Skip to content
Water supply

Fire water tank sizing calculator

Size the sprinkler water tank from the code's own tables: pick the hazard group and sprinkler height, the Annex 8/A (Minimum Water Tank Volume for the Preliminary Calculation of Sprinkler, Hose Cabinet and Hydrant Design) cell lights up and the tank section fills. The Art. 92/5 cabinet + hydrant cross-check, a hydraulic mode, EN 12845 and NFPA 13 sit on the same screen.

Turkish codeEN 12845NFPA 13Effective volume

This tool is for preliminary sizing and checking; confirm the final design against the edition of the standard in force and the authority having jurisdiction.

38 more calculators ↓

What governs a fire water tank calculation?

In Türkiye the tank volume for a fire design is set first by the Regulation on the Fire Protection of Buildings (BYKHY). Article 92 gives the durations and the preliminary sizing routes, and Article 96/5 requires sprinkler systems to be designed to BS EN 12845. The calculator therefore offers three modes: BYKHY (default), EN 12845 and, for comparison, NFPA 13.

The regulation gives the Annex 8/A values as the “minimum water tank volume”; the word “effective” comes from EN 12845: 9.3.2.2 treats the Table 9 values as the minimum effective volume, and 9.3.2.1 defines the effective capacity as the difference between the normal water level and the lowest effective water level. The tool reads the table values as usable water in that sense: water below the suction inlet and the freeboard sit outside that figure; the tool adds them as a separate "design allowance" that is not a code value.

BYKHY Article 92: three routes to the tank volume

The calculator's default reading (interpretation)

Route: Art. 92/4 permits either route. Art. 96/5, however, ties sprinkler design to BS EN 12845, where Table 9 (= Annex 8/A (preliminary, minimum volume)) sets the sprinkler volume of a pre-calculated system. The tool therefore takes the larger of the two routes by default and shows both values with their sources. The switch "Use only the selected route (Art. 92/4)" applies the literal wording and warns if the result falls below the cautious value.

Cabinets and hydrants: Annex 8/A is titled "Minimum Water Tank Volume for the Preliminary Calculation of Sprinkler, Hose Cabinet and Hydrant Design", which can be read as the table value already covering cabinets and hydrants. EN 12845 §9.3.2.2, on the other hand, reserves the table volume solely for the sprinkler system. Where cabinets and hydrants draw from the same tank, the tool adds the Annex 8/C flow × duration to the Annex 8/A (preliminary, minimum volume) value by default. The switch "Annex 8/A (preliminary, minimum volume) value already covers cabinets and hydrants" selects the other reading. Agree both points with the authority on each project.

Annex 8/A: Minimum Water Tank Volume for the Preliminary Calculation of Sprinkler, Hose Cabinet and Hydrant Design (m³)

h is the height between the lowest and the highest sprinkler. Some rows are shared, such as "OH1 dry" with "OH2 wet".

Group and systemh ≤ 15 m15 < h ≤ 30 m30 < h ≤ 45 m
Low hazard wet / pre-action91011
OH1 wet557080
OH1 dry · OH2 wet105125140
OH2 dry · OH3 wet135160185
OH3 dry · OH4 wet160185200
OH4 dry · High hazardUse hydraulic calculation

A low-hazard dry system is designed as OH1 dry under Annex 8/B, so the "OH1 dry" row applies. The table stops at 45 m; above that nothing is extrapolated and a hydraulic calculation is needed.

Annexes 8/B and 8/C: inputs to the Art. 92/5 method

Annex 8/B lists design densities and areas: low hazard 2.25 mm/min over 84 m²; OH1–OH4 5.0 mm/min over 72 / 144 / 216 / 360 m² (dry 90 / 180 / 270 m², OH4 dry uses HH1); HH1, HH2 and HH3 over 260 m² (dry 325 m²); HH4 needs deluge protection. The regulation text gives 7.7 mm/min for High Hazard 1, whereas EN 12845 Table 3 gives 7.5. The tool uses the regulation value as written and notes the difference.

