The second article in the NFPA 25 series covers Chapter 5: sprinkler systems. The first article dealt with the fire pump assembly; this one covers the sprinkler system itself as installed to NFPA 13 or NFPA 13R: sprinklers, pipe, hangers, signs, the spare sprinkler cabinet, sprinkler sample testing, antifreeze systems and what to do when a component changes. Common components such as valves, gauges, alarm devices and the fire department connection are sent to Chapter 13; they will get their own article in the series. Every line carries its clause number from NFPA 25-2026.
In short: Sprinklers, pipe, hangers, sprinkler guards, the spare sprinkler cabinet and signs are inspected annually from the floor level (5.2). A sprinkler that leaks, is damaged, has lost fluid from its glass bulb, or shows corrosion, loading or field-applied paint detrimental to performance is replaced (5.2.1.1.1). Keep at least 18 in. (457 mm) between deflector and storage, and at least 36 in. (914 mm) for ESFR, CMSA and rubber tire storage (5.2.1.2). Sprinklers are replaced or sample-tested at 50 years (25 for fast-response, 20 for ESFR/CMSA and dry sprinklers) (5.3.1.1). Antifreeze is tested every year before the freezing season (5.3.4). At least 6 spare sprinklers are kept on the premises (5.4.1.6).
A. Scope and general rules
Chapter 5 gives the minimum requirements for routine inspection, testing and maintenance of sprinkler systems installed to NFPA 13, NFPA 13R or another approved installation standard (5.1.1.1). Minimum frequencies come from Table 5.1.1.2 (5.1.1.2).
| Check | Criterion | Clause |
|---|---|---|
| ☐ Common components and valves | Inspected, tested and maintained per Chapter 13 | 5.1.2 |
| ☐ Internal piping assessment or obstruction investigation needed | Follow the procedures of Chapter 14 | 5.1.3 |
| ☐ Impairment to protection | Follow the impairment procedures of Chapter 15 | 5.1.4 |
| ☐ Hose connections | Inspected, tested and maintained per Chapters 6 and 13 | 5.1.5 |
B. Frequency summary: Table 5.1.1.2
The standard’s summary table is reproduced below in condensed form. Rows marked "—" have no frequency of their own in the table; the frequency and method come from the chapter in the right-hand column (mostly Chapter 13).
| Item | Frequency | Reference |
|---|---|---|
| Inspection | ||
| Assessment of the internal piping condition | — | Chapter 14 |
| Automatic air vents | — | Chapter 13 |
| Control valves | — | Chapter 13 |
| Fire department connections | — | Chapter 13 |
| Gauges (wet and deluge systems) | — | Chapter 13 |
| Gauges (dry and preaction systems) | — | Chapter 13 |
| Hangers, braces and supports | Annually | 5.2.3 |
| Heat tracing | — | 5.2.6 |
| Hydraulic design information sign | Annually | 5.2.5 |
| Information signs | Annually | 5.2.7, 5.2.8 |
| Pipe and fittings | Annually | 5.2.2 |
| Sprinklers | Annually | 5.2.1 |
| Sprinklers (electrically operated) | Annually | 5.2.1.5 |
| Sprinklers (spare) | Annually | 5.2.1.4 |
| Sprinkler guards | Annually | 5.2.1.1.7 |
| Supervisory signal devices (except valve supervisory switches) | — | 5.2.4, Chapter 13 |
| System valves | — | Chapter 13 |
| Valve supervisory signal devices | — | 5.2.4, Chapter 13 |
| Waterflow alarm devices | — | 5.2.4, Chapter 13 |
| Test | ||
| Antifreeze solution | Annually | 5.3.4 |
| Control valves | — | Chapter 13 |
| Electrically operated sprinklers | — | 5.3.2 |
| Gauges | — | Chapter 13 |
| Main drain | — | Chapter 13 |
| Sprinklers (all) | At 50 years and every 10 years thereafter | 5.3.1 |
| Sprinklers (all) | At 75 years and every 5 years thereafter | 5.3.1 |
| Sprinklers (dry) | At 20 years and every 10 years thereafter | 5.3.1 |
