There are four installation types, and the choice starts with one question: does this space freeze? If not, wet. If it does, you have to decide between dry, alternate and pre-action — and each affects the design area, the water delay and the cost differently.

Four types in one table

FeatureWetDryAlternatePre-action
Medium in the pipeWaterCompressed air / nitrogenWater in summer, air in winterAir plus independent detection
Where usedNo freezing riskCold stores, car parks, roof voidsSeasonal freezingData centres, archives, museums
Water delayNone (pipe full of water)EN 12845: up to 90 s LH, 60 s OH/HHAs dry, in dry modeDetection plus pipe fill time
Design areaBaseEN 12845: plus 25 percent; NFPA 13: plus 30 percentPlus 25 percent for dry mode (EN)EN 12845: same as wet; NFPA 13 double interlock: plus 30 percent
Gridded or looped layoutPermittedNot permittedNot permittedEN 12845: not permitted; NFPA 13: limited
Accidental discharge riskPresentPresentPresentLowest (EN Type A, NFPA single/double interlock)
Corrosion riskModerate (MIC)High (humid air)HighestHigh
Maintenance burdenLowModerate (compressor, accelerator)High (seasonal changeover)High (detection loop)
High hazard storage (HHS)SuitableStrongly discouragedStrongly discouragedSame column as wet in EN 12845 tables

The area increases come from EN 12845 Table 3 (OH1 72 → 90 m², OH2 144 → 180 m², OH3 216 → 270 m², HHP 260 → 325 m²) and the notes to Tables 4 and 5 for HHS, and from NFPA 13-2025 19.2.3.2.6 (dry and double interlock pre-action: plus 30 percent). EN 12845 does not allow dry or alternate systems for LH or OH4 (OH1 and HHP1 are used instead). For grid and loop systems EN 12845 11.1.1 allows wet installations only; NFPA 13 prohibits gridded dry systems (8.2.1) and gridded double interlock pre-action (8.3.2.7.1), and prohibits gridding single and non-interlock pre-action only in high-piled storage (8.3.2.7.2).

Water delivery time: the heart of a dry system

EN 12845 limits the time between a single sprinkler opening and water discharging: 90 seconds for LH and 60 seconds for OH and HH (11.2.2, Table 18). The test is carried out at the remote test valve specified in 15.5.2. A note in the standard says that with an accelerator, a pipe volume of no more than 4 m³ for LH or OH and 3 m³ for HH is expected to meet the limit. If the limit is exceeded there are three routes: fit an accelerator, split the pipe volume into subsidiary installations, or revisit the pipe sizes.

Compressor capacity is selected from the internal pipe volume, not the sprinkler count: under NFPA 13-2025 8.2.7.3 the air supply must be able to restore normal system pressure within 30 minutes (60 minutes in refrigerated spaces held below −15 °C, 8.2.7.4).

Alternate systems: two decisions a year

An alternate installation runs wet in summer and dry in winter. The changeover is driven by temperature, not the calendar; the practical reference is when the coldest night temperature crosses 4 °C. In a typical Anatolian climate that means switching to dry in late October and back to wet in late March. Returning to wet early removes the water delay and cuts compressor running hours; the hydraulic design, however, must always be made for the dry mode (the 25 percent larger area).

The most common alternate system error: the water left above the alarm valve. If the valve room is not held above 4 °C, that small volume freezes even in dry mode. The pipework side is full of compressed air and does not freeze; the risk always sits in the valve room.

Pre-action: EN 12845 Type A and Type B, NFPA 13 interlock types

For water-sensitive spaces such as data centres and archives, the type EN 12845 recommends is Type A; Type B gives no more protection against accidental discharge than a dry system. With double interlock, an unnoticed detection fault means no water even when a sprinkler operates, so the detection system needs regular inspection and its fault signal must go to a constantly monitored point.

Decision flow

  1. Is the ambient continuously between 4 and 70 °C? → Wet. Discussion over.
  2. Does only a small section freeze? → Keep the main installation wet and make that section a subsidiary dry extension (EN 12845 11.5.2: 100 sprinklers maximum per extension; 250 in total where more than two extensions share one control valve set).
  3. Does the building freeze seasonally? → Alternate.
  4. Is it permanently cold (a cold store)? → Dry or pre-action, with the valve in a heated space.
  5. Are the contents water sensitive (servers, archives, museums)? → Pre-action (Type A under EN 12845; single or double interlock under NFPA 13).
  6. Is it high hazard storage? → Avoid dry and alternate systems (EN 12845 11.2.2); look for another solution such as heating the space.

Frequently Asked Questions

Why is the design area enlarged on a dry system?

During the delay while the air vents, the fire grows and more sprinklers open. EN 12845 increases the area of operation by 25 percent on dry and alternate systems (Table 3; notes to Tables 4 and 5 for HHS), and NFPA 13 increases it by 30 percent on dry and double interlock pre-action systems (19.2.3.2.6).

What is the maximum water delivery time?

Under EN 12845 Table 18, 90 seconds for LH and 60 seconds for OH and HH. The test is carried out at the remote test valve.

What is the difference between Type A and Type B pre-action?

Under EN 12845, Type A is opened by the fire detection system only; sprinkler operation does not open the valve. Type B is opened either by the detection system or by sprinkler operation. Type A is the one recommended for water-sensitive areas. The double interlock system, which needs both detection and sprinkler operation, is defined in NFPA 13.

Is a dry system used in high hazard storage?

EN 12845 11.2.2 strongly recommends against it: the delay in water reaching the first operating sprinklers could seriously impair the effectiveness of the system. If it is nonetheless necessary, the area of operation is increased by 25 percent.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

EN 12845:2015+A2:2026 Clause 11 (installation types, Tables 17 and 18) and Tables 3–5. NFPA 13 (2025) Chapter 8 and 19.2.3.2.6. EN 12259-2 and EN 12259-3 (alarm valve assemblies). Values are for information only.