The second article in the NFPA 25 series covers Chapter 5: sprinkler systems. The first article dealt with the fire pump assembly; this one covers the sprinkler system itself as installed to NFPA 13 or NFPA 13R: sprinklers, pipe, hangers, signs, the spare sprinkler cabinet, sprinkler sample testing, antifreeze systems and what to do when a component changes. Common components such as valves, gauges, alarm devices and the fire department connection are sent to Chapter 13; they will get their own article in the series. Every line carries its clause number from NFPA 25-2026.

In short: Sprinklers, pipe, hangers, sprinkler guards, the spare sprinkler cabinet and signs are inspected annually from the floor level (5.2). A sprinkler that leaks, is damaged, has lost fluid from its glass bulb, or shows corrosion, loading or field-applied paint detrimental to performance is replaced (5.2.1.1.1). Keep at least 18 in. (457 mm) between deflector and storage, and at least 36 in. (914 mm) for ESFR, CMSA and rubber tire storage (5.2.1.2). Sprinklers are replaced or sample-tested at 50 years (25 for fast-response, 20 for ESFR/CMSA and dry sprinklers) (5.3.1.1). Antifreeze is tested every year before the freezing season (5.3.4). At least 6 spare sprinklers are kept on the premises (5.4.1.6).

A. Scope and general rules

Chapter 5 gives the minimum requirements for routine inspection, testing and maintenance of sprinkler systems installed to NFPA 13, NFPA 13R or another approved installation standard (5.1.1.1). Minimum frequencies come from Table 5.1.1.2 (5.1.1.2).

CheckCriterionClause
☐ Common components and valvesInspected, tested and maintained per Chapter 135.1.2
☐ Internal piping assessment or obstruction investigation neededFollow the procedures of Chapter 145.1.3
☐ Impairment to protectionFollow the impairment procedures of Chapter 155.1.4
☐ Hose connectionsInspected, tested and maintained per Chapters 6 and 135.1.5

B. Frequency summary: Table 5.1.1.2

The standard’s summary table is reproduced below in condensed form. Rows marked "—" have no frequency of their own in the table; the frequency and method come from the chapter in the right-hand column (mostly Chapter 13).

ItemFrequencyReference
Inspection
Assessment of the internal piping condition—Chapter 14
Automatic air vents—Chapter 13
Control valves—Chapter 13
Fire department connections—Chapter 13
Gauges (wet and deluge systems)—Chapter 13
Gauges (dry and preaction systems)—Chapter 13
Hangers, braces and supportsAnnually5.2.3
Heat tracing—5.2.6
Hydraulic design information signAnnually5.2.5
Information signsAnnually5.2.7, 5.2.8
Pipe and fittingsAnnually5.2.2
SprinklersAnnually5.2.1
Sprinklers (electrically operated)Annually5.2.1.5
Sprinklers (spare)Annually5.2.1.4
Sprinkler guardsAnnually5.2.1.1.7
Supervisory signal devices (except valve supervisory switches)—5.2.4, Chapter 13
System valves—Chapter 13
Valve supervisory signal devices—5.2.4, Chapter 13
Waterflow alarm devices—5.2.4, Chapter 13
Test
Antifreeze solutionAnnually5.3.4
Control valves—Chapter 13
Electrically operated sprinklers—5.3.2
Gauges—Chapter 13
Main drain—Chapter 13
Sprinklers (all)At 50 years and every 10 years thereafter5.3.1
Sprinklers (all)At 75 years and every 5 years thereafter5.3.1
Sprinklers (dry)At 20 years and every 10 years thereafter5.3.1
Sprinklers (extra-high or greater temperature solder type)Every 5 years5.3.1
Sprinklers (fast-response, except ESFR and CMSA)At 25 years and every 10 years thereafter5.3.1
Sprinklers (ESFR and CMSA with fast-response elements)At 20 years and every 10 years thereafter5.3.1
Sprinklers (harsh environments)Every 5 years5.3.1
Supervisory signal devices (except valve supervisory switches)—Chapter 13
System valves—Chapter 13
Valve supervisory signal devices—Chapter 13
Waterflow alarm devices—5.3.3, Chapter 13
Maintenance
Low-point drains (dry pipe and preaction systems)—Chapter 13
Sprinklers and automatic spray nozzles protecting commercial cooking equipment and ventilation systemsAnnually5.4.1.8
Replacement of sprinklers—5.4.1.1
Replacement of sprinklers affected by a fire—5.4.1.1
Replacement of threaded sprinklers removed from a fitting for any reason (except dry type)—5.4.1.2
Stock of spare sprinklers—5.4.1.6
Valves (all types)—Chapter 13
Investigation
Obstruction—Chapter 14

