Ports host tank farms storing gasoline, diesel and jet fuel. A single tank can reach 50,000-100,000 m3; the 2005 Buncefield blast caused damage across an area about 1 km in diameter. NFPA 30 covers flammable and combustible liquids and dike dimensions, while API 650 covers tank design.

NFPA 30 Classification

  • Class IA: Flash <23 °C, BP <38 °C
  • Class IB: Flash <23 °C, BP >=38 °C (gasoline)
  • Class IC: Flash 23-38 °C
  • Class II: Flash 38-60 °C (diesel)
  • Class IIIA: Flash 60-93 °C (fuel oil)

Tank Setback Distances

  • Class I tank: shell-to-shell spacing is a fraction of the sum of adjacent tank diameters (NFPA 30 Table 22.4.2.1); at least 0.9 m for tanks up to 45 m diameter
  • Dike: at least the largest amount of liquid that can spill from the largest tank (NFPA 30 22.11.2.2)
  • Dike wall: if the average interior height exceeds 1.8 m, access and egress provisions are required (NFPA 30 22.11.2.5)
  • Tank-dike: tank shell to the toe of the interior dike wall at least 1.5 m (NFPA 30 22.11.2.5)
  • Property line: per NFPA 30 Table 22.4.1.1(a) by tank type, diameter and protection; dike outer base at least 3 m (22.11.2.3)

Foam and Cooling Rates (NFPA 11-2024, hydrocarbons)

  • Floating-roof rim seal foam: 12.2 L/min/m2 (top-of-seal with foam dam, Section 5.3)
  • Full surface: 4.1 L/min/m2 with fixed foam discharge outlets (Table 5.2.5.2.2); 6.5 L/min/m2 with monitors and handlines (Table 5.2.4.2.2)
  • Dike foam: 4.1 L/min/m2 with low-level fixed outlets, 6.5 L/min/m2 with foam monitors (Table 5.7.3.2)

Lightning and Overfill

  • API 2003: Lightning grounding
  • Bypass ring: Upper rim bonded
  • Overfill protection: procedures or equipment to prevent overfilling; facilities receiving Class I liquid from marine vessels or mainline pipelines need written procedures using one of the listed methods (NFPA 30 21.7.1)
  • Tank gauging: Radar + servo
  • Cathodic protection: Bottom CP

Major Incidents

  • Buncefield UK 2005: Overfill - 43 injured
  • A terminal: Lightning
  • A large refinery: about 12 Mt/y capacity
  • A port: Tank fire
  • CSB investigation: Large incident analysis

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

NFPA 30, NFPA 11, API 650, API 2003, FM DS 7-88. NFPA 30 Flammable and Combustible Liquids.