| Sprinklers (extra-high or greater temperature solder type) | Every 5 years | 5.3.1 |
| Sprinklers (fast-response, except ESFR and CMSA) | At 25 years and every 10 years thereafter | 5.3.1 |
| Sprinklers (ESFR and CMSA with fast-response elements) | At 20 years and every 10 years thereafter | 5.3.1 |
| Sprinklers (harsh environments) | Every 5 years | 5.3.1 |
| Supervisory signal devices (except valve supervisory switches) | — | Chapter 13 |
| System valves | — | Chapter 13 |
| Valve supervisory signal devices | — | Chapter 13 |
| Waterflow alarm devices | — | 5.3.3, Chapter 13 |
| Maintenance | ||
| Low-point drains (dry pipe and preaction systems) | — | Chapter 13 |
| Sprinklers and automatic spray nozzles protecting commercial cooking equipment and ventilation systems | Annually | 5.4.1.8 |
| Replacement of sprinklers | — | 5.4.1.1 |
| Replacement of sprinklers affected by a fire | — | 5.4.1.1 |
| Replacement of threaded sprinklers removed from a fitting for any reason (except dry type) | — | 5.4.1.2 |
| Stock of spare sprinklers | — | 5.4.1.6 |
| Valves (all types) | — | Chapter 13 |
| Investigation | ||
| Obstruction | — | Chapter 14 |
C. Annual inspection: sprinklers
Sprinklers are inspected annually from the floor level (5.2.1.1). A sprinkler showing any of the following is replaced (5.2.1.1.1):
| Check | Criterion | Clause |
|---|---|---|
| ☐ Leakage | Replace if present | 5.2.1.1.1(1) |
| ☐ Corrosion | Replace if detrimental to sprinkler performance | 5.2.1.1.1(2) |
| ☐ Physical damage | Replace if present | 5.2.1.1.1(3) |
| ☐ Glass bulb heat-responsive element | Replace if fluid has been lost | 5.2.1.1.1(4) |
| ☐ Loading (dust, grease, lint) | Replace if detrimental to sprinkler performance | 5.2.1.1.1(5) |
| ☐ Paint | Replace if applied by anyone other than the manufacturer and detrimental to performance | 5.2.1.1.1(6) |
| ☐ Sprinkler installed in the incorrect orientation | Correct by repositioning the branch line, drop or sprig, or replace the sprinkler | 5.2.1.1.2 |
| ☐ Sprinklers in concealed spaces such as above suspended ceilings | No inspection required | 5.2.1.1.3 |
| ☐ Sprinklers in areas inaccessible for safety reasons due to process operations | Inspected during each scheduled shutdown | 5.2.1.1.4 |
Escutcheons and coverplates for recessed, flush and concealed sprinklers
| Check | Criterion | Clause |
|---|---|---|
| ☐ Escutcheon or coverplate missing | Replace with a listed escutcheon or coverplate that is part of the listed sprinkler assembly | 5.2.1.1.5 |
| ☐ Physical damage, or corrosion, loading or field paint detrimental to performance | Replace with a listed escutcheon or coverplate | 5.2.1.1.5(1)–(4) |
| ☐ Escutcheon or coverplate adhered or attached to the ceiling or wall | Replace | 5.2.1.1.5.1 |
| ☐ Required listed escutcheon or coverplate no longer commercially available | Replace the whole sprinkler assembly | 5.2.1.1.5.2 |
| ☐ Escutcheon missing on a pendent sprinkler that is not recessed, flush or concealed | Replacement not required | 5.2.1.1.6 |
Sprinkler guards and electrically operated sprinklers
| Check | Criterion | Clause |
|---|---|---|
| ☐ Sprinkler guards (where installed) | Inspected annually from the floor level | 5.2.1.1.7.1 |
| ☐ Damaged sprinkler guard | Replace with a guard listed for that sprinkler | 5.2.1.1.7.2 |
| ☐ Electrically operated sprinklers | Inspected annually from the floor level per 5.2.1.1 and the manufacturer’s requirements | 5.2.1.5 |
D. Clearance between storage and deflectors
The following minimum clearance is maintained below all sprinkler deflectors (5.2.1.2). This is the most frequent annual finding: racks get taller and piles creep toward the ceiling.