C. Annual inspection: sprinklers

Sprinklers are inspected annually from the floor level (5.2.1.1). A sprinkler showing any of the following is replaced (5.2.1.1.1):

CheckCriterionClause
☐ LeakageReplace if present5.2.1.1.1(1)
☐ CorrosionReplace if detrimental to sprinkler performance5.2.1.1.1(2)
☐ Physical damageReplace if present5.2.1.1.1(3)
☐ Glass bulb heat-responsive elementReplace if fluid has been lost5.2.1.1.1(4)
☐ Loading (dust, grease, lint)Replace if detrimental to sprinkler performance5.2.1.1.1(5)
☐ PaintReplace if applied by anyone other than the manufacturer and detrimental to performance5.2.1.1.1(6)
☐ Sprinkler installed in the incorrect orientationCorrect by repositioning the branch line, drop or sprig, or replace the sprinkler5.2.1.1.2
☐ Sprinklers in concealed spaces such as above suspended ceilingsNo inspection required5.2.1.1.3
☐ Sprinklers in areas inaccessible for safety reasons due to process operationsInspected during each scheduled shutdown5.2.1.1.4

Escutcheons and coverplates for recessed, flush and concealed sprinklers

CheckCriterionClause
☐ Escutcheon or coverplate missingReplace with a listed escutcheon or coverplate that is part of the listed sprinkler assembly5.2.1.1.5
☐ Physical damage, or corrosion, loading or field paint detrimental to performanceReplace with a listed escutcheon or coverplate5.2.1.1.5(1)–(4)
☐ Escutcheon or coverplate adhered or attached to the ceiling or wallReplace5.2.1.1.5.1
☐ Required listed escutcheon or coverplate no longer commercially availableReplace the whole sprinkler assembly5.2.1.1.5.2
☐ Escutcheon missing on a pendent sprinkler that is not recessed, flush or concealedReplacement not required5.2.1.1.6

Sprinkler guards and electrically operated sprinklers

CheckCriterionClause
☐ Sprinkler guards (where installed)Inspected annually from the floor level5.2.1.1.7.1
☐ Damaged sprinkler guardReplace with a guard listed for that sprinkler5.2.1.1.7.2
☐ Electrically operated sprinklersInspected annually from the floor level per 5.2.1.1 and the manufacturer’s requirements5.2.1.5

D. Clearance between storage and deflectors

The following minimum clearance is maintained below all sprinkler deflectors (5.2.1.2). This is the most frequent annual finding: racks get taller and piles creep toward the ceiling.

CheckCriterionClause
☐ General caseAt least 18 in. (457 mm) between deflector and top of storage5.2.1.2.1
☐ ESFR and CMSA sprinklersAt least 36 in. (914 mm)5.2.1.2.2
☐ Another standard than NFPA 13 requires a larger clearanceThat value is followed5.2.1.2.3
☐ Rubber tire storageAt least 36 in. (914 mm)5.2.1.2.4
☐ In-rack sprinklersObstruction and storage clearance requirements do not apply5.2.1.2.5
☐ Where the installation standard permitsLess than 18 in. (457 mm) is allowed5.2.1.2.6
☐ Storage violating the clearance rulesCorrected5.2.1.3

