In BS EN 12845+A2:2026 the valves are gathered in Clause 15 (TS p.110-113 / EN p.107-110): the control valve set, stop valves, ring main valves, drain valves, test valves, flushing connections and pressure gauges. This article gives all the subclauses, the related definitions (Clause 3) and the monitoring provisions (Annex H), each with its source.
Definitions: control valve set and alarm valve types
Clause 3.17 control valve set (TS p.20 / EN p.17): the assembly comprising an alarm valve, a stop valve and all associated valves and fittings for the control of a sprinkler installation.
The alarm valve types are at the start of Clause 3 (TS p.19 / EN p.16) and the numbers are often confused:
| Clause | Term | Definition |
|---|---|---|
| 3.5 | alarm valve, alternate | Can serve a wet, a dry or an alternate installation |
| 3.6 | alarm valve, dry | Serves a dry installation, and/or is combined with a wet alarm valve to form an alternate installation |
| 3.7 | alarm valve, pre-action | Serves a pre-action installation |
| 3.8 | alarm valve, wet | Serves a wet installation |
The clauses that follow immediately are not alarm valve definitions: 3.9 is "area of operation", 3.10 "hydraulically most favourable area of operation" and 3.11 "hydraulically most unfavourable area of operation".
The gauge definitions are on the same page: 3.14 'B' gauge, a pressure gauge connected to and at the same level as the alarm valve, indicating the pressure on the upstream side of the valve; 3.16 'C' gauge, connected in the same way and indicating the pressure on the downstream side.
15.1 and 15.2: Control valve set and stop valves
Clause 15.1 (TS p.110 / EN p.107): Each installation shall have a control valve set in accordance with EN 12259-2 or EN 12259-3.
Clause 15.2 Stop valves (TS p.110 / EN p.107): every stop valve whose closure could interrupt the water supply to the sprinklers must meet three conditions:
- it must close when turned clockwise;
- it must carry an indicator that shows clearly whether it is open or closed;
- it must be locked in its correct position with a strap and padlock, or by an equivalent means.
The same clause continues: apart from the cases the standard itself provides for, stop valves must not be fitted downstream of the control valve set. To make testing and maintenance easier, a stop valve may be added downstream of the control valve, but only if it is monitored.
15.3: Ring main valves
Clause 15.3 (TS p.110 / EN p.107): when the sprinkler systems on a site are supplied from a ring main, stop valves must be fitted that divide the ring into isolatable sections, and each section may contain at most 4 control valve sets.
15.4 and Table 39: Drain valves
Clause 15.4 (TS p.110 / EN p.107): drain valves, sized to Table 39, must be provided so that the pipework can be emptied at these points:
- a) just after the control valve set, or just after its downstream stop valve where one exists;
- b) just after every subsidiary alarm valve;
- c) just after every subsidiary stop valve;
- d) between a dry pipe or subsidiary control valve set and a subsidiary stop valve provided for testing;
- e) on any pipe that no other drain valve can empty, drop pipes to single sprinklers in a wet installation excepted.
Further rules (TS p.111 / EN p.108): each valve must sit at the lowest point of the pipework it drains, with its size taken from Table 39. The outlet must be at most 3 m above floor level and must be closed with a suitable plug.
Table 39: Minimum size of drain valves
| What the valve mainly drains | Smallest valve and pipe diameter, mm |
|---|---|
| A whole LH installation | 40 |
| A whole OH, HHP or HHS installation | 50 |
| A subsidiary installation | 50 |
| One zone | 50 |
| Trapped distribution pipe up to 80 mm diameter | 25 |
| Trapped distribution pipe over 80 mm diameter | 40 |
| Trapped range pipe | 25 |
| Trapped section between a dry or subsidiary alarm valve and a subsidiary stop valve fitted for testing | 15 |
15.5: Test valves
Clause 15.5.1 Alarm and pump set start test valves (TS p.111 / EN p.108): 15 mm test valves must be provided, where relevant, so that the following can be tested:
- a) the hydraulic alarm and any electric alarm pressure switch, with water taken directly on the downstream side of a wet alarm valve (and of any main stop valves after it) or of an alternate alarm valve;
- b) the same hydraulic alarm and pressure switch, with water taken after the main water supply stop valve but before an alternate, a dry pipe or a pre-action alarm valve;
- c) any water flow alarm switch fitted after the control valve set, with water taken downstream of that flow alarm;
- d) the automatic starting device of a pump set;
- e) any sprinkler alarm flow switch in a pump house or pressure tank house that sits upstream of the control valve set.
