Source: BS EN 12845+A2:2026, Annex H (normative) "Sprinkler systems monitoring", H.1 and H.2.1-H.2.5 (EN p.153), H.2.6 and H.2.7 (EN p.154).
Annex H consists of two main clauses: H.1 General and H.2 Functions to be monitored. There are six sub-headings under H.2 (seven including H.2.1 General). The whole annex runs to two pages; there is no clause H.3 or H.4.
H.1 General
Clause H.1 (EN p.153): the aim of monitoring sprinkler systems is to ensure the continuous operability of the main functions of the system, that is, those whose failure might impair the correct automatic operation of the system in case of fire, and to raise a supervisory alarm so that corrective measures can be taken. This annex specifies requirements that are additional to those elsewhere in the standard.
The numerical provisions of Clause H.1:
| Subject | Provision |
|---|---|
| Degree of protection of monitoring devices | At least IP 54 in accordance with EN 60529 |
| Number of non-addressable supervisory alarm devices that may be connected to a common indication | No more than 15 |
| Signalling and alarm circuits | Must be fully supervised; a short or open circuit that amounts to a fault must raise a fault alarm |
| Control and indicating equipment | Must comply with whatever provisions apply in the country of use |
Source: Clause H.1, EN p.153.
H.2 Functions to be monitored
Clause H.2.1 (EN p.153): the functions below must be monitored on top of every monitoring requirement given elsewhere in the standard (see Annex I).
H.2.2 Stop valves controlling water flow to sprinklers
Clause H.2.2 (EN p.153): the position of all stop valves whose closing could prevent adequate water flowing to the sprinklers shall be monitored, including water supply valves, control valve sets, subsidiary valves and sectional valves.
For a valve that is normally open, the alarm must be triggered as soon as the valve begins to close.
H.2.3 Other stop valves
Clause H.2.3 (EN p.153): the position of all stop valves whose closing could prevent the correct operation of an alarm or indicating device shall be monitored; the examples given are the pressure switch, the hydraulic alarm and the flow switch.
Here too, a normally open valve must trigger the alarm as soon as it begins to close.
H.2.4 Liquid levels
Clause H.2.4 (EN p.153): all critical liquid levels, including water storage tanks and engine fuel tanks, shall be monitored.
| Case | Indication threshold |
|---|---|
| Water storage level | An indication is given before the level drops more than 10% below its nominal fill level |
| Fuel level | An indication is given before the level drops more than 25% below its nominal fill level |
| Pressure tanks | A further indication is given before the level reaches 10% above its nominal fill level |
Source: Clause H.2.4, EN p.153.
H.2.5 Pressures
Clause H.2.5 (EN p.153): pressures shall be monitored, including at water supplies and downstream of all dry and alternate control valve sets.
| Type of supply | Indication threshold |
|---|---|
| Town main supplies | An indication is given if the static pressure drops below the calculated running pressure |
| All other cases | An indication is given if the static pressure drops by more than 20% below the tested level |
Source: Clause H.2.5, EN p.153.
The related provision for the town main is also found in Clause 9.2 (EN p.46): a pressure switch shall be installed on the town main and shall give an alarm when the supply pressure falls to a predetermined value; the switch is located upstream of the non-return valve and is fitted with a test valve (see Annex I and H.2.5).
H.2.6 Electrical power
Clause H.2.6 (EN p.154): the power supply to electrical pump sets or other critical electrical equipment shall be monitored. An indication shall be given if one or more phases fail at any point in the main supply, in the control circuit, in an electric or diesel pump set controller or in any other critical control equipment.
H.2.7 Temperature
Clause H.2.7 (EN p.154): the minimum temperature of the sprinkler valve room and the pump room shall be monitored. An indication shall be given if the temperature drops below the minimum required level.
The minimum required level is given in Clause 10.3.3 (EN p.58): the pump set compartment shall be maintained at or above 4 °C for electric driven pump sets and 10 °C for diesel driven pump sets. In addition, Clause 8.1.3 (EN p.42) requires the feed pipe and the control valve set to be maintained at a minimum temperature of 4 °C.
Alarm type of Annex H signals
The signals of systems monitored under Annex H are listed in Annex I Table I.1 (EN p.156) under the heading "Monitored sprinkler systems - Annex H", and all of them are Type B (fault / technical) alarms:
| Signal | Alarm type |
|---|---|
| Stop valve partially closed | Type B |
| Liquid levels | Type B |
| Low pressure | Type B |
| Power failure | Type B |
| Low pump room temperature | Type B |
Source: Table I.1, EN p.156.
