The anatomy of the control valve set: why the stop valve must be OS&Y or monitored, choosing between wet, dry, alternate and pre-action alarm valves, drains and test connections, tamper switch monitoring, and the "dead installation" error seen most often on site.

On an annual inspection at a textile warehouse we noticed something: the butterfly stop valve on the main control valve set showed its indicator arrow near the closed position, and the locking chain on the valve lever had secured it, by mistake, half shut. The installation had been running on half its water for three months and nobody had noticed — because it was not a monitored butterfly: no tamper switch, no rising stem. The control valve set clause in EN 12845 exists to prevent exactly this: stop valve, alarm valve, drain and test connections are designed as one assembly, with each part checking the others. This article opens the control valve set piece by piece.

What a control valve set is

EN 12845 defines the control valve set as the assembly comprising the alarm valve, the stop valve and all associated valves and accessories needed to operate the installation. One set per installation is mandatory, and its components must be certified to EN 12259-2 (wet alarm valve assemblies) or EN 12259-3 (dry alarm valve assemblies). An alarm valve alone, or a stop valve alone, is not a control valve set; it is expected to be supplied as a complete certified assembly.

A typical wet set is built on the riser in this order, top to bottom:

The order is not accidental. With the stop valve at the bottom, closing it allows the whole installation above to be drained for service; the gauge between alarm valve and stop valve reads the supply-side pressure independently. The gauge above gives the installation-side pressure; the difference between the two shows up as clapper loss and static head difference.

The stop valve: three golden rules

Three conditions apply to every stop valve capable of shutting off water to sprinklers:

  1. It closes clockwise — standardised so that an operator under pressure turns it the right way.
  2. It has a position indicator — open or shut must be clearly readable by eye. An OS&Y gate valve shows its stem outside, visible from a distance; a butterfly relies on the indicator arrow on the body, and that lever can mislead mechanically, so the monitored version is preferred.
  3. It is strapped and padlocked, or equivalently secured, in the correct position. The word "correct" is critical: usually that means open, but where a line is held shut for testing after draining, that position is what gets secured.

The standard also states that no stop valve is fitted downstream of the control valve set — with the exception that a monitored stop valve may be fitted for ease of maintenance. "Monitored" means a tamper switch mounted on the valve that produces an electrical signal on the smallest movement of the spindle towards closed.

OS&Y or monitored butterfly?

Both are accepted on site; the choice usually comes down to space and cost. The advantage of an OS&Y gate valve is that the position cannot be faked mechanically — the stem is out where you can see it. The disadvantages: it takes space, it is heavy and expensive, and large sizes need a gearbox to operate. A monitored butterfly is compact, light and cheap; but if the tamper switch fails, position is judged only by eye, and you fall into the half-shut trap described above. So where a monitored butterfly is chosen, wiring the tamper signal to the fire alarm panel and testing it is not negotiable.

Choosing the alarm valve type

EN 12845 defines four basic alarm valve types:

Type Holding medium Typical use EN 12259
WetWaterNo freezing risk, normal buildingsPart 2
DryCompressed air or nitrogenCold stores, car parks, roof voidsPart 3
AlternateWater or air by seasonBuildings wet in summer, dry in winterParts 2 and 3 combined
Pre-actionAir plus independent detectionData centres, archives, museums, where accidental discharge is unacceptablePart 3 (special)

A wet alarm valve works on a pressure balance: supply pressure below tries to lift the clapper, while installation pressure above — the water column plus the retard chamber — holds it shut. When a sprinkler opens, the pressure above falls, the balance breaks, the clapper lifts, water passes and the alarm line is fed. A retard chamber is added so that pump pressure fluctuations do not produce false alarms; it absorbs brief low-flow pressure drops while passing the continuous flow of a genuine sprinkler operation.

In a dry valve the balance is reversed: a modest air pressure (2–3 bar) over a much larger clapper area holds back a much higher water pressure (around 10 bar) — the differential design. That is why a maximum pressure indicator (drag pointer) is added to the gauge on a dry valve, so that any unexpected water entry into the dry side leaves a trace.

Drain and test valves

The drain valve does more than empty the installation for maintenance; it also performs the main drain test below the alarm valve. Fully opened, the flow passing from the supply side is measured together with the drop on the supply gauge — the simplest test of whether the water supply still delivers its expected capacity.