| Check | Criterion | Clause |
|---|---|---|
| ☐ General case | At least 18 in. (457 mm) between deflector and top of storage | 5.2.1.2.1 |
| ☐ ESFR and CMSA sprinklers | At least 36 in. (914 mm) | 5.2.1.2.2 |
| ☐ Another standard than NFPA 13 requires a larger clearance | That value is followed | 5.2.1.2.3 |
| ☐ Rubber tire storage | At least 36 in. (914 mm) | 5.2.1.2.4 |
| ☐ In-rack sprinklers | Obstruction and storage clearance requirements do not apply | 5.2.1.2.5 |
| ☐ Where the installation standard permits | Less than 18 in. (457 mm) is allowed | 5.2.1.2.6 |
| ☐ Storage violating the clearance rules | Corrected | 5.2.1.3 |
E. Pipe, fittings, hangers and supports
| Check | Criterion | Clause |
|---|---|---|
| ☐ Pipe and fittings | Inspected annually from the floor level | 5.2.2 |
| ☐ Condition of pipe and fittings | Free of mechanical damage, leakage and corrosion | 5.2.2.1 |
| ☐ Use of sprinkler piping | Not used to support nonsystem components | 5.2.2.2 |
| ☐ Hangers, braces and supports | Inspected annually from the floor level | 5.2.3 |
| ☐ Condition of hangers, braces and supports | Not damaged, loose or unattached | 5.2.3.1 |
| ☐ Damaged, loose or unattached hangers and supports | Replaced or refastened | 5.2.3.2 |
| ☐ Pipe, hangers and supports in concealed spaces such as above suspended ceilings | No inspection required | 5.2.2.3, 5.2.3.3 |
| ☐ Pipe, hangers and supports in areas inaccessible due to process operations | Inspected during each scheduled shutdown | 5.2.2.4, 5.2.3.4 |
F. Signs, heat tracing and alarm devices
| Check | Criterion | Clause |
|---|---|---|
| ☐ Hydraulic design information sign | Annually: provided, attached securely to the sprinkler riser and legible | 5.2.5 |
| ☐ Missing or illegible hydraulic design sign | Replaced | 5.2.5.1 |
| ☐ Pipe schedule system | Hydraulic design sign reads “Pipe Schedule System” | 5.2.5.2 |
| ☐ General information sign (where required by NFPA 13) | Annually: provided, securely attached and legible | 5.2.7 |
| ☐ General information sign material | Permanently marked weatherproof metal or rigid plastic, secured with corrosion-resistant wire, chain or other acceptable means | 5.2.7.1 |
| ☐ General information sign location | At each system riser | 5.2.7.2 |
| ☐ System where a general information sign was not required at acceptance | Only the information sign required by 4.1.10 is inspected annually | 5.2.7.3 |
| ☐ Antifreeze information sign (4.1.11) | Annually: provided, securely attached and legible | 5.2.8 |
| ☐ Heat tracing | Inspected and maintained per the manufacturer’s requirements | 5.2.6 |
| ☐ Waterflow alarm and supervisory signal initiating devices | Inspected and tested per Chapter 13 | 5.2.4, 5.3.3 |
G. Sprinkler sample testing: when?
Once sprinklers reach a certain age or condition there are two options: replace them, or send representative samples to an approved testing laboratory for field service testing and retest at set intervals (5.3.1.1).
