 50 mm200 kg30 mm² (M8)30 mm
50 < d ≤ 100 mm350 kg50 mm² (M10)40 mm
100 < d ≤ 150 mm500 kg70 mm² (M12)40 mm
150 < d ≤ 200 mm850 kg125 mm² (M16)50 mm

Three notes are critical:

  1. Load capacity must not fall by more than 25 % when the material is heated to 200 °C (NOTE 1 uses "should") — so the hanger does not sag during a fire.
  2. The nominal cross section of threaded rods should be increased so that the minimum cross section above is still achieved (NOTE 2). M10 is nominally 78 mm² but 52 mm² at the thread root — very close to the limit.
  3. The length of anchor bolts depends on the type used and on the quality and type of the material into which they are fixed; the values given are for concrete (NOTE 3). In aerated or lightweight concrete and in brick, the manufacturer's table differs.

A second table gives minimum flat bar and clamp dimensions:

Pipe diameterFlat bar (galvanised)Flat bar (black)Clamp (galvanised)Clamp (black)
d ≤ 50 mm2.5 mm3.0 mm25 × 1.5 mm25 × 3.0 mm
50 < d ≤ 200 mm2.5 mm3.0 mm25 × 2.5 mm25 × 3.0 mm

Table 41 requires a thicker minimum size for ungalvanised material. In humid ceiling voids — kitchens, wet areas — ungalvanised steel hangers are exposed to corrosion; stainless hangers should be specified around pools, laundries and near-freezing stores.

Fire resistance and materials

No part of any support may be made of combustible material, and nails shall not be used (Clause 17.2.1). That rules out combustible items such as plastic anchors, timber packers and nylon ties. In a fire, flame melts the plastic anchors first, the hanger drops, the pipe breaks and the system is out of service. Field practice:

  • Galvanised steel threaded rod with a galvanised clamp in dry areas.
  • 304 stainless in humid, chlorinated or external locations.
  • Concrete anchors: steel expansion anchors. Plastic-sleeved anchors are not accepted on sprinkler work.
  • Steel beam connections: beam clamps.

Seismic bracing: A2:2026 refers to EN 12845-3

For seismic bracing, BS EN 12845+A2:2026 Clause 13.1 gives the following recommendation: where an area is at risk of earthquakes as defined in EN 12845-3, applying the EN 12845-3 requirements to the sprinkler system is recommended; the note explains that the system then moves together with the building, which prevents leaks, pipe breaks and consequential damage. In Turkish seismic zones, leaving a sprinkler network on vertical hangers alone conflicts with the seismic bracing requirement of BYKHY Article 96(6). In practice, the corresponding NFPA 13 and FM Global provisions are applied:

  • NFPA 13-2025 18.5.5.1: lateral sway bracing on all feed and cross mains regardless of size and on branch lines and other piping of 65 mm (2½ in.) and larger.
  • Four-way bracing on risers; on horizontal pipe, lateral braces at no more than 12 m (40 ft) and longitudinal braces at no more than 24 m (80 ft) centres (NFPA 13-2025 18.5.5 and 18.5.6).
  • Restraint of branch lines to NFPA 13-2025 Section 18.6, with spacing by seismic coefficient from Table 18.6.4.
  • FM Global DS 2-8 (2.2.1.1) requires four-way bracing on risers regardless of size and lateral sway bracing on branch lines of 65 mm (2½ in.) and larger.

In Turkey the basic requirements are set by BYKHY Article 96(6). Because Article 5(2) gives precedence to Turkish standards, then European standards, and only then to other internationally recognised standards, EN 12845-3 should be consulted first for seismic bracing; NFPA 13 or FM Global DS 2-8 fill only what it does not cover.

A field error: unhung pipe inside a plasterboard ceiling

In a shopping centre being converted into a hotel, a DN50 sprinkler branch running inside the plasterboard suspended ceiling had been fixed to the ceiling profiles with plastic clips. There was no structural hanger at all. When the suspended ceiling collapsed in an earthquake, the pipe went down with it and water ran for 40 minutes until the main valve was shut. Two causes:

  1. The pipe was invisible inside the ceiling, so site supervision could not check it.
  2. A plasterboard profile is not a "structure" in EN 12845 terms and cannot carry sprinkler pipe. A ceiling profile does not have 200 kg of load capacity.

The correct arrangement: an M10 anchor into the concrete above, threaded rod and clamp; the ceiling profile carries only the sprinkler escutcheon.

