Under NFPA 13-2025 Table 19.2.3.1.1 the design density for Ordinary Hazard Group 2 (OH2) is 8.1 mm/min over 140 m² (0.20 gpm/ft² over 1,500 ft²); next to unsprinklered combustible concealed spaces 6.9 mm/min over 280 m² (0.17 gpm/ft² over 3,000 ft²) applies. Hose allowance is 950 L/min (250 gpm) and water supply duration is 60 or 90 minutes (Table 19.2.3.1.2).
Definition
Ordinary Hazard Group 2 covers spaces where the quantity and combustibility of contents are moderate to high. Stockpiles of moderate heat release material stay within 12 ft (about 3.7 m) and those of high heat release material within 8 ft (about 2.4 m). Shops, workshops and a good share of light industry sit in this group.
Design parameters
| Parameter | SI | US units |
|---|---|---|
| Density (standard design) | 8.1 mm/min | 0.20 gpm/ft² |
| Design area (standard) | 140 m² | 1,500 ft² |
| Density (concealed space rule, 19.2.3.1.5) | 6.9 mm/min | 0.17 gpm/ft² |
| Design area (concealed space rule) | 280 m² | 3,000 ft² |
| Theoretical sprinkler flow (standard / concealed space) | 1,134 / 1,932 L/min | 300 / 510 gpm |
| Hose allowance (inside + outside) | 950 L/min | 250 gpm |
| Inside hose (part of the total) | 0, 190 or 380 L/min | 0, 50 or 100 gpm |
| Water supply duration | 60 or 90 min | 60 or 90 min |
| Maximum area per sprinkler (standard spray, Table 10.2.4.2.1(b)) | 12 m² | 130 ft² |
| Maximum distance between sprinklers | 4.6 m | 15 ft |
Theoretical flow is simply density × area. Actual system demand is higher because of hydraulic imbalance and the minimum sprinkler pressure (7 psi (0.5 bar), 28.2.4.11.1). Coverage and spacing values are for standard spray sprinklers; for ordinary hazard this limit applies regardless of construction type; smaller values apply in storage areas.
Typical occupancies
- Retail (mercantile) floors
- Automobile parking garages
- Agricultural facilities, barns and stables
- Machine shops and metalworking
- Repair garages
- Printing and publishing
- Textile, leather goods and tobacco manufacturing
- Paper and pulp mills
- Chemical plants (ordinary)
- Cereal and feed mills
- Wood machining and assembly
- Library stack rooms; stages
- Post offices; exterior loading docks
How the design area is set
NFPA 13-2025 no longer has the density/area curve of earlier editions. Table 19.2.3.1.1 gives a single design point for each class: 8.1 mm/min over 140 m² for OH2. The second column, 6.9 mm/min over 280 m², applies only to the systems or portions of systems adjacent to unsprinklered combustible concealed spaces (19.2.3.1.5); the concealed spaces listed in 19.2.3.1.5.2 are exempt. Where an area of operation smaller than 140 m² is used, the density for 140 m² still applies (19.2.3.1.4). The density must be delivered over the whole hydraulically most remote area.
For dry pipe and double interlock pre-action systems the area of operation is increased by 30% without revising the density (19.2.3.2.6). Ceilings sloping more than 2 in 12 usually need a 30% increase as well (19.2.3.2.4). Where several adjustments apply they are compounded on the area first taken from Table 19.2.3.1.1, and the concealed space rule is applied last (19.2.3.2.8).
With listed quick-response sprinklers throughout a wet system, or a portion with the same hydraulic design basis, and a ceiling no higher than 20 ft (6.1 m), the area of operation may be reduced without revising the density: by 40% for ceilings of 10 ft (3 m) or less and by 25% at 20 ft (6.1 m), linear in between (Figure 19.2.3.2.3.1). Unprotected ceiling pockets must not exceed 32 ft² (3.0 m²), there must be no unprotected areas above cloud ceilings, and the design area must always contain at least five sprinklers (19.2.3.2.3). Where OH2 ceilings exceed 30 ft (9.1 m), sprinklers below K-11.2 (K160) may not be used; between 30 and 40 ft (9.1–12.2 m) a minimum density of 0.37 gpm/ft² (15.1 mm/min) applies, and above 40 ft (12.2 m) 0.45 gpm/ft² (18.3 mm/min) with a 30% larger area, unless an extended-coverage sprinkler of nominal K25.2 (K360) or larger is used, in which case the area is not increased (19.2.3.2.5). Standard-response standard-coverage sprinklers are prohibited above 9.1 m under 10.2.5 but above 12.2 m under 19.2.3.2.5.1(C); given this conflict within the standard, use the 9.1 m limit.
In shops, shelf and stack height is the critical threshold: once stacks exceed the heights in the OH2 definition, or fall within the scope of the storage chapters, the hazard class method no longer applies and storage criteria take over.
The inside hose allowance (0, 50 or 100 gpm) is part of the total above. The lower duration value is accepted where the waterflow alarm and supervisory devices are electrically supervised and monitored at an approved, constantly attended location (19.2.3.1.3).
Comparison with EN 12845
On the EN 12845 side the nearest match is usually OH3 (5.0 mm/min, 216 m², 60 minutes), and for some process areas OH4 (360 m²). The NFPA OH2 density in Table 19.2.3.1.1 is 8.1 mm/min, well above EN's fixed 5.0 mm/min. The two classifications cannot be converted into each other; use the tables of whichever standard the project is designed to.
The class comes from how the space is actually used. A project title or the occupancy on a permit is not enough; contents, stack height and flammable liquids are checked on site and the class is recorded with a written justification. For a quick first pass, use the NFPA 13 hazard classification tool.
Checklist
- Is the activity and type of contents recorded in writing?
- Are stack heights within the class definition; if not, have storage criteria been checked?
- Is the system type (wet/dry/pre-action) reflected in the area adjustment?
- Are hose allowance and duration included in the tank volume?
- Are areas of different classes in the same building calculated separately?
Frequently Asked Questions
What is the minimum water demand for NFPA 13 OH2?
In theory, at the standard design point 1,134 L/min (300 gpm) of sprinkler flow plus 950 L/min (250 gpm) of hose allowance, multiplied by 60 or 90 minutes. The real figure comes from the hydraulic calculation and is usually higher; the fire water tank sizing calculator helps with the volume.
What hazard class is a retail shop under NFPA 13?
A typical sales floor is OH2. Where high shelving is used on the sales floor, particularly with plastic goods, storage criteria may apply instead.
What is the hose allowance for OH2?
250 gpm (950 L/min) combined inside and outside hose. Water supply duration is 60 or 90 minutes (Table 19.2.3.1.2).

SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.
Download SprinkCalc on the App Store
MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App StoreNFPA 13, Standard for the Installation of Sprinkler Systems (2025 edition): 4.3, Table 10.2.4.2.1, 19.2.3, A.4.3 · BS EN 12845+A2:2026 (EN 12845:2015+A2:2026). Values are for information; the binding text is the edition in force and the decision of the authority having jurisdiction.