Section protected by the drain valveMin. size (mm)
LH installation40
OH / HHP / HHS installation50
Subsidiary installation50
Zone50
Trapped distribution pipe, ≤ DN8025
Trapped distribution pipe, > DN8040
Trapped range pipes25
Test pipe between dry/alternate valve and the stop valve below15

The drain outlet sits no more than 3 m above floor level and is plugged. Visibility matters too — the operator must see the water actually flowing during a test; routing it into a drain out of sight is not enough.

The 15 mm test valves:

Tamper switches and position monitoring

In practice, tamper contacts go on: the main control valve set stop valve, each zone stop valve, sectional stop valves on the ring main, the pump suction and discharge stop valves, and the tank fill valve. All of them should appear as separate zones on the fire alarm panel, with an alarm generated within the first quarter turn towards closed. At annual maintenance the tamper contact is tested by hand — closing the valve slightly on purpose and confirming the signal reaches the panel.

Comparison with NFPA 13

NFPA 13 uses the term control valve assembly and requires the same components: indicating control valve, alarm valve (wet, dry, pre-action or deluge), main drain, alarm test connection and inspector's test connection. Some differences:

The five most common field errors

  1. The "dead installation" — a half-shut stop valve. An unmonitored butterfly with the locking chain in the wrong position. The fix: monitor every main and zone stop valve and test the tamper signal at the panel.
  2. A blocked or hidden drain outlet. The plug has not been removed since installation and the outlet is full of silt. You discover it when the main drain test shows flow down by half.
  3. Supply and installation gauges swapped. If the upper gauge reads supply pressure, the installation is reversed and you cannot interpret the clapper loss. Know the riser schematic by heart.
  4. Missing detection integration on a pre-action panel. The pre-action valve is fitted but the detector loop is not wired to the panel, so the valve trips only on manual release. An end-to-end test at commissioning is essential.
  5. A wet alarm valve in a freezing area. The valve room is uninsulated or unheated. The feed pipe and control valve set must be kept at a minimum of 4 °C; if that cannot be achieved, either heat the valve room or move to a dry or alternate set.

Turkish context

BYKHY ties sprinkler installations to TS EN 12845. In practice, fire brigade and insurance inspections look for an EN 12259-2/3 certified control valve set, working gauges, drain and alarm test lines, and every stop valve wired to the fire alarm panel through a tamper switch. On industrial projects, FM Global approved sets are accepted directly; on conventional projects an EN 12259 approval is sufficient. At commissioning, the main drain test, the alarm test valve test (gong and pressure switch) and the remote test valve test must be recorded in writing; insurers may ask for those records later.

One point deserves repeating: the control valve set is both the heart of the system and its panic door. It is what lets water through when there is a fire, and it is what can leave a building unprotected during maintenance. That is why every sub-clause is written around safety — there is no line item in the set design you can wave through as a small detail.

Frequently Asked Questions

Why must the stop valve be monitored?

So that a half-shut valve cannot go unnoticed. A tamper switch signals within the first quarter turn towards closed, and that signal must reach the fire alarm panel.

What is a retard chamber for?

It absorbs brief pressure drops from pump fluctuation so they do not raise a false alarm, while passing the continuous flow of a genuine sprinkler operation.

How large must the main drain be?

40 mm on an LH installation and 50 mm on OH, HHP and HHS installations, with smaller sizes for trapped pipework.

What is the main drain test?

Opening the drain fully and reading the flow together with the drop on the supply gauge — the simplest check that the water supply still delivers its expected capacity.

SprinkCalc — Fire Sprinkler Design Across Three Standards

SprinkCalc covers hazard classification, design density and area, K-factor selection, water demand and hydraulic calculations for NFPA 13, FM Global and BS EN 12845 in a single iOS app, and exports a professional PDF report.

Download SprinkCalc on the App Store

MEP Calc — 86+ Engineering Calculators

MEP Calc bundles 86+ engineering modules in one iOS app: 21 fire calculations plus heating, cooling, HVAC, plumbing, steam and natural gas.

Download MEP Calc on the App Store
Standards & References

BS EN 12845:2015+A1:2019 Fixed firefighting systems — Automatic sprinkler systems. EN 12845-2:2024 (CMSA & ESFR sprinkler systems). NFPA 13 Standard for the Installation of Sprinkler Systems. Turkish Regulation on Fire Protection of Buildings (BYKHY). FM Global Property Loss Prevention Data Sheet 2-0.

FS

Fatih Selvi

Mechanical engineer and software developer with field experience in MEP and fire protection, working actively with NFPA, FM Global and BS EN 12845 on site projects.