| Sprinklers | Replace or first test | Retest | Clause |
|---|---|---|---|
| All sprinklers | After 50 years in service | Every 10 years | 5.3.1.1.1 |
| Sprinklers with fast-response elements (except ESFR and CMSA) | After 25 years | Every 10 years | 5.3.1.1.1.1 |
| ESFR and CMSA sprinklers with fast-response elements | After 20 years | Every 10 years | 5.3.1.1.1.2 |
| Solder-type, extra-high or greater temperature classification [325 °F (163 °C) and above], exposed to semi-continuous to continuous maximum allowable ambient temperature | After 5 years | Every 5 years | 5.3.1.1.1.3 |
| Sprinklers manufactured in 1920 and later | After 75 years | Every 5 years | 5.3.1.1.1.4 |
| Dry sprinklers | After 20 years | Every 10 years | 5.3.1.1.1.5 |
| Sprinklers in dwelling units | After 50 years: replace with fast-response sprinklers, or test samples for thermal sensitivity so that RTI does not exceed 65 (m·s)1/2 | — | 5.3.1.1.1.7 |
| Sprinklers exposed to harsh environments, including corrosive atmospheres | After 5 years | Every 5 years | 5.3.1.1.2 |
| Listed corrosion-resistant sprinklers in harsh environments | After 10 years | Every 5 years | 5.3.1.1.3 |
Longer intervals are permitted where historical data indicate (5.3.1.1.4). Sprinklers manufactured before 1920 are not tested; they are replaced (5.4.1.1(1)). Concealed sprinklers that fail sample testing have coverplates and sprinklers replaced together as a listed assembly (5.3.1.1.1.6).
H. How is the sample chosen?
| Check | Criterion | Clause |
|---|---|---|
| ☐ Sample size | At least four sprinklers or 1 percent of the sprinklers per sample area, whichever is greater | 5.3.1.2 |
| ☐ Representativeness | Each sprinkler type and manufacturer in the sample area is represented | 5.3.1.2.1 |
| ☐ Sprinklers replaced at prior tests | Not included in the sample | 5.3.1.2.2 |
| ☐ One sprinkler in the sample fails | All sprinklers in the area represented by that sample are replaced | 5.3.1.3 |
| ☐ Electrically operated sprinklers | Tested per the manufacturer’s requirements; electronic actuation and supervision tested per the manufacturer and NFPA 72 or the local fire alarm code | 5.3.2.1, 5.3.2.2 |
I. Antifreeze systems: annual test
Every year, toward the beginning of the heating season and before freezing conditions set in, the antifreeze solution is tested in this order (5.3.4):
- The type of antifreeze is determined from the antifreeze information sign (4.1.11), installation and maintenance records, the owner, chemical tests or other reliable sources. If the type is no longer permitted or cannot be reliably determined, the system is drained and refilled with a listed or acceptable solution. If it is not replaced, samples are taken at the top and bottom of each system, plus the most remote portion and the water supply connection where these are not near the top or bottom (5.3.4(1)).
- The specific gravity of each sample is checked with a hydrometer with a suitable scale or a refractometer calibrated for that antifreeze (5.3.4(2)).
- If any sample is outside the allowable range, the system is drained and refilled with a listed or acceptable solution per 5.3.4.4 (5.3.4(3)).
- If a concentration greater than 5.3.4.4 permits was needed to keep the fluid from freezing, alternative methods of preventing pipe freezing are used (5.3.4(4)).
