CMSA (Control Mode Specific Application) sprinklers are large-drop sprinklers tested and listed for specific storage arrangements, and they replace the density/area method for many warehouse designs. In NFPA 13-2025, CMSA installation is covered in Chapter 13 and storage design criteria in Chapter 22, and together they answer one question: for this commodity, this storage arrangement and this ceiling height, how many sprinklers must open, and at what pressure?

What this part of the standard covers

With standard spray sprinklers you pick a density (mm/min) and an area of operation (m²). CMSA works differently. Full-scale fire tests establish a number of sprinklers and a minimum operating pressure that control a fire in a given arrangement, and the designer reads those values directly from the tables. You are not computing a density; you are selecting the correct table row and then making sure every condition of that row is actually delivered on site.

The requirements fall into four groups:

  • Applicability: which commodity class, storage type (palletised, solid-piled, rack), storage height and ceiling height each CMSA option covers.
  • Sprinkler selection: K-factor, orientation (upright or pendent), temperature rating and system type (wet or dry).
  • Installation: protection area, spacing, distances below the ceiling and above the storage, and obstruction rules.
  • Hydraulic demand: number of design sprinklers, minimum pressure, hose stream allowance and duration.

Key numeric criteria

The values below are the general limits you meet most often. Final values must always be taken from the relevant table row, the product listing and the edition of NFPA 13 in force.

ParameterGeneral criterionNote
Minimum K-factor (7.2.2.5)K11.2 (K160)Common options: K11.2 / K16.8 (K240) / K19.6 (K280) / K25.2 (K360)
Protection area per sprinkler (13.2.4)Not more than 12 m² (130 ft²), not less than 7.4 m² (80 ft²)Upper limit 9 m² (100 ft²) under combustible obstructed construction and for rack storage
Maximum distance between sprinklers (13.2.5.1)3.7 m (12 ft)3.0 m (10 ft) under combustible obstructed construction
Minimum distance between sprinklers (13.2.5.4)2.4 m (8 ft)Prevents cold soldering of adjacent heads
Deflector to top of storage (13.2.8)At least 900 mm (36 in)Space needed for the spray pattern to develop
Design methodFixed number of sprinklers × minimum pressureBoth values come from the table

Design decisions: reading the table row correctly

Each row in a CMSA table represents a tested scenario. The variables that define the row are commodity class (Class I–IV, Group A plastics, cartoned or exposed, expanded or unexpanded), storage arrangement, maximum storage height, maximum ceiling height, K-factor, orientation and system type. If one variable is not covered, you do not interpolate from a neighbouring row; you move to another protection option or add in-rack sprinklers.

Commodity class is the critical input

A CMSA selection is only as good as the commodity classification behind it. The step from cartoned to exposed Group A plastics can make a design valid or invalid. See commodity classification in NFPA 13 for the logic.

Ceiling height and slope

The tables are built around the highest point of the ceiling, not the average. On pitched roofs the ridge governs. CMSA sprinklers may be installed only where the roof or ceiling slope does not exceed 4 in 12 (13.2.1.2). If the roof is steeper, the answer is a flat ceiling below it or a different protection approach. The ceiling-only CMSA tables (Tables 22.2–22.5) go up to a 12.2 m (40 ft) ceiling; roll paper (Table 22.7) is the exception.

Wet or dry?

An important difference from ESFR is that CMSA sprinklers may be used in wet, dry or pre-action systems in accordance with their listing (13.2.1.3). The Chapter 22 tables give separate rows for dry systems; the number of design sprinklers in those rows usually rises significantly, and water delivery time is a separate requirement. In storage, dry pipe systems use high-temperature sprinklers (13.2.2.4). This matters in applications such as cold storage sprinkler protection.

What "control mode" means

CMSA controls a fire; it does not promise extinguishment. It limits heat release, protects the structure and stops the fire spreading, while final extinguishment is left to the fire service. The hose allowance and duration are therefore part of the demand and must be included in the tank calculation. The fire water tank sizing calculator is a quick way to check storage volume.

CMSA, CMDA and ESFR compared

FeatureCMDA (density/area)CMSAESFR
Protection modeControlControlSuppression
Design inputDensity + areaNumber of sprinklers + pressure12 sprinklers + pressure
Dry systemsPossible with area increasePossible where the table has a dry rowWet only (unless specifically listed)

For a deeper comparison read ESFR vs CMSA sprinklers and the field view in CMDA vs CMSA sprinklers. To see quickly whether ESFR is even an option for the building, try the ESFR suitability checker.

Common site mistakes

  1. The commodity changes after handover. The design is based on cartoned Class III goods; a few years later the same racks hold products in exposed plastic packaging, and the CMSA row no longer applies.
  2. Losing the 900 mm clearance. Storage height creeps up in operation until the top load sits close to the deflectors and the spray pattern is disrupted.
  3. Obstructions added later. Lighting, cable trays and ductwork cut across the large-drop pattern.
  4. Mixed-up sprinklers. A standard spray head with the same K-factor is fitted in place of a CMSA head. Always check the sprinkler identification number.
  5. Wrong ceiling height. Selecting the table row from eaves height instead of the ridge.
  6. Heads closer than 2.4 m. Water from the first sprinkler can wet and delay its neighbour.

Rule of thumb: a CMSA design is a recipe. If one condition of the recipe is missing on site, getting the others right does not deliver protection. Write the selected table row and every assumption into the design report so that operational changes can be checked against it.

Design checklist

  • Is the commodity class and packaging type recorded in writing?
  • Is the storage arrangement (palletised, solid-piled, single/double/multiple-row rack) and maximum storage height defined?
  • Have the highest ceiling point and roof slope (not more than 4 in 12) been measured?
  • Does the listing of the selected sprinkler cover this row?
  • Are protection area and maximum/minimum spacing met?
  • Is there at least 900 mm clearance between deflector and storage?
  • Have obstruction rules been checked for every ceiling element?
  • Are the hose allowance and duration included in the water supply calculation?
  • Does the temperature rating match the table? (temperature rating selector)

Frequently Asked Questions

What is the main difference between CMSA and standard spray sprinklers?

Standard spray design is based on density and area. CMSA takes a tested number of sprinklers and a minimum pressure straight from a table for a specific storage scenario, and uses large-K sprinklers that produce larger drops.

Can CMSA sprinklers be used on dry pipe systems?

NFPA 13-2025 (13.2.1.3) permits CMSA sprinklers in wet, dry or pre-action systems in accordance with their listing. The Chapter 22 tables have separate dry-system rows; the number of operating sprinklers usually increases and water delivery time is checked separately.

Do CMSA designs need in-rack sprinklers?

Many rack scenarios can be protected by CMSA ceiling sprinklers alone. When storage height, commodity or rack arrangement exceeds the table limits, in-rack sprinklers are added or another protection option is used.

Why is the number of CMSA sprinklers fixed?

Because it comes from full-scale fire tests in which that number of sprinklers controlled the fire. The hydraulic calculation must prove that the most demanding group of that many sprinklers reaches the minimum pressure.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

NFPA 13 (2025 edition) – Chapter 13 (CMSA installation), 7.2.2.5 (K-factor) and Chapter 22 (CMSA storage criteria); product listings (UL/FM). Confirm with the authority having jurisdiction for each project. The findings here are typical defect patterns, not an account of events at any particular site.