Clause 15.5.2 Remote test valves (TS p.112 / EN p.109): a test facility is required: a test valve, together with its fittings and pipework, that gives a flow equal to what one sprinkler discharges, connected to a distribution pipe at its hydraulically most remote point.
This test valve is used to measure the water delivery time of dry and alternate installations: Clause 11.2.2 (TS p.70 / EN p.67) requires the maximum time between the opening of a single sprinkler and the discharge of water not to exceed the value in Table 18, and requires the test to be carried out with the remote test valve specified in 15.5.2. Table 18: 90 s for LH, 60 s for OH and HH.
15.6: Flushing connections
Clause 15.6 (TS p.112 / EN p.109): flushing connections, whether or not they have permanent valves, are required at the dead (spur) ends of the installation's distribution pipes. Their size must match the distribution pipe, except that a pipe larger than DN40 may take a DN40 flushing connection if it is taken off the underside of the pipe. Every flushing connection must be closed with a suitable plug.
According to the same clause, flushing connections serve not only for periodic flushing of the pipework: they may also be used to confirm that water is available and to run pressure and flow tests. The clause further warns that a rise in temperature can raise the pressure enough to damage pipework that is entirely full of water. Where an installation is likely to be fully vented of air, for example a gridded layout with flushing connections at its extremities, the fitting of pressure relief valves must be considered.
15.7: Pressure gauges
Clause 15.7.1 General (TS p.112 / EN p.109): the scale divisions of a pressure gauge must be no larger than a) 0.2 bar when the top of the scale is 10 bar or less, and b) 0.5 bar when the top of the scale is above 10 bar. The top of the scale must be roughly 150 % of the maximum pressure.
Clause 15.7.2 Water supply connections (TS p.112 / EN p.109): every town main connection needs a pressure gauge, the 'A' gauge, placed between the supply pipe stop valve and the non-return valve. Every pump set supply needs a damped pressure gauge on its supply pipe, placed just after the outlet non-return valve and before any outlet stop valve.
Clause 15.7.3 Control valve set (TS p.112 / EN p.109): a pressure gauge is required at each of these points:
- a) directly upstream of every control valve set (the 'B' gauge);
- b) directly downstream of every control valve set (the 'C' gauge);
- c) just after every alternate or dry subsidiary control valve set, before any stop valve.
Additional provision (TS p.113 / EN p.110): The 'B' gauge on dry alarm valves shall have an indicator showing the maximum pressure attained.
'B' is upstream, 'C' is downstream. Water enters the control valve set from the water supply side and leaves it on the installation side; on a vertical riser, therefore, 'B' is physically below the alarm valve and 'C' above it. The standard defines the gauges not as "upper" or "lower" but as upstream and downstream in the direction of flow.
Clause 15.7.4 Removal (TS p.113 / EN p.110): it must be possible to take out each pressure gauge without interrupting the installation's water or air supply.
The note below Table 6 (TS p.42 / EN p.39) shows the role of the 'C' gauge in the hydraulic calculation: ps is the static head loss in bar due to the height of the highest sprinkler in the array above the 'C' gauge of the control valve set.
Alarm devices: Clause 16
The alarm side of the control valve set is in Clause 16.
Clause 16.1.1 (TS p.113 / EN p.110): every control valve set must have a water motor alarm complying with EN 12259-4 plus an electrical device that signals the alarm remotely, both placed as close to the alarm valve as possible. A group of wet alarm valves may share one alarm motor and gong, on condition that the valves are in the same valve room and each alarm valve has an indicator showing when it operates. Each water motor alarm gong must carry the installation number in a prominent marking.
Clause 16.1.2 (TS p.113 / EN p.110): the water motor must be mounted so that the gong sits on the outer face of an exterior wall, with the gong's centre line at most 6 m above the point where the line connects to the alarm valve. Between the motor nozzle and the alarm valve connection a strainer must be fitted that is easy to reach for cleaning, and the water outlet must be arranged so that any water flow is visible.
Clause 16.1.3 (TS p.113 / EN p.110): the alarm line must be 20 mm galvanized steel or a non-ferrous metal. From the alarm valve to the water motor its equivalent length must not exceed 25 m, counting 2 m of equivalent length for every change of direction. The line needs a stop valve inside the premises and a permanent drain through an orifice not larger than 3 mm in diameter.
Clause 16.2.3 (TS p.114 / EN p.111): On dry and pre-action systems, each installation shall be provided with a low air/gas pressure alarm giving visual and audible warning in accordance with Annex I.
Installation type and size: Clause 11
The type of control valve set determines the type of installation.