E. Pipe, fittings, hangers and supports

CheckCriterionClause
☐ Pipe and fittingsInspected annually from the floor level5.2.2
☐ Condition of pipe and fittingsFree of mechanical damage, leakage and corrosion5.2.2.1
☐ Use of sprinkler pipingNot used to support nonsystem components5.2.2.2
☐ Hangers, braces and supportsInspected annually from the floor level5.2.3
☐ Condition of hangers, braces and supportsNot damaged, loose or unattached5.2.3.1
☐ Damaged, loose or unattached hangers and supportsReplaced or refastened5.2.3.2
☐ Pipe, hangers and supports in concealed spaces such as above suspended ceilingsNo inspection required5.2.2.3, 5.2.3.3
☐ Pipe, hangers and supports in areas inaccessible due to process operationsInspected during each scheduled shutdown5.2.2.4, 5.2.3.4

F. Signs, heat tracing and alarm devices

CheckCriterionClause
☐ Hydraulic design information signAnnually: provided, attached securely to the sprinkler riser and legible5.2.5
☐ Missing or illegible hydraulic design signReplaced5.2.5.1
☐ Pipe schedule systemHydraulic design sign reads “Pipe Schedule System”5.2.5.2
☐ General information sign (where required by NFPA 13)Annually: provided, securely attached and legible5.2.7
☐ General information sign materialPermanently marked weatherproof metal or rigid plastic, secured with corrosion-resistant wire, chain or other acceptable means5.2.7.1
☐ General information sign locationAt each system riser5.2.7.2
☐ System where a general information sign was not required at acceptanceOnly the information sign required by 4.1.10 is inspected annually5.2.7.3
☐ Antifreeze information sign (4.1.11)Annually: provided, securely attached and legible5.2.8
☐ Heat tracingInspected and maintained per the manufacturer’s requirements5.2.6
☐ Waterflow alarm and supervisory signal initiating devicesInspected and tested per Chapter 135.2.4, 5.3.3

G. Sprinkler sample testing: when?

Once sprinklers reach a certain age or condition there are two options: replace them, or send representative samples to an approved testing laboratory for field service testing and retest at set intervals (5.3.1.1).

SprinklersReplace or first testRetestClause
All sprinklersAfter 50 years in serviceEvery 10 years5.3.1.1.1
Sprinklers with fast-response elements (except ESFR and CMSA)After 25 yearsEvery 10 years5.3.1.1.1.1
ESFR and CMSA sprinklers with fast-response elementsAfter 20 yearsEvery 10 years5.3.1.1.1.2
Solder-type, extra-high or greater temperature classification [325 °F (163 °C) and above], exposed to semi-continuous to continuous maximum allowable ambient temperatureAfter 5 yearsEvery 5 years5.3.1.1.1.3
Sprinklers manufactured in 1920 and laterAfter 75 yearsEvery 5 years5.3.1.1.1.4
Dry sprinklersAfter 20 yearsEvery 10 years5.3.1.1.1.5
Sprinklers in dwelling unitsAfter 50 years: replace with fast-response sprinklers, or test samples for thermal sensitivity so that RTI does not exceed 65 (m·s)1/2—5.3.1.1.1.7
Sprinklers exposed to harsh environments, including corrosive atmospheresAfter 5 yearsEvery 5 years5.3.1.1.2
Listed corrosion-resistant sprinklers in harsh environmentsAfter 10 yearsEvery 5 years5.3.1.1.3

Longer intervals are permitted where historical data indicate (5.3.1.1.4). Sprinklers manufactured before 1920 are not tested; they are replaced (5.4.1.1(1)). Concealed sprinklers that fail sample testing have coverplates and sprinklers replaced together as a listed assembly (5.3.1.1.1.6).

