Plastic raw material — polyethylene, polypropylene and polystyrene pellets — is one of the toughest fire loads. Its heat release rate is very high, so conventional density/area sprinklers fall short once it ignites. Polymer producers' warehouses therefore use ESFR K25.2 (K360) sprinklers. Three inputs drive the design: packaging (exposed or cartoned), ceiling/storage height and the matching minimum operating pressure; the design area is always 12 sprinklers.

Plastic Group Classification

ESFR K25.2 (K360) System

Pile and Rack Design

Alternative Protection

Required Infrastructure

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, FM-200 clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.