Short answer: BS EN 12845+A2:2026 Clause J.1 (EN p.157) does not give a numbered procedure but a 10-item list of measures from a) to j): the authorities and any central monitoring station are informed; alterations and repairs are carried out during normal working hours; supervisory staff in the areas affected are notified and the area is patrolled continuously; any hot work is subject to a permit system; outside working hours all fire doors and fire shutters remain closed; fire extinguishing appliances are kept ready with trained personnel; the parts not being worked on are kept operative by blanking off pipework; machinery is stopped for extensive work; any pump set out of commission is isolated; blinders and blanks are marked with numbered and logged indicator tags.

Source: BS EN 12845+A2:2026, Annex J (informative) "Precautions and procedures when a system is not fully operational", J.1 and J.2 (EN p.157), the continuation of J.2, J.3, J.4.1 and J.4.2 (EN p.158).

Annex J is informative, which is why its provisions are written in the "should" form (recommended). The annex consists of four clauses: J.1 Minimizing the effects, J.2 Planned shut-down, J.3 Unplanned shut-down, J.4 Action following sprinkler operation. Clause 20.1.3 (EN p.118) points directly to Annex J for the precautions to be taken during maintenance.

J.1 Minimizing the effects

The opening of Clause J.1 (EN p.157) sets the overall aim: any maintenance, alteration or repair work on a system that is not fully operational should be organized so that both the duration and the extent of the outage are kept to a minimum.

For the period an installation is out of action, the clause lists the measures the user should take (10 items, a) to j)):

Item Measure
a) The authorities and any central monitoring station should be notified
b) Alteration and repair work on the installation or its water supply should take place within normal working hours (not required where Annex F has been applied)
c) Supervisors responsible for the affected areas should be told, and those areas should be under continuous patrol
d) Hot work of any kind should be allowed only under a permit system. While the work is in progress, smoking and naked lights should be banned in the affected areas
e) If the installation is still out of action after working hours, every fire door and fire shutter should be kept closed
f) Fire extinguishing appliances should be ready for use, and trained people should be on hand to operate them
g) The largest practicable part of the installation should stay in service, by blanking off the pipework that supplies the section or sections being worked on
h) On manufacturing premises, every effort should be made to do the work with the machinery stopped if the alterations or repairs are extensive, if a pipe of more than 40 mm nominal diameter has to be disconnected, or if a main stop valve, alarm valve or non-return valve has to be overhauled or removed
i) A pump set that is out of service should be isolated with the valves fitted for it
j) Where it can be done, sections of the installation should be put back into service overnight so that some protection remains, using blinders and blanks inside the pipework; each blinder and blank should carry a visible indicator tag that is numbered and recorded in a log, to help make sure they are removed in good time

Source: Clause J.1 a)-j), EN p.157.

Annex F, referred to in Clause J.1 b) (normative, EN p.143-144), sets out additional measures that increase the reliability and availability of the system. Clause F.8 (EN p.144) gives additional precautions for maintenance: only one zone of a multi-zone installation is shut down at a time; an installation or zone is shut down for the minimum time necessary for maintenance; partial or complete shut-down is avoided wherever possible and only the smallest part of the installation necessary is isolated.

J.2 Planned shut-down

Clause J.2 (EN p.157-158):

  • Apart from emergencies, permission to shut down a sprinkler installation or zone should come from the user alone.
  • Before any full or partial shut-down, the whole of the premises should be inspected to confirm there is no sign of fire.
  • If the premises are divided into separate occupancies (buildings in communication or at risk) that share sprinkler systems or installations, every occupier should be told that the water is going to be turned off.
  • Particular attention should be given to situations where the installation pipework passes through walls or ceilings and could from there feed sprinklers in areas needing special consideration.

J.3 Unplanned shut-down

Clause J.3 (EN p.158): if an installation goes out of action urgently or by accident, the J.1 precautions should be applied to the extent they are relevant, and without any avoidable delay. The authorities concerned should also be told at the earliest possible moment.