Clause 17.2.1 requires supports to be fixed directly to the building or, where necessary, to machines, storage racks or other structures, and the part of the structure to which they are secured must be capable of supporting the pipework (see Table 40) — at least 200 kg for pipe up to 50 mm. A suspended ceiling profile that cannot carry that load is not an acceptable fixing point. Pipework in concealed spaces is covered in Clause 17.3.

Comparison with NFPA 13 hanger spacing

NFPA 13-2025 Table 17.4.2.1(b) gives hanger spacing by pipe diameter (steel pipe except threaded lightwall). In summary:

Pipe diameterNFPA 13 max.EN 12845 max.
1" / DN253.7 m (12 ft)4.0 m
1¼" / DN323.7 m4.0 m
1½"–2" / DN40–DN504.6 m (15 ft)4.0 m
2½"–8" / DN65–DN2004.6 m4.0 m (6.0 m with the exception)

NFPA is tighter at small diameters (3.7 m) and looser at large ones (4.6 m). EN 12845 gives a single spacing of 4 m and opens an exception for larger pipe. NFPA additionally covers seismic bracing in detail in Chapter 18; on the EN side, A2:2026 leaves this subject to EN 12845-3.

Turkish context

BYKHY Article 96(5) requires sprinkler system design to BS EN 12845, which ties the hanger detail to the standard. Through this link, compliance of the hanger detail with EN 12845 Clause 17.2 and Table 40 can be questioned at permit stage. On the seismic side, Article 96(6) requires, in first- and second-degree seismic zones, four-way bracing of risers, flexible couplings where pipes of 65 mm and larger connect from the floors to the mains, two-way lateral and longitudinal restraint hangers where pipes are fixed to the ceiling, and details at expansion joints that accommodate movement in all three directions. EN 12845 itself does not size these supports; A2:2026 recommends EN 12845-3 for this. Under Article 5(2) the European standard (EN 12845-3) comes first, and internationally recognised standards such as NFPA 13 or FM Global DS 2-8 may be used only for matters it does not cover.

Checklist — before going to site

  • Any steel pipe spacing above 4 m? If so, is the exception documented?
  • Any copper pipe spacing above 2 m? Is the insulating liner inside the clamp?
  • Is there a support within 1 m of every mechanical joint (grooved coupling)?
  • Terminal sprinkler to last support: ≤ 0.9 m on DN25, ≤ 1.2 m above?
  • Additional support on vertical pipe over 2 m?
  • Is any pipe over 50 mm (DN65 and above) hung from corrugated steel sheet or aerated concrete, or any pipe from plasterboard ceiling profiles? It must not be.
  • Anchors: non-combustible (steel expansion type), correct M8/M10/M12/M16 size, 30/40/50 mm embedment in concrete?
  • Any plastic anchors or nylon ties? There must be none.
  • In a seismic zone, is there a sway bracing plan for risers and mains?

Frequently asked questions

What is the maximum hanger spacing on steel pipe?

4 m. Above 50 mm it can be increased by 50 % to 6 m, provided two independent supports are used or a single support carrying 50 % more than the tabulated load.

Why is copper spaced more closely?

Copper's modulus of elasticity is lower than steel's, so it deflects faster. Clause 17.2.2 sets a maximum of 2 m, rising to 3 m above 50 mm with the 50 % exception. An insulating liner is also required inside the clamp to prevent galvanic corrosion.

How far can the last support be from the end sprinkler?

0.9 m on DN25 pipe and 1.2 m above DN25. An upright sprinkler must be at least 0.15 m from the support.

Does EN 12845 require seismic bracing?

BS EN 12845+A2:2026 Clause 13.1 recommends applying EN 12845-3 in areas at risk of earthquakes. BYKHY Article 96(6), in addition, requires four-way bracing of risers, flexible couplings where pipes of 65 mm and larger connect to the mains, and two-way lateral and longitudinal restraint hangers in first- and second-degree seismic zones; EN 12845-3 comes first for sizing these supports, with NFPA 13 or FM Global DS 2-8 used for matters it does not cover.

When does a vertical pipe need additional support?

Above 2 m in general, and above 1 m for a drop feeding a single sprinkler. Low-level pipe exposed to mechanical impact is separately supported, though horizontal connections under 0.45 m and vertical drops under 0.6 m are exempt.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

EN 12845:2015+A2:2026 Fixed firefighting systems — Automatic sprinkler systems. EN 12845-2:2024 (CMSA & ESFR sprinkler systems). NFPA 13 Standard for the Installation of Sprinkler Systems. Turkish Regulation on Fire Protection of Buildings (BYKHY). FM Global Property Loss Prevention Data Sheet 2-0.