Source: BS EN 12845+A2:2026, Annex I (normative) "Transmission of alarms", I.1 and Table I.1 (EN p.155), continuation of Table I.1 and I.2 (EN p.156).
Annex I consists of two clauses: I.1 Functions to be monitored and I.2 Alarm levels. Table I.1 in between shows which clause each alarm in the standard comes from and which type it is.
It is worth starting with an important conceptual correction: A and B are alarm types, not transmission levels. The standard does not define a transmission tier such as "direct to fire brigade" or "local only".
I.1 Functions to be monitored
Clause I.1 (EN p.155):
- Every alarm the standard specifies must be wired to an alarm panel located in the sprinkler control room or the pump room and passed on further according to how important the alarm is.
- Alarms must reach a location that is permanently attended, whether on the premises or elsewhere.
- B-Type Alarms (Technical Alarms) may also be sent to a responsible person, in a way that allows corrective action to be taken at once (see Clause 20.1).
- Where the system has a direct link to the fire brigade, the procedure for transmitting alarms should be agreed with the authorities.
Table I.1: Type of alarm for transmission
| Signal | Source clause | Type |
|---|---|---|
| Water flow alarm | 16.1.1 | A |
| Town main: low pressure | 9.2 | B |
| Pump room: water flow detector | 10.3.2 | A |
| Priming tank: low level | 10.6.2.4 | B |
| Electric pump set: on demand | 10.8.5.1 | B |
| Electric pump set: start failure | 10.8.5.1 | B |
| Electric pump set: running | 10.8.5.1 | A |
| Electric pump set: power not available | 10.8.5.1 | B |
| Diesel pump set: automatic mode off | 10.9.2 | B |
| Diesel pump set: start failure | 10.9.2 | B |
| Diesel pump set: running | 10.9.2 | A |
| Diesel pump set: common fault | 10.9.2 | B |
| Trace heating (electrical heating trace) circuits | 11.1.2.3 | B |
| Low pressure: pre-action Type A system | 11.4.1.2 | B |
| Low pressure: dry pipe and pre-action systems | 16.2.3 | B |
Source: Table I.1, EN p.155.
Continuation of the table (EN p.156):
| Alarm | Clause | Alarm type |
|---|---|---|
| Zoned systems: open control valve | D.3.7 | B |
| Zoned systems: partially closed control valve | D.3.7 | B |
| Zoned systems: partially open subsidiary valve | D.3.7 | B |
| Zoned systems: low mains pressure | D.3.7 | B |
| Zoned systems: water flow in installation | D.3.7 | A |
| Zoned systems: water flow in zone | D.3.7 | A |
| Monitored sprinkler systems: partially closed stop valves | Annex H | B |
| Monitored sprinkler systems: liquid levels | Annex H | B |
| Monitored sprinkler systems: low pressure | Annex H | B |
| Monitored sprinkler systems: power failure | Annex H | B |
| Monitored sprinkler systems: low temperature in pump room | Annex H | B |
Source: continuation of Table I.1, EN p.156.
The way to read the table comes down to a simple rule: everything related to water flow is Type A, everything related to technical status and faults is Type B.
I.2 Alarm levels
Clause I.2 (EN p.156):
- Signals coming from water flow alarms and/or alarm valves must be displayed as fire alarms (Alarm level A in Table I.1).
- Depending on local conditions, the signal that the sprinkler pump set is running may instead be handled as a trouble alarm.
- Technical faults, a power failure being one example, that could keep the system from operating correctly in a fire must be displayed as trouble alarms (Alarm level B in Table I.1).
