A pre-action system is a sprinkler system whose pipework is normally filled with air, where water enters the pipe only after an independent detection system operates. Its purpose is to make accidental discharge close to impossible.

Why it exists

In a wet system the pipe holds pressurised water at all times; if a head is broken, water flows. In spaces such as data centres, archives, museums and cleanrooms an accidental discharge costs as much as the fire itself. A pre-action system reduces that risk without giving up sprinklers.

Three types

TypeFor water to enter the pipeFor water to leave a sprinkler
Non-interlockDetector or sprinkler operationSprinkler operation
Single interlockDetector operationSprinkler operation
Double interlockDetector operation and loss of pipe pressureSprinkler operation

The last step is the same in all three: no water goes anywhere until a sprinkler opens. The difference is when the valve opens.

Where double interlock is needed

Where pipe damage is the biggest risk: cold stores, areas with heavy forklift traffic, production lines with a high risk of mechanical impact. In a double interlock system a detector alone does not open the valve; there must also be a pressure drop in the pipe. An accidental detector alarm discharges no water.

The price is delay: water enters the pipe later and leaves the sprinkler later. To compensate, NFPA 13 requires the area of sprinkler operation for dry pipe and double interlock preaction systems to be increased by 30% without revising the density (NFPA 13-2025 19.2.3.2.6; single interlock and non-interlock types are not increased). The size of a double interlock system is also limited: up to 500 gal (1900 L) no water delivery requirement applies; larger systems must meet one of the options such as delivering water to the test connection in no more than 60 seconds (8.3.2.3.1). EN 12845 Table 3, by contrast, places pre-action in the same column as wet systems; the area increase applies only to dry and alternate systems.

The cold store exception. A wet system cannot be used because of the freezing risk. A dry system is one option; a double interlock pre-action system prevents freezing and accidental discharge at the same time. That combination is the typical cold store solution.

What to watch in design

  1. The detection must be more sensitive than the sprinklers. If the detector operates after the sprinkler, the pre-action logic collapses and — outside the non-interlock type — the system is late.
  2. Pipe volume is limited. Water transit time is critical; large installations need an accelerator or sectioning.
  3. The air must be dried. Moist compressed air corrodes the pipe; a dryer or nitrogen is preferred.
  4. The testing regime is heavy. Detection, valve and air pressure all need regular testing to the NFPA 25 intervals.
  5. Standby power. Detection and valve control depend on electricity, and the system's behaviour on loss of supply must be defined.

A common mistake

Feeding gaseous suppression and the pre-action system from the same detection line in a data centre. Unless the logic for agent release is separated from that for opening the water valve, the pipe fills the moment the gas discharges. The correct arrangement is a separate detection zone for the gas and a second level for the pre-action system.

The EN 12845 equivalent

EN 12845 clause 11.4 defines two types. Type A: the control valve set is activated by an automatic fire detection system only, not by the operation of the sprinklers (similar to NFPA single interlock); if the detection system fails the installation operates as an ordinary dry pipe system, and it is recommended only where accidental discharge could cause considerable damage. Type B: the valve is activated by the detection system or by the operation of the sprinklers (similar to NFPA non-interlock). EN 12845 does not define a double interlock type.

Frequently Asked Questions

What is the difference between single and double interlock?

In single interlock, detector operation alone opens the valve. In double interlock a loss of pipe pressure is also required, so an accidental detector alarm does not fill the pipe.

Where are pre-action systems used?

Where accidental discharge costs as much as the fire: data centres, archives, museums, cleanrooms; the double interlock type is also used in cold stores and production areas with a high impact risk.

Why is the design area increased for a pre-action system?

Because water enters the pipe late, discharge from the sprinkler is delayed. NFPA 13-2025 19.2.3.2.6 requires a 30% increase in the design area for dry pipe and double interlock preaction systems; single interlock and non-interlock types are not increased. EN 12845 requires no area increase for pre-action systems.

Why must the air in pre-action pipework be dried?

Moist compressed air corrodes the pipe from inside. An air dryer or nitrogen protects pipe life and system reliability.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

NFPA 13 (2025) · NFPA 15 · NFPA 855 · EN 12845:2015+A2:2026 · FM Global DS 5-33 · FM Global DS 4-1N. Definitions are for information only.