Building hazard (Annex 8/C)CabinetHydrantDuration
Low hazard100 L/min400 L/min30 min
Ordinary 1–2100 L/min400 L/min60 min
Ordinary 3–4100 L/min1000 L/min60 min
High hazard200 L/min1500 L/min90 min

EN 12845: Table 9, Table 10 and calculated systems

EN 12845 §9.3.2.2 gives Table 9 as the minimum effective volume for pre-calculated LH and OH systems. Its values are identical to Annex 8/A (preliminary, minimum volume) and are reserved solely for the sprinkler system. The OH4 dry row says "use HH protection", and Table 3 sends that to HHP1. Table 10 gives HHP and HHS volumes by design density (for example 7.5 mm/min: 225 m³ wet, 280 m³ dry; 12.5 mm/min: 350 / 440 m³). A density between two rows uses the higher "not exceeding" row.

For calculated systems (§9.3.2.3) the minimum effective volume is the maximum flow Qmax times the §8.1.1 duration: LH 30, OH 60, HHP and HHS 90 minutes. The Table 3 redirection applies to the duration too: LH dry is calculated as OH1 (60 min) and OH4 dry as HHP1 (90 min). The source must be able to refill a full-capacity tank within 36 hours (§9.3.3). A reduced capacity tank (§9.3.4) needs an automatic town-main inflow through at least two float valves. Tank plus inflow must cover the full volume, and the tank may not drop below the Table 11 floor (LH 5, OH1 wet 10 … HHP/HHS 70 m³ and at least 10% of full capacity). A pressure tank is a separate type of supply; as a single supply it needs at least 15 m³ of water for LH and 23 m³ for OH1 (§9.5.3).

Worked example: OH2 wet, h ≤ 15 m

Take a fire design with ordinary hazard group 2, a wet-pipe system and 10 m between the lowest and highest sprinkler. The site also has a hydrant system.

  1. Annex 8/A (preliminary, minimum volume): row "OH1 dry · OH2 wet", column h ≤ 15 m → 105 m³ (sprinklers).
  2. Annex 8/C: Ordinary 1–2 row: 100 L/min cabinet + 400 L/min hydrant = 500 L/min; over 60 min that is 30 m³. Annex 8/A (preliminary, minimum volume) + 8/C = 135 m³.
  3. Art. 92/5 cross-check: 5.0 × 144 = 720 L/min sprinklers + 500 L/min = 1220 L/min; over 60 min that is 73.2 m³.
  4. The larger route gives 135 m³. Under the reading that Annex 8/A (preliminary, minimum volume) already covers cabinets and hydrants, the result is 105 m³.
  5. Refill: 135 m³ ÷ 36 h = 62.5 L/min inflow.
  6. Size: at 5 m effective water height the footprint is 27 m²: Ø ≈ 5.86 m for a cylinder, or a 5.20 m square. Water below the suction and freeboard come on top.

The Art. 92/5 example and Table 9: the 73.2 m³ from Art. 92/5 already includes cabinet and hydrant water, yet it is below the 105 m³ that EN 12845 Table 9 reserves for sprinklers alone; its sprinkler share is only 720 L/min × 60 min = 43.2 m³. Because EN 12845 treats Table 9 as the minimum effective volume of a pre-calculated system, the tool shows the Art. 92/5 figure on its own only behind a switch and with a warning.

The previous version of this calculator multiplied density × area × duration by an "overrun factor" even for pre-calculated systems. For OH2 wet that gives about 55 m³, roughly half the table value. For pre-calculated systems the table governs, and that error has been corrected.

Tank sizing: concrete and modular tanks (3D)

Once you have the volume, pick the tank size. For a reinforced concrete tank you set the internal length, width and height freely; for a modular panel tank length and width move in 1 m panel and 0.5 m half-panel steps and height is up to three tiers (1–3 m). The tool compares the selected tank's internal volume (L × W × H) with the required volume; where a design allowance is entered, the comparison uses the gross volume. If the tank is too small it shows the shortfall and suggests the height needed on the same footprint or the length needed at the same height.