Clause 11.1.1 (TS p.69 / EN p.66): a wet pipe installation is kept full of pressurized water at all times; it must only be used in premises with no risk of frost damage and where the ambient temperature stays at or below 95 °C. Grid and loop systems must always be wet pipe installations.
Clause 11.2.1 (TS p.70 / EN p.67): in a dry pipe installation the pipework after the dry alarm valve is normally held under air or inert gas pressure, while the side before the valve holds pressurized water. A permanent air/inert gas supply must be installed to keep the pipework at pressure. The installation pressure must lie inside the range that the alarm valve supplier recommends. A dry pipe installation must only be used where frost damage is possible or where temperatures above 70 °C occur, for example in drying ovens.
The standard gives no numerical value and no differential ratio for the air and water pressure in a dry system; it leaves the range to the alarm valve supplier.
Clause 11.3.1 (TS p.71 / EN p.68): Alternate installations incorporate either an alternate alarm valve or a composite set consisting of a wet and a dry alarm valve. During the winter months the pipework downstream of the alarm valve is charged with air or inert gas under pressure and upstream with water under pressure; during the rest of the year the system operates as a wet pipe installation.
Clause 11.4.1.2 Type A pre-action installation and 11.4.1.3 Type B (TS p.71 / EN p.68): in Type A the control valve set is actuated by an automatic fire detection system and not by the operation of the sprinklers; the air/inert gas pressure is monitored at all times and at least one quick opening manually operated valve is installed to actuate the pre-action valve in an emergency. In Type B the control valve set is actuated either by the detection system or by the operation of the sprinklers.
Clause 11.1.3, Table 17 (TS p.70 / EN p.67) gives the maximum protected area that a single control valve set may control in wet pipe and pre-action installations (including any sprinklers in a subsidiary extension):
| Hazard class | Maximum protected area per control valve set |
|---|---|
| LH | 10 000 m² |
| OH, including any LH sprinklers | 12 000 m² (except as allowed in Annexes D and F) |
| HH, including any OH and LH sprinklers | 9 000 m² |
Frost protection and monitoring
Clause 8.1.3 Protection against freezing (TS p.45 / EN p.42): The supply pipe and the control valve set shall be kept at a minimum temperature of 4 °C.
Annex H, H.2.2 Stop valves controlling the flow of water to sprinklers (TS p.156 / EN p.153): the position of all stop valves whose closure could prevent sufficient water flowing to the sprinklers shall be monitored, including water supply valves, control valve sets, subsidiary valves and section valves. For normally open valves the alarm shall be initiated as soon as the valve starts to close.
H.2.3 Other stop valves (TS p.156 / EN p.153): the position of all stop valves whose closure could prevent the correct operation of an alarm or indicating device (for example a pressure switch, a hydraulic alarm or a flow switch) shall be monitored; for normally open valves the alarm shall again be initiated as soon as the valve starts to close.
The standard gives no measure such as "the first quarter turn" here; the criterion is that the valve starts to close.
Annex H, H.1 (TS p.156 / EN p.153): every monitoring device must be protected to at least IP 54 according to EN 60529, and a common indication must not serve more than 15 non-addressable supervisory alarm devices.
Valves in maintenance
Clause 20.3.2.7 Stop valves (TS p.124 / EN p.121): in the quarterly routine, all stop valves controlling the flow of water to sprinklers shall be operated to make sure that they are in working order and securely refixed in the correct mode. This includes those on all water supplies, on the alarm valve and all zone or other subsidiary stop valves.
Clause 20.3.3.2 Dry alarm valves (TS p.124 / EN p.121): in the half yearly routine, the moving parts of the dry alarm valves on dry pipe installations and subsidiary extensions, and of any accelerators and exhausters, shall be moved in accordance with the supplier's instructions. NOTE: alternate installations need not be tested in this way, because they are already operated as a result of the changeover from wet to dry and back twice a year.
Clause 20.3.5.3 (TS p.125 / EN p.122): in the 3 year routine, all water supply stop valves, alarm valves and non-return valves shall be examined and, where necessary, replaced or overhauled.
Field note
Read together, the downstream stop valve exception in Clause 15.2 ("if monitored") and the "alarm as soon as the valve starts to close" requirement of Annex H.2.2 show that every isolation point on the installation side has to enter the monitoring architecture. Annex H.2.2 itself lists water supply valves, control valve sets, subsidiary valves and sectional valves. On projects that satisfy the two provisions separately but never connect them, a single unmonitored maintenance valve can blind the whole installation. (This paragraph is engineering commentary.)
Frequently Asked Questions
How does EN 12845 define the control valve set?