| Check | Criterion | Clause |
|---|---|---|
| ☐ Test points | At the most remote portion and where it interfaces with the wet pipe system | 5.3.4.1 |
| ☐ Antifreeze system larger than 150 gal (568 L) | One additional test point for every 100 gal (379 L) | 5.3.4.2 |
| ☐ Incorrect freeze point anywhere in the system | Drain and refill with a listed or acceptable solution | 5.3.4.2.1 |
| ☐ Listed solutions | Follow the manufacturer’s instructions for number of test points and refill procedure | 5.3.4.2.2 |
| ☐ Health regulations | Antifreeze use conforms with state and local health regulations | 5.3.4.3 |
| ☐ Listed CPVC sprinkler pipe and fittings | Protected from freezing with a listed solution or a glycerine solution per 5.3.4.4; diethylene, ethylene and propylene glycols are specifically prohibited | 5.3.4.3.1, 5.3.4.3.1.1 |
| ☐ Type of solution | Listed antifreeze solutions in all antifreeze systems, except as permitted by 5.3.4.4.2 and 5.3.4.4.3 | 5.3.4.4 |
| ☐ Listed solution replacing a nonlisted one | May be used outside its system volume and hydraulic calculation requirements if temperature range limits are not exceeded; complies with all other requirements | 5.3.4.4.1, 5.3.4.4.1.1 |
| ☐ Existing nonlisted solution remaining in a system | Tests at its specified concentration and the premix is limited to 30 percent propylene glycol or 38 percent glycerine by volume | 5.3.4.4.2 |
| ☐ Nonlisted premixed propylene glycol above 30 percent by volume | Only with ESFR sprinklers listed for such use in a specific application | 5.3.4.4.3 |
J. Spare sprinkler cabinet
The cabinet is inspected annually for three things: the correct number and type of sprinklers required by 5.4.1.6, a sprinkler wrench for each type of sprinkler (5.4.1.6.5) and the list of spare sprinklers (5.4.1.6.6) (5.2.1.4).
| Check | Criterion | Clause |
|---|---|---|
| ☐ Under 300 sprinklers in the facility | No fewer than 6 spare sprinklers in the cabinet | 5.4.1.6.4(1) |
| ☐ 300 to 1000 sprinklers | No fewer than 12 spare sprinklers | 5.4.1.6.4(2) |
| ☐ Over 1000 sprinklers | No fewer than 24 spare sprinklers | 5.4.1.6.4(3) |
| ☐ Type of spares | Correspond to the types and temperature ratings of the sprinklers in the property | 5.4.1.6.1 |
| ☐ Cabinet location | Temperature never exceeds the maximum ceiling temperature in Table 5.4.1.6.2 for any sprinkler in the cabinet | 5.4.1.6.2 |
| ☐ Dry sprinklers of different lengths | Spare dry sprinklers not required if a means of returning the system to service is furnished | 5.4.1.6.3 |
| ☐ Sprinkler wrench | One wrench as specified by the manufacturer for each type of sprinkler installed, kept with the spares | 5.4.1.6.5 |
| ☐ Sprinkler list | Posted in the cabinet | 5.4.1.6.6 |
The posted list includes at least (5.4.1.6.6.1): the sprinkler identification number (SIN) if equipped, or the manufacturer, model, K-factor, deflector type, thermal sensitivity, pressure rating and temperature rating; the manufacturer’s wrench model number for each sprinkler type; a general description; the quantity of each type installed in the property; the quantity of each type to be kept in the cabinet; and the issue or revision date of the list.
| Maximum ceiling temperature | Temperature rating | Classification | Color code | Glass bulb color |
|---|---|---|---|---|
| Table 5.4.1.6.2 | ||||
| 100 °F (38 °C) | 135–170 °F (57–77 °C) | Ordinary | Uncolored or black | Orange or red |
| 150 °F (66 °C) | 175–225 °F (79–107 °C) | Intermediate | White | Yellow or green |
| 225 °F (107 °C) | 250–300 °F (121–149 °C) | High | Blue | Blue |
| 300 °F (149 °C) | 325–375 °F (163–191 °C) | Extra high | Red | Purple |
| 375 °F (191 °C) | 400–475 °F (204–246 °C) | Very extra high | Green | Black |