In the 3D view the water is the level the required volume reaches in the selected tank; the dashed line marks the required level and the amber hatched bottom band the unusable volume allowance. If the tank is too small, the shortfall is drawn in red above the tank. Concrete wall thickness in the view is illustrative and comes from the structural design. For modular tanks only surface panels are counted; corner and joint pieces, internal stays, manhole and support base are not. Panel sizes are nominal; the manufacturer confirms net volume and the parts list.

Common mistakes

The NFPA 13 mode is there for comparison. Under §1.6.1.3 the first-stated US values are the requirement, so the calculation runs in gpm/ft², ft² and gpm in both unit modes and SI figures are conversions. The Table 19.2.3.1.1 design point (e.g. OH2 0.20 gpm/ft² over 1500 ft²) is modified as follows: area +30% for dry-pipe and double-interlock pre-action systems (19.2.3.2.6); area +30% under a ceiling sloped more than 2 in 12 unless one of the 19.2.3.2.4 exceptions applies; and 19.2.3.2.5.2 for ceilings above 30 ft (9.1 m): OH1 area +30%, OH2 at least 0.37 gpm/ft² at 30–40 ft and 0.45 gpm/ft² with area +30% above 40 ft, extra hazard at least 0.45 gpm/ft². Area increases are compounded (19.2.3.2.8.1). Hose allowance and duration come from Table 19.2.3.1.2; the lower duration applies only where alarm devices are electrically supervised (19.2.3.1.3).

Frequently Asked Questions

How big should a fire water tank be?

Under BYKHY the preliminary volume comes from the Annex 8/A (preliminary, minimum volume) table or the Art. 92/5 method, and a hydraulic calculation governs where one exists. For an OH2 wet system with up to 15 m between the lowest and highest sprinkler, Annex 8/A (preliminary, minimum volume) gives 105 m³. Where hose cabinets and hydrants draw from the same tank, the calculator cautiously adds the Annex 8/C water: (100 + 400) L/min × 60 min = 30 m³, 135 m³ effective in total. Water below the suction and freeboard come on top.

What tank volume does an Ordinary Hazard 3 wet system need?

Annex 8/A (preliminary, minimum volume) and EN 12845 Table 9 give 135 m³ for OH3 wet (the same row as OH2 dry) up to h = 15 m, 160 m³ for 15–30 m and 185 m³ for 30–45 m. Where cabinets and hydrants share the tank, the Annex 8/C water of (100 + 1000) L/min × 60 min = 66 m³ is added, giving 201 m³ up to 15 m. The Art. 92/5 cross-check gives 5.0 × 216 + 100 + 1000 = 2180 L/min × 60 min = 130.8 m³, which is smaller.

Is hose cabinet and hydrant water added to the Annex 8/A value?

The regulation does not say so explicitly, and there are two readings. Annex 8/A (preliminary, minimum volume) is titled for the combined preliminary sizing of sprinklers, cabinets and hydrants; on that reading Annex 8/C is not added again. Article 96/5, however, ties sprinkler design to EN 12845, which (§9.3.2.2) reserves the table volume for sprinklers alone. The calculator uses that cautious reading by default and adds the Annex 8/C water; a switch selects the other reading. Agree which one applies with the authority.

When is a hydraulic calculation required for the tank volume?

Annex 8/A (preliminary, minimum volume) says "use hydraulic calculation" for OH4 dry/alternate and high hazard, and the table does not cover heights above 45 m. The volume is then the calculated maximum flow times the Art. 92/3 duration (30/60/90 min). Following the addition in Art. 92/5, the calculator also adds the Annex 8/C cabinet and hydrant flow by default; switch it off if your hydraulic calculation already includes them. EN 12845 §9.3.2.3 and §8.1.1 follow the same logic.

What is the difference between effective and gross tank volume?

The tables give effective volume: the water between the normal level and the lowest level at which the suction works. Water below the suction inlet, vortex submergence and freeboard are added to reach the gross volume. The regulation gives no number for this allowance; derive it from the suction detail.

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store

SprinkCalc — Fire Sprinkler Design in Three Standards

Run these calculations on site, offline and with PDF reports: NFPA 13, FM Global and BS EN 12845 in one iOS app.

Get SprinkCalc on the App Store

Related content

Other fire protection calculators

All calculators →