Zorlu Center 103,000 m2, Istinye Park 85,000 m2 and Forum Istanbul 175,000 m2 host Turkey's biggest mall atriums. A 4-storey 25 m atrium sees 80,000 daily visitors. NFPA 92 requires atrium smoke control with 1.8 m clear height, CFD FDS 6 modelling, 400 C 2 h exhaust fans and balanced makeup air.
Atrium Geometry
- Height: 20-40 m typical
- Open balcony: 4-6 storeys
- Shop opening: Open to atrium
- Glass roof: Skylight smoke vent
- Foot traffic: 80,000/day peak
NFPA 92 Calc
- Clear height: 1.8 m above egress
- Smoke layer: Z = layering depth
- Exhaust rate: m = 0.071 Q^1/3 z^5/3
- Makeup air: 60 percent of exhaust
- Egress time: 6 min before layering breaks
CFD FDS
- Fire Dynamics Simulator: NIST
- Mesh: 10-20 cm cell
- Design HRR: 5 MW retail
- Steady state: 20 min run
- ASET vs RSET: Safe egress
Exhaust Fan
- Capacity: 50-200 m3/s
- 400 C 2 h: Smoke-rated
- Motor out of flow: Heat isolation
- Redundancy: N+1
- Control: FSCS panel
Turkey Malls
- Zorlu Center: 103,000 m2
- Istinye Park: 85,000 m2
- Forum Istanbul: 175,000 m2
- Mall of Istanbul: 155,000 m2
- 2022 BAU Mall: Smoke control project

MEP Calc — 86+ Engineering Calculators
MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, FM-200 clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 92, NFPA 101, IBC 909, NIST FDS 6, Zorlu Center projects. NFPA 92 Smoke Control Systems.