Turkey has 30,000 km of dual carriageway fed by 200+ asphalt plants. The rotary dryer brings aggregate to 150 °C and bitumen sits at 140-180 °C. Burners run LPG, diesel or natural gas. NFPA 87 covers asphalt fluid heaters, silo venting, rotary-dryer deflagration and fuel tank setback.
Plant Main Units
- Rotary dryer: 3-5 m dia x 10-15 m long
- Burner: 10-40 MW
- Hot aggregate silo: 150-180 °C
- Bitumen tank: 50-200 m3, 160 °C
- Baghouse: bag dust filter
Bitumen Hazard
- Flash point: 218-280 °C (Class IIIB)
- Storage temp: 160 °C
- Ignition: at about 260 °C
- Tank foam: 0.16 gpm/ft2 (6.5 L/min/m2) per NFPA 11; NFPA 11 Annex A warns that foam on hot oil or burning asphalt tanks can cause violent frothing and slop-over, so apply with care
- Heater coil: Hot oil safer
Rotary Dryer Risk
- CO alarm: 50 ppm early warning, 100 ppm burner lockout
- Deflagration vent: NFPA 68
- Flame scanner: UV/IR
- Purge: 5 volume changes before ignition
- BMS: NFPA 85 burner management
Baghouse Fire
- Filter bag: PTFE 240 °C max
- Aramid (Nomex): 200 °C
- Sprinkler: dry pipe inside the baghouse
- Spark detector: IR, at the inlet
- Inlet gate: Quick isolation
Turkey Operators and Related Standards
- KGM: 30,000 km asphalt network
- Typical plants: 180-240 t/h
- A single metropolitan area: 6 plants
- Reference plant fire: Bitumen tank
- Fluid heaters: NFPA 87
- Burner management: NFPA 85
- Deflagration venting: NFPA 68
- Mix test methods: TS EN 12697

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, FM-200 clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 87, NFPA 85, NFPA 68, TS EN 12697, KGM (General Directorate of Highways). NFPA 87 Fluid Heaters.