Under NFPA 13-2025 Table 19.2.3.1.1 the design density for Ordinary Hazard Group 1 (OH1) is 6.1 mm/min over 140 m² (0.15 gpm/ft² over 1,500 ft²); next to unsprinklered combustible concealed spaces 4.9 mm/min over 280 m² (0.12 gpm/ft² over 3,000 ft²) applies. Hose allowance is 950 L/min (250 gpm) and water supply duration is 60 or 90 minutes (Table 19.2.3.1.2).

Definition

Ordinary Hazard Group 1 describes contents of low combustibility present in moderate quantity. Stockpiles of low-combustibility contents do not exceed 8 ft (about 2.4 m). Production and service areas handling low-combustibility goods typically fall here.

Design parameters

ParameterSIUS units
Density (standard design)6.1 mm/min0.15 gpm/ft²
Design area (standard)140 m²1,500 ft²
Density (concealed space rule, 19.2.3.1.5)4.9 mm/min0.12 gpm/ft²
Design area (concealed space rule)280 m²3,000 ft²
Theoretical sprinkler flow (standard / concealed space)854 / 1,372 L/min225 / 360 gpm
Hose allowance (inside + outside)950 L/min250 gpm
Inside hose (part of the total)0, 190 or 380 L/min0, 50 or 100 gpm
Water supply duration60 or 90 min60 or 90 min
Maximum area per sprinkler (standard spray, Table 10.2.4.2.1(b))12 m²130 ft²
Maximum distance between sprinklers4.6 m15 ft

Theoretical flow is simply density × area. Actual system demand is higher because of hydraulic imbalance and the minimum sprinkler pressure (7 psi (0.5 bar), 28.2.4.11.1). Coverage and spacing values are for standard spray sprinklers; for ordinary hazard this limit applies regardless of construction type; smaller values apply in storage areas.

Typical occupancies

Examples from NFPA 13-2025 A.4.3.3.1; automobile parking garages are not on this list but on the OH2 list (A.4.3.3.2).

  • Automobile showrooms
  • Porte cocheres
  • Electric fire pump rooms
  • Bakeries
  • Beverage manufacturing and canneries
  • Dairy product manufacturing
  • Electronics assembly plants
  • Glass and glass product manufacturing
  • Laundries
  • Restaurant service areas
  • Plant rooms

How the design area is set

NFPA 13-2025 no longer has the density/area curve of earlier editions. Table 19.2.3.1.1 gives a single design point for each class: 6.1 mm/min over 140 m² for OH1. The second column, 4.9 mm/min over 280 m², applies only to the systems or portions of systems adjacent to unsprinklered combustible concealed spaces (19.2.3.1.5); the concealed spaces listed in 19.2.3.1.5.2 are exempt. Where an area of operation smaller than 140 m² is used, the density for 140 m² still applies (19.2.3.1.4). The density must be delivered over the whole hydraulically most remote area.

For dry pipe and double interlock pre-action systems the area of operation is increased by 30% without revising the density (19.2.3.2.6). Ceilings sloping more than 2 in 12 usually need a 30% increase as well (19.2.3.2.4). Where several adjustments apply they are compounded on the area first taken from Table 19.2.3.1.1, and the concealed space rule is applied last (19.2.3.2.8).

With listed quick-response sprinklers throughout a wet system, or a portion with the same hydraulic design basis, and a ceiling no higher than 20 ft (6.1 m), the area of operation may be reduced without revising the density: by 40% for ceilings of 10 ft (3 m) or less and by 25% at 20 ft (6.1 m), linear in between (Figure 19.2.3.2.3.1). Unprotected ceiling pockets must not exceed 32 ft² (3.0 m²), there must be no unprotected areas above cloud ceilings, and the design area must always contain at least five sprinklers (19.2.3.2.3). Where OH1 ceilings exceed 30 ft (9.1 m) the area of operation is increased by 30% (19.2.3.2.5.2(A)) and sidewall sprinklers may not be used (19.2.3.2.5.1).

The inside hose allowance (0, 50 or 100 gpm) is part of the total above. The lower duration value is accepted where the waterflow alarm and supervisory devices are electrically supervised and monitored at an approved, constantly attended location (19.2.3.1.3).

Comparison with EN 12845

The closest EN 12845 matches are OH1 and OH2 (5.0 mm/min; 72 m² and 144 m²; 60 minutes). The NFPA OH1 value in Table 19.2.3.1.1, 6.1 mm/min over 140 m², is slightly higher in density and considerably larger in area. There is no one-to-one mapping, and the example occupancy lists differ between the two standards.

The class comes from how the space is actually used. A project title or the occupancy on a permit is not enough; contents, stack height and flammable liquids are checked on site and the class is recorded with a written justification. For a quick first pass, use the NFPA 13 hazard classification tool.

Checklist

  1. Is the activity and type of contents recorded in writing?
  2. Are stack heights within the class definition; if not, have storage criteria been checked?
  3. Is the system type (wet/dry/pre-action) reflected in the area adjustment?
  4. Are hose allowance and duration included in the tank volume?
  5. Are areas of different classes in the same building calculated separately?

Frequently Asked Questions

What is the minimum water demand for NFPA 13 OH1?

In theory, at the standard design point 854 L/min (225 gpm) of sprinkler flow plus 950 L/min (250 gpm) of hose allowance, multiplied by 60 or 90 minutes. The real figure comes from the hydraulic calculation and is usually higher; the fire water tank sizing calculator helps with the volume.

What hazard class is an enclosed car park under NFPA 13?

In NFPA 13-2025 automobile parking garages are an OH2 example (A.4.3.3.2), while automobile showrooms are OH1 (A.4.3.3.1). If a dry system is chosen because of freezing risk, the design area is increased by 30% (19.2.3.2.6).

What is the difference between OH1 and OH2?

In OH1 the contents have low combustibility and stockpiles stay below 8 ft. In OH2 quantity and combustibility are moderate to high, and the stockpile limit is 8 or 12 ft depending on heat release.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

NFPA 13, Standard for the Installation of Sprinkler Systems (2025 edition): 4.3, Table 10.2.4.2.1, 19.2.3, A.4.3 · BS EN 12845+A2:2026 (EN 12845:2015+A2:2026). Values are for information; the binding text is the edition in force and the decision of the authority having jurisdiction.