H. How is the sample chosen?

CheckCriterionClause
☐ Sample sizeAt least four sprinklers or 1 percent of the sprinklers per sample area, whichever is greater5.3.1.2
☐ RepresentativenessEach sprinkler type and manufacturer in the sample area is represented5.3.1.2.1
☐ Sprinklers replaced at prior testsNot included in the sample5.3.1.2.2
☐ One sprinkler in the sample failsAll sprinklers in the area represented by that sample are replaced5.3.1.3
☐ Electrically operated sprinklersTested per the manufacturer’s requirements; electronic actuation and supervision tested per the manufacturer and NFPA 72 or the local fire alarm code5.3.2.1, 5.3.2.2

I. Antifreeze systems: annual test

Every year, toward the beginning of the heating season and before freezing conditions set in, the antifreeze solution is tested in this order (5.3.4):

  1. The type of antifreeze is determined from the antifreeze information sign (4.1.11), installation and maintenance records, the owner, chemical tests or other reliable sources. If the type is no longer permitted or cannot be reliably determined, the system is drained and refilled with a listed or acceptable solution. If it is not replaced, samples are taken at the top and bottom of each system, plus the most remote portion and the water supply connection where these are not near the top or bottom (5.3.4(1)).
  2. The specific gravity of each sample is checked with a hydrometer with a suitable scale or a refractometer calibrated for that antifreeze (5.3.4(2)).
  3. If any sample is outside the allowable range, the system is drained and refilled with a listed or acceptable solution per 5.3.4.4 (5.3.4(3)).
  4. If a concentration greater than 5.3.4.4 permits was needed to keep the fluid from freezing, alternative methods of preventing pipe freezing are used (5.3.4(4)).
CheckCriterionClause
☐ Test pointsAt the most remote portion and where it interfaces with the wet pipe system5.3.4.1
☐ Antifreeze system larger than 150 gal (568 L)One additional test point for every 100 gal (379 L)5.3.4.2
☐ Incorrect freeze point anywhere in the systemDrain and refill with a listed or acceptable solution5.3.4.2.1
☐ Listed solutionsFollow the manufacturer’s instructions for number of test points and refill procedure5.3.4.2.2
☐ Health regulationsAntifreeze use conforms with state and local health regulations5.3.4.3
☐ Listed CPVC sprinkler pipe and fittingsProtected from freezing with a listed solution or a glycerine solution per 5.3.4.4; diethylene, ethylene and propylene glycols are specifically prohibited5.3.4.3.1, 5.3.4.3.1.1
☐ Type of solutionListed antifreeze solutions in all antifreeze systems, except as permitted by 5.3.4.4.2 and 5.3.4.4.35.3.4.4
☐ Listed solution replacing a nonlisted oneMay be used outside its system volume and hydraulic calculation requirements if temperature range limits are not exceeded; complies with all other requirements5.3.4.4.1, 5.3.4.4.1.1
☐ Existing nonlisted solution remaining in a systemTests at its specified concentration and the premix is limited to 30 percent propylene glycol or 38 percent glycerine by volume5.3.4.4.2
☐ Nonlisted premixed propylene glycol above 30 percent by volumeOnly with ESFR sprinklers listed for such use in a specific application5.3.4.4.3

J. Spare sprinkler cabinet

The cabinet is inspected annually for three things: the correct number and type of sprinklers required by 5.4.1.6, a sprinkler wrench for each type of sprinkler (5.4.1.6.5) and the list of spare sprinklers (5.4.1.6.6) (5.2.1.4).

CheckCriterionClause
☐ Under 300 sprinklers in the facilityNo fewer than 6 spare sprinklers in the cabinet5.4.1.6.4(1)
☐ 300 to 1000 sprinklersNo fewer than 12 spare sprinklers5.4.1.6.4(2)
☐ Over 1000 sprinklersNo fewer than 24 spare sprinklers5.4.1.6.4(3)
☐ Type of sparesCorrespond to the types and temperature ratings of the sprinklers in the property5.4.1.6.1
☐ Cabinet locationTemperature never exceeds the maximum ceiling temperature in Table 5.4.1.6.2 for any sprinkler in the cabinet5.4.1.6.2
☐ Dry sprinklers of different lengthsSpare dry sprinklers not required if a means of returning the system to service is furnished5.4.1.6.3
☐ Sprinkler wrenchOne wrench as specified by the manufacturer for each type of sprinkler installed, kept with the spares5.4.1.6.5
☐ Sprinkler listPosted in the cabinet5.4.1.6.6

The posted list includes at least (5.4.1.6.6.1): the sprinkler identification number (SIN) if equipped, or the manufacturer, model, K-factor, deflector type, thermal sensitivity, pressure rating and temperature rating; the manufacturer’s wrench model number for each sprinkler type; a general description; the quantity of each type installed in the property; the quantity of each type to be kept in the cabinet; and the issue or revision date of the list.