Other clauses related to Annex I
| Subject | Provision | Source |
|---|---|---|
| Checkability of the transmission equipment | It must be possible to check it both for continuity of the connection and for continuity of the link between the alarm switch and the control unit | Clause 16.3, EN p.111 |
| Direct connection to the fire brigade | The testing procedure should be agreed with the authorities in order to avoid false calls | Clause 16.3, EN p.111 |
| Electric pump indications | Each monitored condition must have its own visual indication in the pump room; in addition, pump running and a fault alarm must be shown both audibly and visually at a location where responsible personnel are permanently present | Clause 10.8.5.2, EN p.65 |
| Diesel pump indications | Pump running, start failure, common faults and automatic mode off shall be indicated both locally and at a responsibly manned location by warning lights | Clause 10.9.2, EN p.66 |
| Colour at the zoned installation panel | Green: each monitored stop valve is in its correct position; amber: a control valve set or subsidiary valve is not fully open, or the static pressure in the trunk main has fallen 0.5 bar or more below normal; red: water is flowing into the installation or into a zone | Clause D.3.7, EN p.137 |
| Silencing of alarms | Facilities shall be provided at the panel for silencing the audible alarms, but the visual indicators continue to operate until the system is restored to the normal standby condition | Clause D.3.7, EN p.137 |
Subjects not covered by Annex I
- Any alarm category called "Type C", or a local-only alarm option.
- Response time (for example 5-15 min, 10-30 min).
- Polling interval, alarm transmission time, changeover time to a standby line.
- A table of transmission line types (PSTN, IP, GSM, radio, satellite).
- "Transmission line fault" and "system test" signals. These two items do not appear in Table I.1.
- The certification standard for the alarm receiving centre. This is outside the scope of EN 12845.
Field note
Field note (engineering interpretation, not from the standard): the A/B distinction is more than a priority label, it determines how the panel and the transmission side are separated; routing Type A signals through the same channel as the Type B fault stream causes a genuine fire signal to be lost in the noise of technical faults. Using Table I.1 verbatim as the signal list for a project largely prevents this confusion.
Frequently Asked Questions
How many alarm levels does EN 12845 Annex I define?
Two. Under BS EN 12845+A2:2026 Clause I.2 (EN p.156), a signal from a water flow alarm and/or an alarm valve must be displayed as a fire alarm (Alarm level A in Table I.1), while a technical fault that could stop the system from working properly in a fire, a power failure for instance, must be displayed as a trouble alarm (Alarm level B). There is no third level and no 'Type C'.
Where are the alarms transmitted to?
Clause I.1 (EN p.155): alarms must be wired to an alarm panel in the sprinkler control room or the pump room and passed on according to their importance, and they must reach a permanently attended location, either on the premises or elsewhere. B-Type Alarms (Technical Alarms) may also be sent to a responsible person in a way that allows corrective action to be taken at once.
What type is the pump running signal?
Table I.1 (EN p.155) lists the 'running' signal for electric and diesel pump sets as Type A. Clause I.2 (EN p.156) allows one flexibility: depending on local conditions, the pump-running signal may instead be handled as a trouble alarm.
Which signals does Table I.1 list?
Type A signals: the water flow alarm (16.1.1), the pump room water flow detector (10.3.2), and the running signal of electric (10.8.5.1) and diesel (10.9.2) pump sets. Type B signals: town main low pressure (9.2); priming tank low level (10.6.2.4); electric pump set on demand, start failure and power not available (10.8.5.1); diesel pump set automatic mode off, start failure and common fault (10.9.2); trace heating circuits (11.1.2.3); and low pressure in a pre-action Type A system (11.4.1.2) or in dry pipe and pre-action systems (16.2.3). The table also covers zoned systems (D.3.7) and monitored sprinkler systems (Annex H).
What applies if there is a direct connection to the fire brigade?
Clause I.1 (EN p.155): where there is a direct link to the fire brigade, the procedure for transmitting alarms should be agreed with the authorities. Clause 16.3 (EN p.111) also requires that the transmission equipment can be checked both for continuity of the connection and for continuity of the link between the alarm switch and the control unit.
References
- BS EN 12845+A2:2026 Clause I.1 and Table I.1 (EN p.155)
- BS EN 12845+A2:2026 continuation of Table I.1 and Clause I.2 (EN p.156)
- BS EN 12845+A2:2026 Clause 16.3 (EN p.111)
- BS EN 12845+A2:2026 Clause 10.8.5.1 and 10.8.5.2 (EN p.65)
- BS EN 12845+A2:2026 Clause 10.9.2 (EN p.66)
- BS EN 12845+A2:2026 Clause D.3.7 (EN p.137)
- BS EN 12845+A2:2026 Annex H (EN p.153-154)
- BS EN 12845+A2:2026 Clause 20.1 (EN p.118)

SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.
Download SprinkCalc on the App Store
MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App StoreBS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; BS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.