| 475 °F (246 °C) | 500–575 °F (260–302 °C) | Ultra high | Orange | Black |
| 625 °F (329 °C) | 650 °F (343 °C) | Ultra high | Orange | Black |
K. Maintenance: replacing sprinklers
| Check | Criterion | Clause |
|---|---|---|
| ☐ Sprinklers to be replaced | Manufactured before 1920; showing the signs in 5.2.1.1.1; failing the 5.3.1 test; affected by a fire as determined by the AHJ | 5.4.1.1 |
| ☐ Threaded sprinkler removed from a fitting or welded outlet | Not reinstalled | 5.4.1.2 |
| ☐ Dry sprinklers | May be reinstalled if removed per the manufacturer’s installation and maintenance instructions | 5.4.1.2.1 |
| ☐ Sprinkler still attached to the original fitting or removable by a grooved connection | May be reinstalled, taking care it is not damaged | 5.4.1.2.2 |
| ☐ Sprinklers listed for use with a specifically listed fitting | May be reinstalled per the manufacturer’s instructions | 5.4.1.2.3 |
| ☐ Characteristics of the replacement | Proper for the application: style, orifice size and K-factor, temperature rating, coating if any, deflector type (upright, pendent, sidewall) and design requirements | 5.4.1.3 |
| ☐ Old-style sprinklers | May be replaced with spray sprinklers | 5.4.1.3.1 |
| ☐ Residential sprinklers made before 2003, no longer available (design density below 0.05 gpm/ft² [204 mm/min]) | A residential sprinkler with an equivalent K-factor (±5 percent or the next larger K-factor), provided the currently listed coverage area is not exceeded | 5.4.1.3.2 |
| ☐ Piers and wharves | Replacement sprinklers comply with NFPA 307 | 5.4.1.3.3 |
| ☐ Replacement sprinklers | Only new, listed sprinklers | 5.4.1.4 |
| ☐ Special and quick-response sprinklers | Replaced with the same orifice, size, temperature range, thermal response characteristics and K-factor | 5.4.1.5 |
| ☐ Alteration | No alteration, ornamentation, paint or coating after shipment from the factory | 5.4.1.7 |
| ☐ Sprinklers and automatic spray nozzles protecting commercial cooking equipment and ventilating systems | Replaced annually; bulb-type units showing no grease or other buildup at the annual examination need not be replaced | 5.4.1.8, 5.4.1.8.1 |
| ☐ Electrically operated sprinklers | Maintained per the manufacturer’s requirements | 5.4.1.9 |
| ☐ Sprinklers in spray areas and mixing rooms of resin application areas | Kept protected against overspray residue with cellophane bags 0.003 in. (0.076 mm) thick or less or thin paper bags, replaced periodically before heavy deposits accumulate | 5.4.1.10.1–5.4.1.10.3 |
L. Dry pipe and marine systems
| Check | Criterion | Clause |
|---|---|---|
| ☐ Dry pipe system | Kept dry at all times | 5.4.2 |
| ☐ Nonfreezing weather, waiting for parts or during repair | May be left wet if the only other option is to take the system out of service | 5.4.2.1 |
| ☐ Refrigerated spaces and other interior areas subject to freezing | May not be left wet | 5.4.2.2 |
| ☐ Air driers | Maintained per the manufacturer’s instructions | 5.4.2.3 |
| ☐ Dry pipe system compressors | Inspected, tested and maintained per Chapter 13 and the manufacturer’s instructions | 5.4.2.4 |
| ☐ Raw water introduced into a marine system normally kept on fresh water | Drained and refilled, then drained and refilled again with fresh water | 5.4.4 |
M. When a component is adjusted, repaired or replaced: Table 5.5.1
Whenever a sprinkler system component is adjusted, repaired, reconditioned or replaced, the actions in Table 5.5.1 are performed (5.5.1). Where the original installation standard differs from the cited one, the appropriate installing standard may be used (5.5.2). These actions do not require a design review, which is outside the scope of the standard (5.5.3).