Maximum ceiling temperatureTemperature ratingClassificationColor codeGlass bulb color
Table 5.4.1.6.2
100 °F (38 °C)135–170 °F (57–77 °C)OrdinaryUncolored or blackOrange or red
150 °F (66 °C)175–225 °F (79–107 °C)IntermediateWhiteYellow or green
225 °F (107 °C)250–300 °F (121–149 °C)HighBlueBlue
300 °F (149 °C)325–375 °F (163–191 °C)Extra highRedPurple
375 °F (191 °C)400–475 °F (204–246 °C)Very extra highGreenBlack
475 °F (246 °C)500–575 °F (260–302 °C)Ultra highOrangeBlack
625 °F (329 °C)650 °F (343 °C)Ultra highOrangeBlack

K. Maintenance: replacing sprinklers

CheckCriterionClause
☐ Sprinklers to be replacedManufactured before 1920; showing the signs in 5.2.1.1.1; failing the 5.3.1 test; affected by a fire as determined by the AHJ5.4.1.1
☐ Threaded sprinkler removed from a fitting or welded outletNot reinstalled5.4.1.2
☐ Dry sprinklersMay be reinstalled if removed per the manufacturer’s installation and maintenance instructions5.4.1.2.1
☐ Sprinkler still attached to the original fitting or removable by a grooved connectionMay be reinstalled, taking care it is not damaged5.4.1.2.2
☐ Sprinklers listed for use with a specifically listed fittingMay be reinstalled per the manufacturer’s instructions5.4.1.2.3
☐ Characteristics of the replacementProper for the application: style, orifice size and K-factor, temperature rating, coating if any, deflector type (upright, pendent, sidewall) and design requirements5.4.1.3
☐ Old-style sprinklersMay be replaced with spray sprinklers5.4.1.3.1
☐ Residential sprinklers made before 2003, no longer available (design density below 0.05 gpm/ft² [204 mm/min])A residential sprinkler with an equivalent K-factor (±5 percent or the next larger K-factor), provided the currently listed coverage area is not exceeded5.4.1.3.2
☐ Piers and wharvesReplacement sprinklers comply with NFPA 3075.4.1.3.3
☐ Replacement sprinklersOnly new, listed sprinklers5.4.1.4
☐ Special and quick-response sprinklersReplaced with the same orifice, size, temperature range, thermal response characteristics and K-factor5.4.1.5
☐ AlterationNo alteration, ornamentation, paint or coating after shipment from the factory5.4.1.7
☐ Sprinklers and automatic spray nozzles protecting commercial cooking equipment and ventilating systemsReplaced annually; bulb-type units showing no grease or other buildup at the annual examination need not be replaced5.4.1.8, 5.4.1.8.1
☐ Electrically operated sprinklersMaintained per the manufacturer’s requirements5.4.1.9
☐ Sprinklers in spray areas and mixing rooms of resin application areasKept protected against overspray residue with cellophane bags 0.003 in. (0.076 mm) thick or less or thin paper bags, replaced periodically before heavy deposits accumulate5.4.1.10.1–5.4.1.10.3

L. Dry pipe and marine systems

CheckCriterionClause
☐ Dry pipe systemKept dry at all times5.4.2
☐ Nonfreezing weather, waiting for parts or during repairMay be left wet if the only other option is to take the system out of service5.4.2.1
☐ Refrigerated spaces and other interior areas subject to freezingMay not be left wet5.4.2.2
☐ Air driersMaintained per the manufacturer’s instructions5.4.2.3
☐ Dry pipe system compressorsInspected, tested and maintained per Chapter 13 and the manufacturer’s instructions5.4.2.4
☐ Raw water introduced into a marine system normally kept on fresh waterDrained and refilled, then drained and refilled again with fresh water5.4.4

M. When a component is adjusted, repaired or replaced: Table 5.5.1

Whenever a sprinkler system component is adjusted, repaired, reconditioned or replaced, the actions in Table 5.5.1 are performed (5.5.1). Where the original installation standard differs from the cited one, the appropriate installing standard may be used (5.5.2). These actions do not require a design review, which is outside the scope of the standard (5.5.3).

