With 40 m ceilings, huge atria and more than 10,000 passengers an hour, an airport terminal is one of the most demanding smoke control scenarios. On a project of this scale we have to apply NFPA 415 (terminal buildings) and NFPA 92 together: one addresses fuel and fire risk, the other smoke control in large volumes. Well-designed zoning keeps smoke in the zone where it starts, so it does not travel to a gate 300 m away.
Smoke Zoning Logic
- Zone size: Maximum 2,000 m² or 60 m in length/width; beyond that the exhaust rate becomes unmanageable.
- Smoke curtain: Automatic curtain dropping 2–3 m from the ceiling to separate the zone physically in a fire.
- Each zone: Independent exhaust and makeup air; one should not serve as the other’s backup.
- Check-in, gates, baggage drop: Planned as separate zones from the outset.
Smoke Exhaust Calculation for a Very High Ceiling
A typical scenario: 40 m ceiling, 2,000 m² zone, 5 MW design fire, smoke layer interface 30 m above the fuel:
- NFPA 92 axisymmetric plume: m = 0.071 × 50001/3 × 305/3
- m = 0.071 × 17.1 × 289.6 ≈ 352 kg/s
- Volumetric flow: ~1,000,000 m³/h (for a single zone)
- Fan group: 10 × 100,000 m³/h (this only meets the demand; standby units must be added)
- A common solution: normal ventilation uses the same fans (dual-use design)
NFPA 415 and Jet Fuel Risk
- Baggage area: Gas cartridges or small canisters in luggage are not unlikely and are considered in the fire load.
- Gate area: Kept at least 15 m inside from the aircraft refueling point.
- Jet A/A-1: Flash point >38 °C; Class II combustible liquid.
- Apron: A separate drainage line and oil-water separator for fuel spills are mandatory.
- Gate monitor: Fixed AFFF monitor rated at 10,000 L/min.
Sprinklers in the Check-in Area
- High ceiling: ESFR is not a solution under a 40 m ceiling (NFPA 13 Table 23.3.1 limits ESFR to a 13.7 m ceiling); at this height ceiling sprinklers alone are not enough, so a performance-based analysis is needed.
- Service/control areas: OH2; standard K8.0 (K115) sprinklers are usually sufficient.
- Under baggage belts: Tunnel sprinklers, OH2, at 2 m spacing.
- Security X-ray screening: Water mist or a clean agent such as FM-200 is preferred to protect the electronics.
Istanbul New Airport Example
- 1.4 million m², the world’s largest terminal building under a single roof
- 250+ smoke zones
- CFD: FDS and Pathfinder, a mesh of more than 1 billion cells
- Large atrium: 40 m facade and an 18 m atrium void across 7 levels

Terminal smoke with MEP Calc
MEP Calc sizes airport terminal smoke zones, 40 m ceiling plume flow and mega AHU banks per NFPA 415/92.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 415, NFPA 92, NFPA 409, ICAO Annex 14, ACI Airport Design Guide. NFPA 415 Airport Terminal standard.