The real work starts on the day a sprinkler system is commissioned: maintenance. NFPA 25 (Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems) defines in detail which check is carried out at which frequency. The operator's question is always the same: "What do I check this month?" This post summarizes the ITM tasks from weekly to five-yearly, in order and in field language.

Weekly Checks

  • Control valve lock indicator: Does the tamper switch signal reach the panel?

Monthly Checks

  • Dry pipe / preaction pressure gauge (quarterly where air pressure supervision is connected to a constantly attended location; NFPA 25-2026 13.2.4.1.3): Is the air pressure within the manufacturer's range, or has it drifted with day-night temperature swings?
  • Wet pipe system pressure gauge: Undamaged and operable (monthly); the water pressure is checked against the normal range quarterly (13.2.4.1.1 and 13.2.4.1.2). If it has dropped, find out why.
  • Control valves open and locked: Valves are inspected weekly; monthly is enough for locked or supervised valves and quarterly for electrically supervised ones (13.3.2.1); no valve may be left closed.
  • Fire pump no-flow (churn) test: diesel pumps run at least 30 min, electric pumps at least 10 min; the frequency is weekly or monthly depending on pump type (weekly for diesel).

Quarterly Checks

  • Alarm devices (flow switch, pressure switch): quarterly inspection for physical damage; signal test by flowing water through the test connection semiannually, quarterly for mechanical water motor gongs (NFPA 25-2026 13.2.3.1–13.2.3.2).
  • FDC (Fire Department Connection): Caps in place, threads clean, check valve leak-free.

Annual Checks

  • Main drain test: Open the main drain and measure the system pressure; if full flow pressure shows a 10 percent reduction compared with the acceptance test or previous tests (NFPA 25-2026 13.2.2.3), investigate a blockage or a partly closed valve in the main.
  • Dry valve partial trip test: the valve opens without the system filling completely with water; the mechanism is observed.
  • Antifreeze concentration test: measured with a refractometer; never accept the mixture on paper.
  • Fire pump annual flow test: the performance curve is plotted at 100% and 150% of capacity and compared with the manufacturer's curve.
  • Visual sprinkler inspection: corrosion, paint, loading and obstructions.
  • Hanger and seismic bracing check: looseness, rust or braces that have shifted angle.
  • Hydrant visual inspection and lubrication (annually and after each operation; NFPA 25-2026 7.2.2.4, 7.2.2.5, 7.4.2.1): including body paint, cap gaskets and stem binding.

Three-Year Checks

  • Dry valve full trip test: the system fills completely with water, simulating a real fire.

Five-Year Checks

  • Sprinkler laboratory test: at 50 years sprinklers are either replaced or representative samples are tested by an approved laboratory and retested every 10 years; at 75 years the retest interval drops to 5 years. Fast-response sprinklers (except ESFR/CMSA) are first tested at 25 years, fast-response ESFR/CMSA and dry sprinklers at 20 years; sprinklers in harsh environments and extra-high temperature solder-type sprinklers every 5 years (NFPA 25-2026 5.3.1.1).
  • Internal pipe inspection: MIC (Microbiologically Influenced Corrosion) check.
  • Gauge calibration or replacement: after 5 years the gauge is either verified or replaced.
  • Tank internal inspection: coating condition and signs of oxidation; the interval is 3 years for steel tanks without corrosion protection (9.2.5.1).

Checks Not to Skip

  1. Weekly round on site: the checklist must not become just a signature.
  2. Fire pump runs: without regular 30-minute runs the diesel batteries can weaken, and in a real fire the pump may not start.
  3. Internal pipe inspection: do not skip the five-year check; internal corrosion (MIC) cannot be seen from outside.
  4. Log book: without records neither the insurer nor the authority having jurisdiction can spot anomalies, and a claim may run into trouble after a fire.

Conclusion

ITM is the heart of the sprinkler system. If you want your system to still work in 20 years, every frequency from weekly to five-yearly has to be carried out with discipline. NFPA 25-2026 Table 5.1.1.2 summarizes the sprinkler-system items; valve, gauge, pump and other frequencies sit in the related chapters (Chapters 8 and 13), and the plan must cover those as well.

ITM schedule in MEP Calc

NFPA 25 frequency-based ITM calendar, reminders, and field log book.

View on App Store

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report. One of the few tools that unifies all three major fire protection standards.

Download SprinkCalc on the App Store
Sources & Further Reading

Core reference: NFPA 25-2026 Table 5.1.1.2 - ITM Frequencies. Original NFPA post: NFPA Today - ITM Frequencies.