A shipyard is a heavy industrial facility with a high fire risk during the construction, repair and dismantling of vessels. The same picture appears on every project: welding, grinding, painting and fuel transfer all run in the same shift. NFPA 312 (Fire Protection of Vessels During Construction, Conversion, Repair, and Lay-Up) defines the rules for dry dock fire systems, hot work permits and gas-free certificates in this chaotic environment. On site, not even a welding machine should be switched on until these three items are in place.
Dry Dock Fire System
- Seawater main: a hydrant every 60 m, supplied at 4,000 L/min
- Foam monitor: AFFF or F3 fixed monitor, 10,000 L/min
- Mobile pump: diesel-driven for access under the hull, usually trailer-mounted
- Dock-side water curtain: a water curtain line above the timber staging
Hot Work Permit
- NFPA 51B: the hot work standard; not a single arc is struck without a permit
- Fire watch: a second person separate from the worker, continuing the watch for at least 30 minutes after the work ends
- Spark blanket: stops sparks falling below or onto the side deck
- Portable extinguisher: 2A:40B:C within 1.5 m of the work point
- Flammable liquids: at least 10.7 m separation, or a physical barrier in between
Gas-Free Certificate
Before any tanker repair begins, a marine chemist steps in:
- An AIHA-certified marine chemist tests the tank in person; there is no remote approval
- Oxygen: 19.5-23.5%
- Lower explosive limit (LEL): below 10%
- H₂S: below 10 ppm
- CO: below 50 ppm
- Benzene (crude oil tankers): below 0.5 ppm
The certificate is valid for 24 hours and is re-verified at the start of every shift. "It was clean yesterday" is not accepted on site.
Onboard Fixed CO₂
- Engine room: CO₂ total flooding under the SOLAS FSS Code
- Design concentration: 40% (diesel), 50% (gas-fuelled machinery)
- Manual release: release from two separate controls is required, with an interlock against discharge on a false alarm
- Special case: LNG carriers favour IG-541 or water mist instead of CO₂

MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations (sprinkler, fire pump, FM-200 clean agent) plus heating, cooling, HVAC, plumbing, steam and natural gas. Download it on the App Store.
Download MEP Calc on the App Store
SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.
Download SprinkCalc on the App StoreNFPA 312, NFPA 51B, SOLAS FSS Code, OSHA 29 CFR 1915, AIHA Marine Chemist. NFPA 312 Vessels Construction standard.