J.4 Action following sprinkler operation

J.4.1 General

Clause J.4.1 (EN p.158):

  • Once the installation has been shut down after operating, each sprinkler that opened should be replaced with one of the correct type and temperature rating, and the water supply should be restored.
  • Sprinklers that did not open, in and around the operating area, should be inspected for heat or other damage and replaced where needed.
  • Water to an installation, or to a zone of it, that has operated should stay on until the fire is completely out.
  • Only the fire service should decide to shut down an installation or zone that has operated in a fire.
  • Any components taken out of the system should be kept by the user so that an authority can examine them.

Clause 20.1.4 (EN p.118-119) gives numbers for the stock of spare sprinklers: per system, at least 6 for LH, 24 for OH and 36 for HHP and HHS; the stock is to be replenished promptly after spares are used, and the spares cabinet is to be in a prominent and easily accessible position where the ambient temperature does not exceed 27 °C.

J.4.2 Installations protecting cold storage warehouses

Clause J.4.2 (EN p.158) is a single sentence: "The installation should be dismantled for drying out after each operation" (for cold storage warehouses with air circulation refrigeration).

What the standard does not say in Annex J

  • A numbered eight-step procedure. J.1 is a 10-item list of measures from a) to j).
  • A colour-coded ("yellow / red / green") out-of-service tag system. J.1 j) only recommends that blinders and blanks be fitted with numbered, logged, visible indicator tags.
  • A time interval for patrols. J.1 c) says "continuously".
  • An outright ban on hot work. J.1 d) requires a permit system; only smoking and naked lights are prohibited.
  • A limit on fire watch duty time, a monitoring period after hot work, or a radius of the area to be cleared.
  • A requirement to call the insurer within a given time. J.1 a) gives no time limit.
  • A record retention period.
  • An itemized checklist for returning the system to service. J.4 contains no such list.

Field note

Field note (this is engineering interpretation, not part of the standard): the fact that Annex J is informative does not mean it will not be applied on site; Clause 20.1.3 in the normative body only refers the reader to Annex J. In practice the two items with the greatest effect are carrying out the work during normal working hours and keeping as much of the installation as possible operative by blanking off; both reduce the area shut down rather than the duration of the shut-down.

Frequently Asked Questions

What precautions are taken when a sprinkler installation is out of service?

BS EN 12845+A2:2026 Clause J.1 (EN p.157) does not give a numbered procedure but a 10-item list of measures from a) to j): the authorities and any central monitoring station are informed; alterations and repairs are carried out during normal working hours; supervisory staff in the areas affected are notified and the area is patrolled continuously; any hot work is subject to a permit system; outside working hours all fire doors and fire shutters remain closed; fire extinguishing appliances are kept ready with trained personnel; the parts not being worked on are kept operative by blanking off pipework; machinery is stopped for extensive work; any pump set out of commission is isolated; blinders and blanks are marked with numbered and logged indicator tags.

How often is the affected area patrolled while out of service?

Clause J.1 c) (EN p.157) gives no interval: supervisory staff in the areas affected should be notified and the area should be patrolled continuously.

Is hot work prohibited while the system is shut down?

Clause J.1 d) (EN p.157): any hot work should be subject to a permit system. Smoking and naked lights, on the other hand, should be prohibited in the affected areas during the progress of the work.

Who gives permission to shut down an installation?

Clause J.2 (EN p.157): except in an emergency, permission to shut down a sprinkler installation or zone should come from the user alone. Before any full or partial shut-down, the whole of the premises should be inspected to confirm there is no sign of fire.

When is the water shut off after a sprinkler has operated?

Clause J.4.1 (EN p.158): water to an installation, or to a zone of it, that has operated should stay on until the fire is completely out, and only the fire service should decide to shut down an installation or zone that has operated because of a fire.

Is there an extra rule for cold storage warehouse installations?

Clause J.4.2 (EN p.158): installations protecting cold storage warehouses (air circulation refrigeration) should be dismantled for drying out after each operation.

References

  • BS EN 12845+A2:2026 Clause J.1 a)-j) and J.2 (EN p.157)
  • BS EN 12845+A2:2026 Clause J.2 continued, J.3, J.4.1, J.4.2 (EN p.158)
  • BS EN 12845+A2:2026 Clause F.8 (EN p.144)
  • BS EN 12845+A2:2026 Clauses 20.1.3 and 20.1.4 (EN p.118-119)

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 110+ Engineering Calculators

MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

BS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; BS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.