Subjects not covered by Annex H
- Pump running, demand, start failure, common fault and automatic mode off signals. These are in Clause 10.8.5.1 (EN p.65), Clause 10.9.2 (EN p.66) and Annex I Table I.1 (EN p.155).
- Monitoring of detection triggering in pre-action systems. Annex H does not cover it; pre-action systems appear in Table I.1 as "low pressure, pre-action Type A system, Clause 11.4.1.2" and "low pressure, dry pipe and pre-action systems, Clause 16.2.3" (both Type B) (EN p.155).
- The position of the drain valve. H.2.3 covers only those valves whose closing could prevent the operation of an alarm or indicating device.
- Tank water temperature or freezing monitoring. H.2.7 covers only the minimum temperature of the valve room and the pump room.
- Alarm panel colour coding, event log duration, alarm transmission time, signal delay or hysteresis values. The coloured indication rule exists only for zoned installations, in Clause D.3.7 (EN p.137): green visual indication for the correct position, amber for a fault, red for water flow.
- Monitoring "levels" or response times.
Field note
Field note (engineering interpretation, not from the standard): the limit on the number of non-addressable devices that may be connected to a common indication and the requirement that circuits be fully supervised constrain the field wiring just as much as the panel itself. In valve monitoring, the wording "once the valve starts to close" means that an arrangement which only signals in the fully closed position is not sufficient.
Frequently Asked Questions
Which functions does Annex H require to be monitored?
BS EN 12845+A2:2026 Clause H.2 (EN p.153-154) lists six headings: H.2.2 stop valves controlling water flow to sprinklers; H.2.3 other stop valves whose closing could prevent the correct operation of an alarm or indicating device; H.2.4 liquid levels; H.2.5 pressures; H.2.6 electrical power; H.2.7 temperature. These are additional to the monitoring requirements specified elsewhere in the standard.
What degree of protection is required for monitoring devices?
Clause H.1 (EN p.153): all devices used for monitoring shall have at least IP 54 protection as specified in EN 60529. In addition, no more than 15 non-addressable supervisory alarm devices may be connected to a common indication.
What are the thresholds for water and fuel levels?
Clause H.2.4 (EN p.153): an indication must be raised before the stored water level falls more than 10% under its nominal fill level, and before the fuel level falls more than 25% under its nominal fill level. For pressure tanks a second indication must be raised before the level climbs to 10% over its nominal fill level.
What is the pressure monitoring threshold?
Clause H.2.5 (EN p.153): for a town main supply, an indication must be raised when the static pressure falls under the calculated running pressure; for every other supply, when the static pressure falls by more than 20% under the tested level. The monitored pressures include those at the water supplies and downstream of every dry and alternate control valve set.
Are pump running and fault signals covered by Annex H?
No. Annex H lists six functional headings; pump set demand, running, start failure and common fault signals are dealt with in Clause 10.8.5.1 and 10.9.2 and in Annex I Table I.1 (EN p.65, 66 and 155).
What does temperature monitoring cover?
Clause H.2.7 (EN p.154): the minimum temperature of the sprinkler valve room and the pump room is monitored; an indication shall be given if the temperature drops below the minimum required level. The minimum required level is given in Clause 10.3.3 (EN p.58): 4 °C for electric pump sets and 10 °C for diesel pump sets.
References
- BS EN 12845+A2:2026 Clause H.1, H.2.1, H.2.2, H.2.3, H.2.4, H.2.5 (EN p.153)
- BS EN 12845+A2:2026 Clause H.2.6, H.2.7 (EN p.154)
- BS EN 12845+A2:2026 Table I.1 (EN p.155-156)
- BS EN 12845+A2:2026 Clause 9.2 (EN p.46)
- BS EN 12845+A2:2026 Clause 10.3.3 (EN p.58)
- BS EN 12845+A2:2026 Clause 10.8.5.1 (EN p.65)
- BS EN 12845+A2:2026 Clause 10.9.2 (EN p.66)
- BS EN 12845+A2:2026 Clause 11.4.1.2 (EN p.68)
- BS EN 12845+A2:2026 Clause D.3.7 (EN p.137)
- BS EN 12845+A2:2026 Clause 8.1.3 (EN p.42)

SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.
Download SprinkCalc on the App Store
MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App StoreBS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; BS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.