ComponentAdjustRepair/reconditionReplaceRequired action
Water delivery components
Antifreeze solution——XTest solution to verify it has not been unacceptably diluted; inspect for leaks at system working pressure
Fire department connectionsXXXSee Chapter 13
Pipe and fittings affecting no more than 20 sprinklersXXXInspect for leaks at system working pressure
Pipe and fittings affecting more than 20 sprinklersXXXHydrostatic test in conformance with NFPA 13
Sprinklers, regardless of numberX—XInspect for leaks at system working pressure
Alarm and supervisory components
Detection system for deluge or preaction systemXXXOperational test for conformance with NFPA 13 and/or NFPA 72
High and low air pressure switchXXXOperational test of high and low settings
Pressure switch–type waterflowXXXOperational test using the inspector’s test connection or alarm bypass test valve
Valve supervisory signal initiating deviceXXXTest for conformance with NFPA 13 and/or NFPA 72
Vane-type waterflowXXXOperational test using inspector’s test connection
Water motor gongXXXOperational test using inspector’s test connection
Testing and maintenance components
Air compressorXXXOperational test for conformance with NFPA 13
Automatic air maintenance deviceXXXOperational test for conformance with NFPA 13
Auxiliary drainsXXXInspect for leaks at system working pressure; main drain test
GaugesX—XVerify at 0 bar (0 psi) and system working pressure
Inspector’s test connectionXXXInspect for leaks at system working pressure; main drain test
Main drainXXXMain drain test
Structural components
Hanger/seismic bracingXXXInspect for conformance with NFPA 13
Pipe standsXXXInspect for conformance with NFPA 13
Informational components
Antifreeze information signXXXInspect for conformance with this standard
General information signXXXInspect for conformance with this standard
Hydraulic design information signXXXInspect for conformance with NFPA 13 and this standard
Identification signXXXInspect for conformance with NFPA 13 and this standard
Information signXXXInspect for conformance with this standard

Frequently Asked Questions

How often are sprinklers inspected under NFPA 25?

Annually, from the floor level (5.2.1.1). Sprinklers in concealed spaces such as above suspended ceilings do not require inspection; those in areas inaccessible for safety reasons due to process operations are inspected during each scheduled shutdown (5.2.1.1.3, 5.2.1.1.4).

When must a sprinkler be replaced?

When it shows leakage, physical damage, loss of fluid in the glass bulb, or corrosion, loading or non-factory paint detrimental to performance (5.2.1.1.1); when it was manufactured before 1920, failed a sample test or was affected by a fire as determined by the AHJ (5.4.1.1). A threaded sprinkler that has been removed is not reinstalled (5.4.1.2).

How much clearance is needed between storage and sprinklers?

Generally at least 18 in. (457 mm) between the deflector and the top of storage; at least 36 in. (914 mm) for ESFR and CMSA sprinklers and for rubber tire storage (5.2.1.2.1, 5.2.1.2.2, 5.2.1.2.4). In-rack sprinklers are exempt (5.2.1.2.5).

At what age are sprinklers tested or replaced?

The general rule is 50 years, then every 10 years (5.3.1.1.1). Fast-response sprinklers at 25 years, ESFR/CMSA with fast-response elements and dry sprinklers at 20 years, harsh environments and extra-high temperature solder-type sprinklers under continuous maximum ambient at 5 years. The sample is at least 4 sprinklers or 1 percent; if one fails, the whole represented area is replaced (5.3.1.2, 5.3.1.3).

How many spare sprinklers must be kept?

At least 6 for facilities with under 300 sprinklers, 12 for 300 to 1000, and 24 for over 1000 (5.4.1.6.4). The cabinet also holds a sprinkler wrench for each type and the sprinkler list, and is inspected annually (5.4.1.6.5, 5.4.1.6.6, 5.2.1.4).

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.