BS EN 12845+A2:2026 Clause 3.17 (TS p.20 / EN p.17): a control valve set is the assembly comprising an alarm valve, a stop valve and all associated valves and fittings for the control of a sprinkler installation. Clause 15.1 (TS p.110 / EN p.107) requires each installation to have a control valve set in accordance with EN 12259-2 or EN 12259-3.
What three requirements apply to stop valves?
Clause 15.2 (TS p.110 / EN p.107): every stop valve whose closure could interrupt the water supply to the sprinklers must close when turned clockwise, must carry an indicator that shows clearly whether it is open or closed, and must be locked in its correct position with a strap and padlock or by an equivalent means. In addition, apart from the cases the standard itself provides for, stop valves must not be fitted downstream of the control valve set; to make testing and maintenance easier, a downstream stop valve may be added only if it is monitored.
Where are the 'B' and 'C' gauges located?
Clause 15.7.3 (TS p.112 / EN p.109): a 'B' gauge must be fitted directly upstream of every control valve set and a 'C' gauge directly downstream of it; a further gauge is required just after every alternate or dry subsidiary control valve set, before any stop valve. The definitions are in Clauses 3.14 and 3.16: the 'B' gauge is connected to and at the same level as the alarm valve and indicates the pressure on the upstream side of the valve; the 'C' gauge indicates the pressure on the downstream side (TS p.19 / EN p.16).
How many control valve sets may a ring main section contain?
Clause 15.3 (TS p.110 / EN p.107): when the sprinkler systems on a site are supplied from a ring main, stop valves must be fitted that divide the ring into isolatable sections, and each section may contain at most 4 control valve sets.
When must a normally open stop valve raise an alarm?
Annex H, H.2.2 and H.2.3 (TS p.156 / EN p.153): the position of all stop valves whose closure could prevent sufficient water flowing to the sprinklers shall be monitored; for normally open valves the alarm shall be initiated as soon as the valve starts to close. The standard gives no number of turns and no percentage.
References
- BS EN 12845+A2:2026 Clauses 3.5-3.8 alarm valve types, 3.14 'B' gauge, 3.16 'C' gauge (TS p.19 / EN p.16)
- BS EN 12845+A2:2026 Clause 3.17 Control valve set (TS p.20 / EN p.17)
- BS EN 12845+A2:2026 Clause 8.1.3 Protection against freezing (TS p.45 / EN p.42)
- BS EN 12845+A2:2026 Clauses 11.1.1, 11.1.3, Table 17, 11.2.1, 11.2.2, Table 18 (TS p.69-70 / EN p.66-67)
- BS EN 12845+A2:2026 Clauses 11.3.1, 11.4.1.2, 11.4.1.3 (TS p.71 / EN p.68)
- BS EN 12845+A2:2026 Clauses 15.1, 15.2, 15.3, 15.4 (TS p.110 / EN p.107)
- BS EN 12845+A2:2026 Table 39 Drain valves, Clause 15.5.1 (TS p.111 / EN p.108)
- BS EN 12845+A2:2026 Clauses 15.5.2, 15.6, 15.7.1, 15.7.2, 15.7.3 (TS p.112 / EN p.109)
- BS EN 12845+A2:2026 Clause 15.7.3 dry alarm valve indicator, 15.7.4, 16.1.1, 16.1.2, 16.1.3 (TS p.113 / EN p.110)
- BS EN 12845+A2:2026 Clause 16.2.3 (TS p.114 / EN p.111)
- BS EN 12845+A2:2026 Clause 7.3.1, Table 6 and the ps note (TS p.42 / EN p.39)
- BS EN 12845+A2:2026 Clauses 20.3.2.7, 20.3.3.2 (TS p.124 / EN p.121), 20.3.5.3 (TS p.125 / EN p.122)
- BS EN 12845+A2:2026 Annex H, H.1, H.2.2, H.2.3 (TS p.156 / EN p.153)

SprinkCalc — Fire Sprinkler Design Across Three Standards
SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.
Download SprinkCalc on the App Store
MEP Calc — 110+ Engineering Calculators
MEP Calc bundles 110+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.
Download MEP Calc on the App StoreBS EN 12845+A2:2026 (EN 12845:2015+A2:2026) Fixed firefighting systems — Automatic sprinkler systems — Design, installation and maintenance; BS EN 12845-2:2025 (EN 12845-2:2024) ESFR and CMSA sprinkler systems. Every figure in this article is taken from the published standard text; clause, table and page references are listed under References. General information only, not a substitute for the standard or for a design review.