| Component | Adjust | Repair/recondition | Replace | Required action |
|---|---|---|---|---|
| Water delivery components | ||||
| Antifreeze solution | — | — | X | Test solution to verify it has not been unacceptably diluted; inspect for leaks at system working pressure |
| Fire department connections | X | X | X | See Chapter 13 |
| Pipe and fittings affecting no more than 20 sprinklers | X | X | X | Inspect for leaks at system working pressure |
| Pipe and fittings affecting more than 20 sprinklers | X | X | X | Hydrostatic test in conformance with NFPA 13 |
| Sprinklers, regardless of number | X | — | X | Inspect for leaks at system working pressure |
| Alarm and supervisory components | ||||
| Detection system for deluge or preaction system | X | X | X | Operational test for conformance with NFPA 13 and/or NFPA 72 |
| High and low air pressure switch | X | X | X | Operational test of high and low settings |
| Pressure switch–type waterflow | X | X | X | Operational test using the inspector’s test connection or alarm bypass test valve |
| Valve supervisory signal initiating device | X | X | X | Test for conformance with NFPA 13 and/or NFPA 72 |
| Vane-type waterflow | X | X | X | Operational test using inspector’s test connection |
| Water motor gong | X | X | X | Operational test using inspector’s test connection |
| Testing and maintenance components | ||||
| Air compressor | X | X | X | Operational test for conformance with NFPA 13 |
| Automatic air maintenance device | X | X | X | Operational test for conformance with NFPA 13 |
| Auxiliary drains | X | X | X | Inspect for leaks at system working pressure; main drain test |
| Gauges | X | — | X | Verify at 0 bar (0 psi) and system working pressure |
| Inspector’s test connection | X | X | X | Inspect for leaks at system working pressure; main drain test |
| Main drain | X | X | X | Main drain test |
| Structural components | ||||
| Hanger/seismic bracing | X | X | X | Inspect for conformance with NFPA 13 |
| Pipe stands | X | X | X | Inspect for conformance with NFPA 13 |
| Informational components | ||||
| Antifreeze information sign | X | X | X | Inspect for conformance with this standard |
| General information sign | X | X | X | Inspect for conformance with this standard |
| Hydraulic design information sign | X | X | X | Inspect for conformance with NFPA 13 and this standard |
| Identification sign | X | X | X | Inspect for conformance with NFPA 13 and this standard |
| Information sign | X | X | X | Inspect for conformance with this standard |
Frequently Asked Questions
How often are sprinklers inspected under NFPA 25?
Annually, from the floor level (5.2.1.1). Sprinklers in concealed spaces such as above suspended ceilings do not require inspection; those in areas inaccessible for safety reasons due to process operations are inspected during each scheduled shutdown (5.2.1.1.3, 5.2.1.1.4).
When must a sprinkler be replaced?
When it shows leakage, physical damage, loss of fluid in the glass bulb, or corrosion, loading or non-factory paint detrimental to performance (5.2.1.1.1); when it was manufactured before 1920, failed a sample test or was affected by a fire as determined by the AHJ (5.4.1.1). A threaded sprinkler that has been removed is not reinstalled (5.4.1.2).
How much clearance is needed between storage and sprinklers?
Generally at least 18 in. (457 mm) between the deflector and the top of storage; at least 36 in. (914 mm) for ESFR and CMSA sprinklers and for rubber tire storage (5.2.1.2.1, 5.2.1.2.2, 5.2.1.2.4). In-rack sprinklers are exempt (5.2.1.2.5).
At what age are sprinklers tested or replaced?
The general rule is 50 years, then every 10 years (5.3.1.1.1). Fast-response sprinklers at 25 years, ESFR/CMSA with fast-response elements and dry sprinklers at 20 years, harsh environments and extra-high temperature solder-type sprinklers under continuous maximum ambient at 5 years. The sample is at least 4 sprinklers or 1 percent; if one fails, the whole represented area is replaced (5.3.1.2, 5.3.1.3).
How many spare sprinklers must be kept?
At least 6 for facilities with under 300 sprinklers, 12 for 300 to 1000, and 24 for over 1000 (5.4.1.6.4). The cabinet also holds a sprinkler wrench for each type and the sprinkler list, and is inspected annually (5.4.1.6.5, 5.4.1.6.6, 5.2.1.4).

SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.
Download SprinkCalc on the App Store
MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App StoreNFPA 25-2026, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems: Chapter 5 (5.1–5.5), Table 5.1.1.2, Table 5.4.1.6.2 and Table 5.5.1. The content of Chapters 13, 14 and 15 and of NFPA 13, NFPA 72 and NFPA 307 referenced by Chapter 5 is not reproduced here.